Panasonic CS-UE12QKE Скачать руководство пользователя страница 1

© Panasonic Corporation 2013.

 

Order No: PAPAMY1312039CE 

 

 
 

Indoor Unit 

Outdoor Unit

(YE9/12QKE)

(UE9/12QKE)

(UE18QKE)

MODE

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1

2

3

FAN SPE E D

SE T

CHE CK

CLOCK

RE SE T

AC

RC

AUT O

HE AT

COO L

DRY

AIR SWING

FAN

SPEED

AIR

SWING

MODE

TEMP

OFF/ON

TIMER

SET

CANCEL

ON

OFF

1

2

3

AIR SWING

FAN SPE ED

SE T

CHE CK

CLOCK

RE SE T

AC

RC

FAN
SPE E D

AIR

SWING

AUT O

HE AT

COO L

DRY

 

CS-YE9QKE 

CS-YE12QKE 

CS-UE9QKE 

CS-UE12QKE 
CS-UE18QKE 

 
 

CU-YE9QKE

CU-YE12QKE

CU-UE9QKE

CU-UE12QKE
CU-UE18QKE

Destination

Europe

E.Europe

Turkey

 

 

 

 

 

 

 

PRECAUTION OF LOW TEMPERATURE 

In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.

 

 

WARNING 

This service information is designed for experienced repair technicians only and is not designed for use by the general public. 

It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. 

Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to 

service or repair the products dealt with in this service information by anyone else could result in serious injury or death. 

Содержание CS-UE12QKE

Страница 1: ...urope E Europe Turkey PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to advise non technical individuals of potentia...

Страница 2: ...on Panel 50 13 Protection Control 51 13 1 Protection Control For All Operations 51 13 2 Protection Control For Cooling Soft Dry Operation 53 13 3 Protection Control For Heating Operation 54 14 Servicing Mode 55 14 1 Auto OFF ON Button 55 14 2 Remote Control Button 56 15 Troubleshooting Guide 57 15 1 Refrigeration Cycle System 57 15 2 Relationship Between The Condition Of The Air Conditioner And Pr...

Страница 3: ...D Otherwise it may cause electrical shock and fire in case equipment breakdown or insulation breakdown 10 Do not use joint cable for indoor outdoor connection cable Use the specified Indoor Outdoor connection cable refer to installation instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor outdoor connection Clamp the cable so that no external force will be acted on the t...

Страница 4: ...ng point is 50 F 70 F 30 C 40 C higher Please use a high temperature solder iron In case of the soldering iron with temperature control please set it to 700 20 F 370 10 C Pb free solder will tend to splash when heated too high about 1100 F 600 C 7 Power supply connection to the room air conditioner Use power supply cord 3 1 5 mm 1 0 1 75HP 3 2 5 mm 2 0 2 5HP type designation 60245 IEC 57 or heavie...

Страница 5: ...22 42 30 22 Indoor Noise Power Level dB 57 58 dB A 47 48 Cooling Outdoor Noise Power Level dB 62 63 kW 0 80 3 30 4 10 0 80 4 00 5 10 BTU h 2730 11300 14000 2730 13600 17400 Capacity kcal h 690 2840 3530 690 3440 4390 Running Current A 3 80 4 90 Input Power W 195 860 1 18k 200 1 10k 1 47k W W 4 10 3 84 3 47 4 00 3 64 3 47 BTU hW 14 00 13 14 11 86 13 65 12 36 11 84 COP kcal hW 3 54 3 30 2 99 3 45 3 ...

Страница 6: ...Removal L h Pt h 1 5 3 2 2 0 4 2 Cool m 3 min ft 3 min 5 74 203 5 69 201 QLo Heat m 3 min ft 3 min 7 03 248 6 79 240 Cool m 3 min ft 3 min 6 68 236 7 59 268 Lo Heat m 3 min ft 3 min 7 62 269 8 85 313 Cool m 3 min ft 3 min 9 22 326 9 94 351 Me Heat m 3 min ft 3 min 10 22 361 10 50 371 Cool m 3 min ft 3 min 11 7 415 12 3 435 Indoor Airflow Hi Heat m 3 min ft 3 min 12 8 450 12 8 450 Cool m 3 min ft 3...

Страница 7: ...on Range Heating Minimum C 10 11 10 11 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet Bu...

Страница 8: ...22 Indoor Noise Power Level dB 57 58 dB A 47 48 Cooling Outdoor Noise Power Level dB 62 63 kW 0 80 3 30 4 10 0 80 4 00 5 10 BTU h 2730 11300 14000 2730 13600 17400 Capacity kcal h 690 2840 3530 690 3440 4390 Running Current A 3 80 4 90 Input Power W 195 860 1 18k 200 1 10k 1 47k W W 4 10 3 84 3 47 4 00 3 64 3 47 BTU hW 14 00 13 14 11 86 13 65 12 36 11 84 COP kcal hW 3 54 3 30 2 99 3 45 3 13 2 99 P...

