170
Operation Manual
FT1020G3 Rev 2.10.4
32.2
Battery Maintenance
The batteries 2 x 12 V (battery size is dependent on the backup requirement), are placed
inside the Control Unit. Larger batteries (
≤
65 AH) can be placed in a separate battery box
attached to the FT1020G3 cabinet.
The Control Unit charges the batteries and continuously monitor its condition, a fault will
be generated when the batteries are disconnected or outside the specified limits.
The batteries are rechargeable Sealed Lead-Acid batteries, it must be approved batteries
by CSIRO. The batteries are normally maintenance-free but the manufacturer's instructions
should always be followed.
The ambient temperature affects the battery's capacity, self-discharge and life span. The
temperature should preferably not be higher than normal room temperature (approx. 20-
22°C). For highest safety, the batteries used in a fire alarm installation should be changed
after two year or load test the batteries yearly.
CAUTION:
Risk of explosion may occur if batteries are replaced by incorrect type. Dispose
used batteries according to the producer's instructions and national regulations.
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...