109
Operation Manual
FT1020G3 Rev 2.10.4
21.3.1
Memory fault
In case of a fault in the Main board S/W (system program) or the MMI board S/W, the
following fault message will be shown:
(Main board software.)
(MMI board software.)
(Not shown in the display, only via EBLWin, Gateway / Web-server or via another unit in
the system).
This is also indicated by LED "System fault" and the buzzer sounds steady (continuous).
The Fault TX output is "activated".
A new download of the S/W (system programs) is required and/or the Main board and/or
the MMI board have to be replaced.
Note:
After
SSD download,
the following messages may be shown:
After restart:
This means that the SSD has
not
been successfully downloaded. A new SSD download
has to be performed.
FAULT: Checksum MMI program, Control Unit xx
No contact with Main board
FAULT: Restart Control Unit nn, code xx,
address yyyyyyyyy
FAULT: Checksum system program, Control Unit xx
FAULT: No connection with MMI board, Control Unit xx
Checksum fault in downloaded data.
Control unit will now restart.
FAULT: Site specific data (SSD), control unit xx
Содержание Firetracker FT1020G3 CIE
Страница 1: ...Operation Manual FT1020G3 Rev 2 10 4 For Software V2 10 4 FT1020G3 FDCIE MA430 March 2023...
Страница 2: ...This page has deliberately been left blank...
Страница 174: ...174 Operation Manual FT1020G3 Rev 2 10 4 Figure 22 19 Rack 22U FT1020G3 General Arrangement with 6U battery box...
Страница 175: ...175 Operation Manual FT1020G3 Rev 2 10 4 Figure 23 19 Rack 13U FT1020G3 General Arrangement with 6U battery box...
Страница 176: ...176 Operation Manual FT1020G3 Rev 2 10 4 Figure 24 FT1020G3 Standard Block Wiring Diagram...
Страница 177: ...177 Operation Manual FT1020G3 Rev 2 10 4 Figure 25 FT1020G3 New 5012 PCB Layout...