Страница 9: ...Pt h 1 5 3 2 2 0 4 2 Cool m 3 min ft 3 min 5 74 203 5 69 201 QLo Heat m 3 min ft 3 min 7 03 248 6 79 240 Cool m 3 min ft 3 min 6 68 236 7 59 268 Lo Heat m 3 min ft 3 min 7 62 269 8 85 313 Cool m 3 min ft 3 min 9 22 326 9 94 351 Me Heat m 3 min ft 3 min 10 22 361 10 50 371 Cool m 3 min ft 3 min 11 7 415 12 3 435 Indoor Airflow Hi Heat m 3 min ft 3 min 12 8 450 12 8 450 Cool m 3 min ft 3 min 32 1 11...

Страница 10: ...ion Range Heating Minimum C 10 11 10 11 1 Cooling capacities are based on indoor temperature of 27 C Dry Bulb 80 6 F Dry Bulb 19 0 C Wet Bulb 66 2 F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet B...

Страница 11: ... 44 37 Indoor Noise Power Level dB 60 dB A 48 Cooling Outdoor Noise Power Level dB 63 kW 0 98 5 40 7 70 BTU h 3340 18400 26300 Capacity kcal h 840 4640 6620 Running Current A 6 70 Input Power W 350 1 47k 2 30k W W 2 80 3 67 3 35 BTU hW 9 54 12 52 11 43 COP kcal hW 2 40 3 16 2 88 Pdesign kW 4 0 Tbivalent C 10 SCOP W W 4 3 Annual Consumption kWh 1302 ErP Class A Power Factor 95 dB A H L 44 37 Indoor...

Страница 12: ... Hi Heat rpm 850 Moisture Removal L h Pt h 2 8 5 9 Cool m 3 min ft 3 min 12 65 447 Lo Heat m 3 min ft 3 min 14 25 503 Cool m 3 min ft 3 min 14 45 510 Me Heat m 3 min ft 3 min 16 05 567 Cool m 3 min ft 3 min 16 30 575 Indoor Airflow Hi Heat m 3 min ft 3 min 17 90 630 Cool m 3 min ft 3 min 34 4 1215 Outdoor Airflow Hi Heat m 3 min ft 3 min 34 0 1200 Control Device Expansion Valve Refrigerant Oil cm ...

Страница 13: ... F Wet Bulb and outdoor air temperature of 35 C Dry Bulb 95 F Dry Bulb 24 C Wet Bulb 75 2 F Wet Bulb 2 Heating capacities are based on indoor temperature of 20 C Dry Bulb 68 F Dry Bulb and outdoor air temperature of 7 C Dry Bulb 44 6 F Dry Bulb 6 C Wet Bulb 42 8 F Wet Bulb 3 Heating low temperature capacity Input Power and COP measured at 230 V indoor temperature of 20 C outdoor 2 1 C 4 Heating ex...

Страница 14: ...tances refrigerant R410A Long Installation Piping o CS CU YE9 12QKE CS CU UE9 12 18QKE long piping up to 15 meters Easy to use remote control Quality Improvement o Random auto restart after power failure for safety restart operation o Gas leakage protection o Prevent compressor reverse cycle o Inner protector to protect compressor Serviceability Improvement o Breakdown Self Diagnosis function ...

Страница 15: ...INDICATOR POWER Green TIMER Orange 4 2 Outdoor Unit 4 3 Remote Control MODE TEMP OFF ON TIMER SET CANCEL ON OFF 1 2 3 FAN SPEED SET CHECK CLOCK RESET AC RC AUTO HEAT COOL DRY AIR SWING FAN SPEED AIR SWING MODE TEMP OFF ON TIMER SET CANCEL ON OFF 1 2 3 AIR SWING FAN SPEED SET CHECK CLOCK RESET AC RC FAN SPEED AIR SWING AUTO HEAT COOL DRY Check Timer setting Airflow direction selection Fan speed sel...

Страница 16: ...n Left piping hole Remote Control Remote Control Holder 22 47 134 61 51 870 1 2 1 2 214 61 45 Right piping hole 290 214 125 115 60 60 410 41 61 Gas side Liquid side Relative position between the indoor unit and the installation plate Front View Right piping hole Left piping hole 497 2 Indoor unit external dimensions line Installation plate Unit mm 16 5 264 2 128 439 432 128 43 95 241 5 241 5 128 ...

Страница 17: ...piping hole Top View Bottom View Front View Back View 240 290 240 Right piping hole 1 2 1070 1 2 115 60 125 60 41 61 410 Relative position between the indoor unit and the installation plate Front View 264 3 Unit mm Right piping hole Left piping hole Installation plate Indoor unit external dimensions line 128 128 241 5 241 5 74 128 8 539 532 169 219 13 3 Remote Control Transmitter Remote Control Ho...

Страница 18: ...ew Front View Side View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100 mm 100 mm 1000 mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 69 6 18 61 6 542 11 5 289 24 4 104 7 60 5 155 84 8 34 5 570 104 9 780 67 6 ...

Страница 19: ...de View Side View Anchor Bolt Pitch 330 540 Space necessary for installation 100mm 100mm 1000mm Unit mm 3 way valve at Gas side Low Pressure 2 way valve at Liquid side High Pressure 22 124 62 6 330 622 167 97 69 20 62 32 540 160 824 68 7 37 299 ...

