8.13. Soft starter (Applicable only for C24BK Australia market)
A. Purpose
To reduce starting current lower than 45A.
B. Basic Operation
1. When indoor relay is turn ON, starting capacitor will be turn ON through RY-C for ~ 1 second. After that reactor will be turn
OFF through RY-L and in the same time RY-C will turn OFF causes starting capacitor to be OFF.
2. When the unit operation ON by remote controller or thermostat OFF
→
ON the starter kit will be functioned.
3. When the unit operation OFF
→
ON by the inner protector, the starter kit will be not function, mean the unit will be ON as
a normal operation.
28
CS-C18BKP CU-C18BKP5 / CS-C18BKP CU-C18BKP6 / CS-C24BKP CU-C24BKP5 / CS-C24BKP CU-C24BKP6