ー
59
ー
Operating Instructions
Intelligent Controller
26
Check the status of air conditioning units
Operation/Status
Changing the settings on the indoor unit
You can select indoor units to change settings, for example, start or stop them, or change their set temperature, etc.. Change settings in the “Settings” dialogue. You can also select multiple indoor units and operate them using the same settings.
4
Touch [Operation].
z
The “Settings” dialogue is displayed.
4
Note
y
There may be dif
ferences in the items you can set in the
“Settings” dialogue, depending on the model of the indoor unit.
y
When you have selected multiple units, setting items in common are displayed in the “Settings” dialogue.
5
Change the settings of the items.
Common display area
Operation display area
Select an item from the common display area and set the operation in the operation display area.
Item
Explanation
ON/OFF
Set whether to start or stop operation.
1)
Touch [ON/OFF].
2)
Select “ON” or “OFF”.
Mode
Set the operating mode.
1)
Touch [Mode].
2)
Select the operating mode (
(heating),
(drying),
(cooling),
(fan),
(automatic)).
Continued on next page
1
Touch [Operation/Status] in “Oper
./
Status”.
1
2
Touch [I/D unit list].
z
The “I/D unit list” screen is displayed.
2
3
Put a check mark in the “Select” column.
z
Select the indoor units whose settings you want to change.
z
You can touch [Select all] to change the settings in a batch.
3
27
Check the status of air conditioning units
Operation/Status
Item
Explanation
Set temp.
Set the temperature.
1)
Touch [Set temp.].
2)
Set the temperature with
and
.
(± in 1
°C steps)
<Setting ranges>
y
In cooling or drying mode: Between 18
°C and 30
°C
y
In heating mode: Between 16
°C and
30
°C*
1
y
Automatic: Between 17
°C and 27
°C
*1
The upper limit for gas heat pump air conditioners is 26
°C.
Fan SPD
Set the strength of the fan.
1)
Touch [Fan SPD].
2)
Select the fan speed (
(high),
(mid),
(low),
(automatic)).
Flap
Set the direction of the airflow
.
1)
Touch [Flap].
2)
Set the flap to the desired position (
(F1),
(F2),
(F3),
(F4),
(F5),
(Swing)).
Touch
during the
swing to stop the flap
at the desired position.
y
Heating, fan, and automatic (heating) can be adjusted in 5 steps and cooling and dry can be adjusted in 3 steps.
y
You can set either
or
if the
model does not support airflow direction
settings.
Prohibitn.*
2
Set whether to allow or prohibit use of the local remote controller
.
1)
Touch [Prohibitn.].
2)
Use
to select from “Accept”,
“Prhbt1”, “Prhbt2”, “Prhbt3”, or “Prhbt4”. Accept:
Allows operations with the remote
controller
.
Prhbt1 to Prhbt4: Operations on the remote controller are restricted.
You can
change the restricted operations. (→P
.185)
Eco
Enable or disable energy saving operation.
1)
Touch [Eco].
2)
Select “V
alid” or “Invl”.
Enable or disable ECONA
VI setting.
1)
Touch
.
2)
Select “V
alid” or “Invl”.
*2
Example of prohibiting or enabling remote controller use (factory setting)
ON/OFF
Mode
Set temp.
Fan SPD
Flap
Eco
Accept
Prhbt1
Prhbt2
Prhbt3
Prhbt4
: Operation and setting with the remote controller is possible
: Operation and setting with the remote controller is not possible
6
Touch [T
ransmit].
z
The settings are registered and the “Settings” dialogue closes.
z
To cancel the settings, touch [Cancel].
6
Note
y
Touch
(or
) at the upper value (or lower value)
of the
set temperature and the set value becomes a blank (no setting). Make the setting blank when you want no setting.
Furthermore, touch
(or
) and the upper value (or lower
value) is displayed.
For example:
If upper value 30
°C and lower value 18
°C (when
cooling)
19
°C
18
°C (lower limit value)
(blank)
30
°C (upper limit value)
29
°C
Changing the settings on the indoor unit
TGR-318_ENG.indb 59
2017/04/06 10:42:58