Страница 20: ...OUTDOOR INTAKE AIR TEMP SENSOR PIPE TEMP SENSOR LIQUID SIDE 2 WAY VALVE 3 WAY VALVE GAS SIDE COOLING HEAT EXCHANGER EVAPORATOR HEATING COMPRESSOR 4 WAYS VALVE CONDENSER MUFFLER MUFFLER STRAINER EXPANSION VALVE Not a standard replacement part ...

Страница 21: ...CU UE9QKE CS UE12QKE CU UE12QKE 1 FUSE101 FUSE104 REACTOR FUSE102 RY PWR PTC1 PTC NTC TH3 CT102 4 WAYS VALVE RY AC FUSE103 IC19 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N SINGLE PHASE POWER SUPPLY 1ø 230V 50Hz NOISE FILTER U ...

Страница 22: ...103 RY PWR NTC TH1 CT101 C103 4 WAYS VALVE FUSE101 IC19 MS 3 MS 3 RY PWR RY PWR2 FUSE301 TEMP FUSE TEMP FUSE SC L U M INDOOR UNIT OUTDOOR UNIT SC 2 3 N SINGLE PHASE POWER SUPPLY 1ø 230V 50Hz NOISE FILTER U PTC1 PTC RY AC FUSE104 REACTOR ...

Страница 23: ...OUNDING TERMINAL L N SINGLE PHASE POWER SUPPLY 1ø 230V 50Hz ELECTRONIC CONTROLLER MAIN UP DOWN LOUVER MOTOR CN STM1 WHT BR 1 5 1 5 R O M Y P REMARKS B BLUE P PINK BR BROWN O ORANGE BL BLACK Y YELLOW W WHITE G GREEN R RED Y G YELLOW GREEN CN DISP YLW CN DISP WHT ELECTRONIC CONTROLLER DISPLAY RECEIVER 1 5 6 1 W W W W W NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT COMMUNICATION CIRCUIT TO OUTDOOR UNIT ...

Страница 24: ...ONIC CONTROLLER MAIN UP DOWN LOUVER MOTOR CN STM1 WHT BR 1 5 1 5 R O M Y P LEFT RIGHT LOUVER MOTOR CN STM2 YLW BR 1 5 1 5 R O M Y P REMARKS B BLUE P PINK BR BROWN O ORANGE BL BLACK Y YELLOW W WHITE G GREEN R RED Y G YELLOW GREEN CN DISP YLW CN DISP WHT ELECTRONIC CONTROLLER DISPLAY RECEIVER 1 5 6 1 W W W W W NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT COMMUNICATION CIRCUIT TO OUTDOOR UNIT PIPING TE...

Страница 25: ...E102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT RECTIFICATION CIRCUIT RED RED TRADE MARK BLUE BLU YELLOW YLW COMP TERMINAL ELECTRO MAGNETIC COIL EXPANSION VALVE CN STM WHT 1 6 M REMARKS BLACK BLK RED RED WHITE WHT BROWN BRW YELLOW YLW GREEN GRN ORANGE ORG GRAY GRY BLUE ...

Страница 26: ...E 1 3 CN HOT WHT CN TH1 WHT P N SWITCHING POWER SUPPLY CIRCUIT FUSE103 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT RECTIFICATION CIRCUIT RED RED TRADE MARK BLUE BLU YELLOW YLW COMP TERMINAL ELECTRO MAGNETIC COIL EXPANSION VALVE CN STM WHT 1 6 M REMARKS BLACK BLK RED RED WHITE WHT BROWN BRW YELLOW YLW GREEN G...

Страница 27: ...Characteristics 40 30 20 10 10 0 10 20 30 40 50 0 Pipe Temp Sensor Intake Air Temp Sensor 1 1 2 2 C25 1µ 16V R62 15 0k C27 1µ 16V R61 20 0k PIPING TEMP SENSOR THERMISTOR SUCTION TEMP SENSOR THERMISTOR 4 3 2 1 t 0 169 170 5V CN TH RED CN DISP YELLOW UP DOWN LOUVER MOTOR CN STM1 WHITE 1 5 4 3 2 12V 74 144 70 64 61 M 12V 1 2 3 4 5 6 7 16 9 8 15 14 13 12 11 10 IC03 R47 1 2W 68 5 143 R46 1 2W 68 5 GND ...

Страница 28: ...TION TEMP SENSOR THERMISTOR 4 3 2 1 t 0 169 170 5V CN TH RED CN DISP YELLOW UP DOWN LOUVER MOTOR CN STM1 WHITE 1 5 4 3 2 12V 74 144 70 64 61 M 12V 1 2 3 4 5 6 7 16 9 8 15 14 13 12 11 10 IC03 R47 1 2W 68 5 143 R46 1 2W 68 5 GND VCC 6 1 2 3 4 5 CN DISP WHITE 5 4 3 2 1 ELECTRONIC CONTROLLER DISPLAY RECEIVER P C B PCB201 POWER green TIMER orange 16 17 R201 470 1 10W 5 R202 2k 1 10W 5 LED201 LED202 GND...

