FMU Technical Manual
5.3 FMU_DataExchange
45
ErrEvent
Explanation
Source of error
Recommendation
70
Input address configured for one unit
exceeds the possible address range of
3584 bytes.
Configuration
The process data image is
limited to 3584 bytes.
71
One predefined connection type is
unknown.
Configuration
Support of cyclic, polled, change
of state, bit strobed only.
72
Multiple connections defined in
parallel.
Configuration
Supports only one type of
connection to one device.
73
The value configured for the expected
packet rate value configured is less
than the value for production inhibit
time.
Configuration
The value for the expected
packet rate must be larger than
the production inhibit time.
In Control Configurator FM,
check the settings for the slave's
poll connection configuration.
5.3.1.3 GlobalBusStateField for CANopen
Identifier part
Identifier
Explanation
Global bits
GlobBit_Status
Lower byte of the WORD. Details follow the table.
Status
GlobBit_Status
Higher byte of the WORD.
The master system can be in one of the following states:
•
16#00:
OFFLINE
•
16#40:
STOP
•
16#80:
CLEAR
•
16#C0: OPERATE
Error remote address
ErrRemAddr_ErrEvent
Lower byte of the WORD.
If the global bits "control error, auto-clear error or
non-exchange error" are set, indicates the address of
the node. If the error occurs in the FMU, the value is 255.
Otherwise the faulty node address is stored.
Error event
ErrRemAddr_ErrEvent
Higher byte of the WORD.
Each error is assigned a number, which are explained
following the table.
Bus error count
BusErrorCnt
Counts how many times bus error limits are exceeded.
Timeout count
TimeOutCount
Counts the number of CAN chip reinitializations.
Message Time Out
MoreInformation
ARRAY [0] of WORD.
Number of cancelled CAN messages because partner
did not acknowledge.
Содержание FMU
Страница 1: ...programmable logic controller FMU Technical Manual ...
Страница 3: ......
Страница 9: ......
Страница 10: ...Chapter 1 Features and Restrictions ...
Страница 13: ......
Страница 14: ...Chapter 2 Parts and Functions ...
Страница 23: ......
Страница 24: ...Chapter 3 Specifications ...
Страница 30: ...Chapter 4 Installation and Wiring ...
Страница 42: ...Chapter 5 Programming Information for Control FPWIN Pro ...
Страница 70: ...Chapter 6 Outline Dimensions ...
Страница 73: ......
Страница 76: ...Record of Changes Manual No Date Description of changes ACGM0161V10EN July 2008 First edition ...