36
Installation Manual
Grid (Utility) Connection
WARNING:
To reduce the risk of injury, use the recommended
wire size above. It is very important for system safety and
efficient operation to use the appropriate wire for grid (utility)
connection.
WARNING:
To prevent the risk of electric shock, make sure
the ground wire is properly earthed before operating this unit
whether the grid is connected or not.
ASSEMBLY (Continued)
5. GRID (UTILITY) CONNECTION
There is an AC (Grid) circuit breaker in the distribution box. This will
ensure the inverter can be safely disconnected during maintenance and
is fully protected from overcurrent of AC input.
Installing an essential load panel provides backup power to connected
circuits. There are two interlocked AC breakers to the essential loads
inside the distribution box. One AC breaker labeled “FROM INVERTER” is
for normal inverter operation. The other breaker labeled “FROM GRID”
bypasses the “AC GRID” breaker and connects the essentials loads
directly to the “Grid Input” terminals.
Note: If the inverter needs to be repaired this breaker can be used to
supply the essential load when the inverter has been taken off-line.
This bypass can also be used while a customer waits for Permission to
Operate from their utility or local Authority Having Jurisdiction.
ESSENTIAL LOAD MAX
POWER
NOMINAL VOLTAGE
WIRE SIZE
Torque
5.5 kW
2.75 kW
240 VAC
120 VAC
Rated for 30 AAC
Rated for 30 AAC
N/A, Spring Connectors
N/A, Spring Connectors
L1 -
L2 -
N -
GND -
Black
R ed
White
Green
240V/120V 60HZ SPLI
T -PH A SE S Y S TEM (U S A)
L1
L1
L2
L2
GND
N
N
L1
N
L2 GND
120V
120V
240V
120V
120V
240V
Grid Terminals
L oad Terminals
L1 -
L2 -
N -
GND -
Black
R ed
White
Green
240V/120V 60HZ SPLI
T -PH A SE S Y S TEM (U S A)
L1
L1
L2
L2
GND
N
N
L1
N
L2 GND
120V
120V
240V
120V
120V
240V
Grid Terminals
L oad Terminals
USA: 240V/120V (60Hz) SPLIT-PHASE SYSTEM
AC GRID
UTILITY
TYPE
Содержание EverVolt EVAC-105-6
Страница 1: ...V 01012021 Installation Service Manual FOR AC AND DC COUPLED EVERVOLT SYSTEMS ...
Страница 65: ...65 Installation Manual Operation and Display Panel ...
Страница 76: ...76 Installation Manual Configuring the Hardware PV INPUT IS ONLY USED FOR EVERVOLT DC COUPLED SYSTEM ...
Страница 83: ...83 Installation Manual Step 5 Install the Generator wire ...