Страница 29: ...CHING POWER SUPPLY CIRCUIT FUSE102 T3 15A L250V FUSE101 20A 250V 3 2 1 COMMUNICATION CIRCUIT PFC CIRCUIT W U V ELECTRONIC CONTROLLER MS 3 FUSE104 15A 250V NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT RECTIFICATION CIRCUIT M TANK TEMP SENSOR 50kΩ 3950 1 3 CN TANK WHITE 5V G8 R1 4 99k 1 G8 C3 1µ 10V CN STM 327 351 322 75 76 77 78 323 378 379 381 422 6 5 4 3 2 1 C189 0 1µ 25V G2 13V 13V 1 2 3 4 5 6 7 1...

Страница 30: ...ENSOR 50kΩ 3950 1 3 t 0 P N FUSE103 20A 250V 3 2 1 PFC CIRCUIT W U V FAN MOTOR ELECTRONIC CONTROLLER MS 3 NOISE FILTER CIRCUIT RECTIFICATION CIRCUIT EXPANSION VALVE 1 2 3 4 5 6 M MS 3 FUSE104 T3 15A L250V 402 403 404 5 4 3 2 1 C178 C186 0 01µ 50V C188 0 01µ 50V C187 0 01µ 50V CN HOT CN STM R313 1k R312 1k R311 1k 5V G2 G2 G2 G2 SWITCHING POWER SUPPLY CIRCUIT COMMUNICATION CIRCUIT RECTIFICATION CIR...

Страница 31: ... 10 Printed Circuit Board 10 1 Indoor Unit 10 1 1 Main Printed Circuit Board CN FM CN STM1 CN STM2 UE18QKE only CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 JP1 Random Auto Restart enable disable ...

Страница 32: ...32 10 1 2 Indicator Receiver Printed Circuit Board CN DISP ...

Страница 33: ... 2 Outdoor Unit 10 2 1 Main Printed Circuit Board 10 2 1 1 CU YE9QKE CU YE12QKE CU UE9QKE CU UE12QKE CN HOT CN STM CN TH CN MTR1 CN MTR2 CN TANK AC BLK DATA AC WHT POWER TRANSISTOR IPM CURRENT TRANSFORMER CT ...

Страница 34: ...34 10 2 1 2 CU UE18QKE CN HOT CN STM CN TH1 CN MTR2 CN MTR1 CN TANK AC BLK FG1 DATA FG2 AC WHT RAT1 RAT2 POWER TRANSISTOR IPM CURRENT TRANSFORMER CT ...

Страница 35: ...35 10 2 2 CPU Printed Circuit Board 10 2 2 1 CU YE9QKE CU YE12QKE CU UE9QKE CU UE12QKE ...

Страница 36: ...m 1 4 5 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 7 5 20 15 3 15 10 30 30 3 20 P H 5 1 2 1 E Y 2 1 E U 2 1 E R RE15 1 75HP 12 7mm 1 2 UE18 2 0HP 7 5 20 20 3 15 8 1 E R RE24 2 5HP 15 88mm 5 8 Example For RE9 If the unit is installed at 10 m distance the quantity of additional refrigerant should be 50 g 10 7 5 m 20 g m 50 g 11 1 3 Indoor Outdoor Unit Installation Diagram 50 mm or more 65 mm or mo...

Страница 37: ...ith 5 screws or more at least 5 screws If mounting the unit on the concrete wall consider using anchor bolts o Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with ø70 mm hole core drill o Line according to the left and right side of the installation plate The meeting point of the extended line ...

Страница 38: ...nnecting the piping column in outdoor unit section Below steps are done after connecting the outdoor piping and gas leakage confirmation Step 7 Insulate and finish the piping Step 8 Secure the Indoor Unit Please refer to Insulation of piping connection column as mentioned in indoor outdoor unit installation Right Rear piping Cover for the bottom piping Cover for the bottom piping Tape it with pipi...

Страница 39: ... Isolating Devices Disconnecting means o Connect approved type polychloroprene sheathed power supply cord 3 1 5 mm2 1 0 1 75HP 3 2 5 mm2 2 0 2 5HP type designation 60245 IEC 57 or heavier cord to the terminal board and connect the others end of the cord to Isolating Devices Disconnecting means o Do not use joint power supply cord Replace the wire if the existing wire from concealed wiring or other...

Страница 40: ...rew and close the front panel Recommended length mm Tape Connection cable Tape Power supply cord Recommended length mm a 55 b 35 c 35 d 50 e 40 f 35 g 60 Terminal Board Control Board Earth wire longer than others AC wires for safety reason Holder Holder Indoor outdoor connection cable Isolating Devices Outdoor unit Power supply cord Note Isolating Devices Disconnecting means should have minimum 3 ...

Страница 41: ...ING REQUIREMENT Conductor fully inserted Conductor not fully inserted gap between wires WARNING RISK OF FIRE JOINING OF WIRES MAY CAUSE OVERHEATING AND FIRE Do not joint wires OR OR OR Use complete wire without joining Use approved socket and plug with earth pin Wire connection in this area must follow to national wiring rules ACCEPT PROHIBITED PROHIBITED ...

