EBL512 G3 V. 3.0.X
- FIRE ALARM SOLUTIONS OPERATING INSTRUCTIONS
52
When "All" or "Single" reset is used, "automatic disablement" (encapsulation function) can be used by
pressing "Reset" (P3) and approx. 0.1 sec. later also press "Alarms queued" and hold them pressed for >
0.5 sec.
Reset via an AA unit is possible only during the investigation time and of AA alarm(s) only (not normal fire
alarms). If more than one AA alarm is activated, they will be reset all at a time.
19.2.3. SINGLE WITH AUTOMATIC DISABLEMENT
Like "Single reset" but incl. the so called encapsulation function: Normally when an alarm point or zone having activated fire alarm is
reset whilst still is in alarm status, it will activate a new fire alarm within 20 seconds. (This is in accordance with the EN54-2 stan
-
dard.)
When "Single with automatic disablement" reset is performed, an alarm point or zone, still in alarm status, will not only be reset but
also disabled, which means it will not activate a new fire alarm.
It has to be re-enabled via menu H2/B1 before it can activate a new fire alarm. (This function, set via EBLWin, is a violation to the
EN54-2 standard.)
LED Fault / Disablements "General disablements" is indicating one or more disablements in the system.
The alarm point or the whole zone (conventional) currently shown in the middle of display with large digits will be reset and disabled.
19.3. TEST MODE ALARM
Test mode alarm is automatically reset after approximately 10 seconds.
19.4. HEAVY SMOKE / HEAT ALARM RESET
If a heavy smoke / heat alarm has been activated, it will be reset at the same time as the corresponding fire alarm is reset. Also the
output(s) will be reset, i.e. de-activated.
19.5. ALERT ANNUNCIATION
Regarding the function, see section
18.1.4. ALERT ANNUNCIATION ALARM (AA ALARM)
on page 43 and EBL512 G3 Planning
Instructions, chapter "Alert annunciation". Reset of the AA alarm(s) can be done via push button "Reset" on a display unit 5054 or in
the c.i.e.