Operating Instructions
Intelligent Controller
96
Settings for energy saving
Energy saving
The “Demand/peak shaving settings” screen
A:
[Select all]/[Clear all] buttons
[Select all]
Select all outdoor units.
[Clear all]
Cancel selection of all outdoor units.
B:
This switches between “Display” and “Address” each time you touch it.
C:
The outdoor units with a check mark next to them will be the subject of the changes to the settings.
D:
The outdoor time slot demand setting is enabled for the selected outdoor unit if you put a check mark here.
This is linked with
the “Demand/peak shaving V
alid” (“Setting”
dialogue) (P
.95) setting.
E:
The “Setting” dialogue is displayed when you touch this.
A
B
D
E
C
Suppressing the consumption of electricity/gas [Demand/peak shaving settings]/[Peak cut settings]
97
Settings for energy saving
Energy saving
Control operation at regular intervals
[I/D unit cyclic]
This type of control rotates through the set times slots at the
specified intervals (3
minutes, 4
minutes,
5
minutes), evenly operating the indoor units in the control groups using the settings (OFF
, thermostat,
mode, set temperature) and recovering.
3
Put a check mark in the “Select” column (3-1), and touch [Set.] (3-2).
z
The “Setting” dialogue is displayed.
3-
1
3-
2
4
Change the settings.
Item
Explanation
Control Gr
. 1
-10
Press
to set the control group that
the indoor unit is to be allocated to. (Up to 10
groups)
Set from “Gr
.1” to “Gr
.10”.
Ope.
Operation of the indoor units is stopped. Set either [OFF] or [----]*.
T/S
The thermostat is set to of
f forcibly
.
Select between [T/S OFF] and [----]*.
Continued on next page
1
Touch [Demand setting] in “EnergySaving”.
1
2
Touch [I/D unit cyclic].
z
The “I/D unit cyclic” screen is displayed.
2
y
When using cycling control at 5
minute intervals on the indoor
units in control groups
1 to 5
Control groups
1 to 3 are “T/S OFF” and control groups
4 and 5 are
“Fan”, and if the interval is “5
min.”, the cycling control happens at
5
minute intervals.
5
min.
5
min.
5
min.
5
min.
5
min.
Thermostat forced OFF
Thermostat forced OFF
Normal operation
Normal operation
Normal operation
Normal operation
Normal operation
Normal operation
Normal operation
Fan
Fan
Thermostat forced OFF
Normal operation
Control group
1
Control group
2
Control group
3
Control group
4
Control group
5
TGR-318_ENG.indb 94