Страница 42: ...e at joint portion of tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in specified torque as stated in the table Do not overtighten overtightening may cause gas leakage Piping size Torque 6 35 mm 1 4 18 N m 1 8 kgf m 9 52 mm 3 8 42 N m 4...

Страница 43: ...re that the needle in the gauge does not move after approximately five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERENT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighten the service port caps of the 3 way valve at a torque of 18 N m with a torque wrench 7 Remove the valve caps of both of the 2 way valve a...

Страница 44: ...rly earthed Earth wire shall be Yellow Green Y G in colour and longer than other AC wires for safety reason 11 3 5 Piping Insulation 1 Please carry out insulation at pipe connection portion as mentioned in Indoor Outdoor Unit Installation Diagram Please wrap the insulated piping end to prevent water from going inside the piping 2 If drain hose or connecting piping is in the room where dew may form...

Страница 45: ...tting temperature and it is updated continuously whenever the electrical power is supplied to the unit 12 1 2 Cooling Operation 12 1 2 1 Thermostat control Compressor is OFF when Intake Air Temperature Internal Setting Temperature 1 5 C continue for 3 minutes When compressor is OFF Thermostat OFF and AUTO FAN is set the fan will stop periodically Compressor is ON after waiting for 3 minutes if the...

Страница 46: ...ment onwards o If indoor intake temperature remote control setting temperature 3 C if previous operate in DRY mode then continue in DRY mode otherwise COOL mode is decided o If 2 C indoor intake temperature remote control setting temperature 3 C maintain with previous mode o If indoor intake temperature remote control setting temperature 2 C HEAT mode is decided 12 2 Indoor Fan Motor Operation 12 ...

Страница 47: ...2550 rpm or 50 rpm continue for 10 seconds then fan motor error counter increase fan motor is then stop and restart If the fan motor counter becomes 7 times then H19 fan motor error is detected Operation stops and cannot on back 12 3 Outdoor Fan Motor Operation Outdoor fan motor is operated with one fan speed only It starts when compressor starts operation and it stops 30 seconds after compressor ...

Страница 48: ...to Control with dew 5 35 Usual 5 12 5 20 27 5 35 Dry Manual Control with dew 5 12 5 20 27 5 35 Heating Manual Usual 5 17 5 30 42 5 55 CS UE18QKE 1 Automatic vertical airflow direction can be set using remote control the vane swings up and down within the angles as stated above For heating mode operation the angle of the vane depends on the indoor heat exchanger temperature as Figure 1 below It doe...

Страница 49: ...gles of the vane are as stated below and the positions of the vane are as Figure 2 above Pattern 1 2 3 4 5 Airflow Direction Patterns at Remote Control Vane Angle 90 70 80 100 110 12 5 ON Timer Control ON timer can be set using remote control the unit with timer set will start operate earlier than the setting time This is to provide a comfortable environment when reaching the set ON time 60 minute...

Страница 50: ...o be selected randomly after power supply resumes This type of control is not applicable during ON OFF Timer setting This control can be omitted by open the circuit of JP1 at indoor unit printed circuit board 12 8 Indication Panel LED POWER TIMER Color Green Orange Light ON Operation ON Timer Setting ON Light OFF Operation OFF Timer Setting OFF Note If POWER LED is blinking the possible operation ...

Страница 51: ... 5 05 6 75 8 76 Cooling Soft Dry B 4 57 6 22 8 25 Cooling Soft Dry C 4 57 6 22 8 25 Heating 4 65 15 02 5 92 15 02 9 50 14 76 4 The first 30 minutes of cooling operation A will be applied 13 1 3 IPM Power transistor Prevention Control Overheating Prevention Control 1 When the IPM temperature rises to 120 C compressor operation will stop immediately 2 Compressor operation restarts after 3 minutes th...

Страница 52: ...18QKE o During Cooling and Soft Dry operations Indoor suction temperature indoor piping temperature is below 4 C o During Heating operations Indoor piping temperature indoor suction is under 5 C Control contents o Compressor stops and restart after 3 minutes o If the conditions above happen 2 times within 20 minutes the unit will Stop operation Timer LED blinks and F91 indicated 13 1 6 Low Frequen...

Страница 53: ...hanger is higher than 5 C At the same time indoor fan speed will be higher than during its normal operation If indoor heat exchanger temperature is higher than 5 C for 5 minutes the fan speed will return to its normal operation 13 2 4 Freeze Prevention Control 2 Control start conditions o During Cooling operation and soft dry operation During thermo OFF condition indoor intake temperature is less ...

Страница 54: ... 13 3 2 Outdoor Air Temperature Control The Max current value is regulated when the outdoor air temperature rise above 14 C in order to avoid compressor overloading 13 3 3 Overload Protection Control The compressor operating frequency is regulated in accordance to indoor heat exchanger temperature as shown below If the heat exchanger temperature exceeds 60 C compressor will stop 13 3 4 Low Tempera...

Страница 55: ...change the advance setting of air conditioner operation 3 REMOTE CONTROL NUMBER SWITCH MODE The Remote Control Number Switch Mode will be activated if the Auto OFF ON button is pressed continuously for more than 11 seconds 3 beep sounds will occur at 11th seconds to identify the Remote Control Number Switch Mode is in standby condition and press AC RESET button and then press any button at remote ...

Страница 56: ...hort beep Turn OFF remote control receiving sound o Long beep Turn ON remote control receiving sound After Auto OFF ON Button is pressed the 20 seconds counter for Remote Control Receiving Sound OFF ON Mode is restarted 14 2 Remote Control Button 14 2 1 SET Button To check remote control transmission code and store the transmission code to EEPROM o Press Set button continuously for 10 seconds by u...

Страница 57: ... problems before inspecting the refrigeration cycle Such problems include insufficient insulation problem with the power source malfunction of a compressor and a fan The normal outlet air temperature and pressure of the refrigeration cycle depends on various conditions the standard values for them are shown in the table on the right ...

Страница 58: ...Electric current during operation Low Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or Strainer Short circuit in the indoor unit Heat radiation deficiency of the outdoor unit Inefficient compression Carry out the measurements of pressure electric current and temperature fifteen minutes after an operation is started ...

Страница 59: ... Turn power on 2 Press the CHECK button on the remote controller continuously for 5 seconds 3 will be displayed on the remote controller display Note Display only for No transmitting signal no receiving sound and no Power LED blinking 4 Press the TIMER or button on the remote controller The code H00 no abnormality will be displayed and signal will be transmitted to the main unit The power LED ligh...

Страница 60: ...ality Port is ON for 10s during ion device off ion device PCB H27 Outdoor air temperature sensor abnormality Continuous for 5s Outdoor air temperature sensor open or short circuit Outdoor air temperature sensor lead wire and connector H28 Outdoor heat exchanger temperature sensor 1 abnormality Continuous for 5s Outdoor heat exchanger temperature sensor 1 open or short circuit Outdoor heat exchange...

Страница 61: ...zing abnormality 3 times happen within 40 minutes Wrong wiring and connecting pipe expansion valve leakage indoor heat exchanger sensor open circuit Check indoor outdoor connection wire and pipe Indoor heat exchanger sensor lead wire and connector Expansion valve lead wire and connector F90 Power factor correction PFC circuit protection 4 times happen within 10 minutes Power factor correction circ...

Страница 62: ...ived from outdoor unit in indoor unit signal transmission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wiring error Indoor unit outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units Troubleshooting ...

Страница 63: ...are interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error due to wrong wiring Indoor outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor units Troubleshooting ...

Страница 64: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 65: ...n Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 66: ...ion Conditions An input current detected by Current Transformer CT is below threshold value when the compressor is operating at certain frequency value for 3 minutes Malfunction Caused Lack of gas Broken CT current transformer Broken Outdoor PCB Troubleshooting ...

Страница 67: ...etermine abnormal fan motor feedback of rotation 2550rpm or 50rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operation stops due to breaking of fan motor lead wires Operation stops due to Hall IC malfunction Operation error due to faulty indoor unit PCB Troubleshooting ...

Страница 68: ... Decision Conditions During startup and operation of cooling and heating the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 69: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 70: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 71: ...tion Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 72: ...nction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 73: ...alfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCBs used Indoor unit or outdoor unit PCB defective Troubleshooting ...

Страница 74: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 75: ...Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 76: ...ction Decision Conditions During startup and operation of cooling and heating the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty connector connection Faulty sensor Faulty PCB Troubleshooting ...

Страница 77: ...h pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation Phenomena unit is stopping and re starting very often in heating mode Malfunction Caused Indoor heat exchanger thermistor Clogged air filter or heat exchanger Over bent pipe liquid side Troubleshooting ...

Страница 78: ...l takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Air short circuit at indoor unit Clogged indoor unit air filter Dust accumulation on the indoor unit heat exchanger 2 3 way valve closed Faulty indoor unit fan motor Refrigerant shortage refrigerant leakage Clogged expansion valve or strainer Faulty indoor pipe temperature sensor Faulty indoor unit PCB Troubleshooting ...

Страница 79: ...cold during heating except deice or when indoor heat exchanger is hot during cooling and compressor operating the 4 way valve is detected as malfunction Malfunction Caused Indoor heat exchanger pipe thermistor 4 way valve malfunction Troubleshooting Check gas side pipe for hot gas flow in cooling mode ...

Страница 80: ...rature and indoor pipe temperature is above 10 C or indoor pipe temperature is below 1 0 C Remark When the indoor standby unit is freezing the outdoor unit transfers F17 error code to the corresponding indoor unit and H39 to other indoor unit s Malfunction Caused Wrong wiring connection Faulty sensor Faulty expansion valve Troubleshooting ...

Страница 81: ...startup and operation of cooling and heating when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal DC voltage level for power transistors When DC voltage detected is LOW transistor switching will turn ON by controller to push up the DC level When DC voltage detected is HIGH 391Vdc 425Vdc active LOW signal will send by the controller to turn OFF relay RY...

Страница 82: ...rigeration Cycle Abnormality Malfunction Decision Conditions The input current is low while the compressor is running at higher than the setting frequency Malfunction Caused Lack of gas 3 way valve close Troubleshooting ...

Страница 83: ...ion Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disconnect Faulty Outdoor PCB Faulty compressor Troubleshooting ...

Страница 84: ... the outdoor unit heat exchanger thermistor Malfunction Caused Outdoor heat exchanger temperature rise due to short circuit of hot discharge air flow Outdoor heat exchanger temperature rise due to defective of outdoor fan motor Outdoor heat exchange temperature rise due to defective outdoor heat exchanger thermistor Outdoor heat exchanger temperature rise due to defective of outdoor unit PCB Troub...

Страница 85: ...vated o Heat Sink Overheating During operation of cooling and heating when heat sink temperature data 90 C is detected by the heat sink temperature sensor Malfunction Caused IPM overheats due to short circuit of hot discharge air flow IPM overheats due to defective of outdoor fan motor IPM overheats due to defective of internal circuitry of IPM IPM overheats due to defective IPM temperature sensor...

Страница 86: ...ling and heating when compressor tank temperature data 103 C is detected by the compressor tank temperature sensor Malfunction Caused Faulty compressor tank temperature sensor 2 3 way valve closed Refrigerant shortage refrigerant leakage Faulty outdoor unit PCB Faulty compressor Troubleshooting ...

Страница 87: ...on of cooling and heating when an input over current X value in Total Running Current Control is detected by checking the input current value being detected by current transformer CT with the compressor running Malfunction Caused Excessive refrigerant Faulty outdoor unit PCB Troubleshooting ...

Страница 88: ...eating when inverter DC peak data is received by the outdoor internal DC Peak sensing circuitry Malfunction Caused DC current peak due to compressor failure DC current peak due to defective power transistor s DC current peak due to defective outdoor unit PCB DC current peak due to short circuit Troubleshooting ...

Страница 89: ...y result in electric shocks 16 1 Indoor Electronic Controllers Cross Flow Fan and Indoor Fan Motor Removal Procedures 16 1 1 CS YE9QKE CS YE12QKE CS UE9QKE CS UE12QKE 16 1 1 1 To remove front grille 2 Remove 2 caps and 2 screws at the bottom of discharge vane 3 Hold both sides of the frontgrille and remove it by pulling up and toward yourself gently 1 Lift to open the horizontal vane gently Figure...

Страница 90: ...FM CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 Figure 3 Figure 4 16 1 1 4 To remove discharge grille 10 Pull out to remove the drain hose from the discharge grille 11 Then pull the discharge grille downward gently to dismantle it Figure 5 ...

Страница 91: ...12 Remove 4 screws holding the control board then pull out the control board Figure 6 16 1 1 6 To remove cross flow fan and indoor fan motor 13 Remove the screw that holding the cross flow fan and fan motor axis Figure 7 16 14 15 Figure 8 ...

Страница 92: ... fan Reminder To reinstall the fan motor adjust the fan motor connector to 45 towards you before fixing control board 17 Remove the cross flow fan from the unit by pulling it to the left and downward Evaporator Figure 9 Reminder To reinstall the cross flow fan ensure cross flow fan is in line as shown in figure 10 Figure 10 ...

Страница 93: ...as discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 16 2 Indoor Electronic Controllers Cross Flow Fan and Indoor Fan Motor Removal Procedures 16 2 1 CS UE18QKE 16 2 1 1 To remove front grille Figure 1 16 2 1 2 To remove horizontal vane Figure 2 ...

Страница 94: ...94 16 2 1 3 To remove power electronic controller CN FM CN STM1 CN TH CN DISP CN RMT RY PWR AC303 G301 AC304 RY PWR2 Figure 3 Figure 4 16 2 1 4 To remove discharge grille Figure 5 ...

Страница 95: ...95 16 2 1 5 To remove control board Figure 6 16 2 1 6 To remove cross flow fan and indoor fan motor Figure 7 Figure 8 ...

Страница 96: ...96 Figure 9 Figure 10 ...

Страница 97: ...nel Fig 1 2 Remove the 6 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove the Top Cover of the Control Board by 4 hooks Fig 3 5 Remove the Control Board as follows Remove 2 Screws Release 3 Terminal Connectors and 2 Earth Wire Screws Remove 2 Control Board Cover Screws Release 6 Connectors and 2 Reactor Connectors Remove 1 Screw Fig 4 Fig 5 Electronic Control...

Страница 98: ... electrostatic discharge 1 Remove the 5 screws of the Top Panel Fig 1 2 Remove the 8 screws of the Front Panel Fig 2 3 Remove the screw of the Terminal Board Cover 4 Remove the Top Cover of the Control Board by 4 hooks Fig 3 5 Remove the Control Board as follows Fig 4 Fig 5 Fig 6 ...

Страница 99: ...HC IP TC SHC IP TC SHC IP 19 0 3535 2919 827 3796 2935 615 3564 2874 827 3500 2993 1090 27 22 0 3995 2171 670 3920 2098 612 3890 2018 791 3428 1912 1071 15 7 3566 3530 736 3366 3333 689 3228 3196 848 2967 2938 1105 23 18 4 3505 2076 776 3561 2077 665 3547 2035 826 3044 1973 1089 13 3 2735 2708 651 2204 2182 305 2495 2470 641 2727 2699 1108 20 15 8 2879 1869 617 2860 1830 586 3160 1991 845 2771 189...

Страница 100: ...2QKE CU YE12QKE CS UE12QKE CU UE12QKE Indoor C Outdoor WB C 10 7 2 7 12 DB TC IP TC IP TC IP TC IP TC IP 24 2308 1358 2993 1415 3309 1325 3695 1109 4012 1142 20 2431 1340 3200 1410 3700 1300 4000 1100 4241 1117 16 1962 1307 3288 1395 3682 1311 3949 1129 4137 1098 17 2 3 CS UE18QKE CU UE18QKE Indoor C Outdoor WB C 10 7 2 7 12 DB TC IP TC IP TC IP TC IP TC IP 24 3991 2060 4775 2172 5500 2128 5261 15...

Страница 101: ...rced cooling at 16 C Hi fan Compressor frequency Rated for cooling operation Piping length 5m Voltage 230V 18 1 1 CS CU YE9QKE CS CU UE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C Low Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 12 1 00 1 50 2 00 2 50 3 00 3 50 4 00 4 50 12 16 20 24 28 32 36 40 44 48 0 88 0 92 0 96 1 00 1 04 1 08 1 12 16 20 24 28 32 36 40 ...

Страница 102: ...MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 2 00 2 50 3 00 3 50 4 00 4 50 5 00 5 50 6 00 6 50 12 16 20 24 28 32 36 40 44 48 0 80 0 84 0 88 0 92 0 96 1 00 1 04 1 08 12 16 20 24 28 32 36 40 44 48 12 00 12 50 13 00 13 50 14 00 14 50 15 00 15 50 16 00 16 50 12 16 20 24 28 32 36 40 44 48 ...

Страница 103: ...Low Pressure MPa 10 0 11 0 12 0 13 0 14 0 15 0 16 0 17 0 18 0 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 0 80 0 90 1 00 1 10 1 20 1 30 1 40 1 50 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 2 00 3 00 4 00 5 00 6 00 7 00 8 00 9 00 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41 43 45 ...

Страница 104: ...ssor frequency Rated for Heating operation Piping length 5m Voltage 230V 18 2 1 CS CU YE9QKE CS CU UE9QKE Outlet Air C Outlet Air C Outdoor Air Temperature C High Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 2 00 2 50 3 00 3 50 4 00 4 50 5 00 15 10 5 0 5 10 15 1 20 1 40 1 60 1 80 2 00 2 20 2 40 2 60 2 80 15 10 5 0 5 10 15 20 24 28 32 36 40 15 10 5 0 5 10 15 ...

Страница 105: ...ir C Outdoor Air Temperature C High Pressure MPa Outdoor Air Temperature C Current A Outdoor Air Temperature C 3 00 3 50 4 00 4 50 5 00 5 50 6 00 15 10 5 0 5 10 15 1 60 1 80 2 00 2 20 2 40 2 60 2 80 3 00 3 20 15 10 5 0 5 10 15 20 24 28 32 36 40 15 10 5 0 5 10 15 ...

Страница 106: ...ure C High Pressure MPa 3 00 4 00 5 00 6 00 7 00 8 00 9 00 10 00 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 25 00 30 00 35 00 40 00 45 00 50 00 55 00 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 1 80 2 30 2 80 3 30 3 80 4 30 4 80 5 30 5 80 16 14 12 10 8 6 4 2 0 2 4 6 8 10 12 14 16 18 20 22 24 26 ...

Страница 107: ...E12QKE CS CU UE9QKE CS CU UE12QKE 0 92 0 94 0 96 0 98 1 00 1 02 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Cooling Capacity Correction Factor Heating Capacity Correction Factor Pipe Length m 0 90 0 92 0 94 0 96 0 98 1 00 1 02 1 04 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Pipe Length m Note The graphs show the factor after added right amount of additional refrigerant ...

Страница 108: ...n Factor Heating Capacity Correction Factor Pipe Length m Pipe Length m 0 95 0 97 0 99 1 01 1 03 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 95 0 96 0 97 0 98 0 99 1 00 1 01 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Note The graphs show the factor after added right amount of additional refrigerant ...

Страница 109: ...5 36 33 45 I I I I I I I I I I O I 46 47 48 54 55 56 I I I I I I I I I I O I 62 57 58 59 60 61 40 3 4 2 5 1 27 23 11 16 26 34 28 29 30 39 9 37 35 7 38 8 41 42 43 50 53 52 51 44 10 49 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 110: ...241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521259 35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 36 REMOTE CONTROL COMPLETE 1 CWA75C4453 CWA75C4455 O 37 FRONT GRILLE COMPLETE 1 CWE11C5835 O 38 INTAKE GRILLE COMPLETE 1 CWE22C1861 39 GRILLE DOOR COMPLETE 1 CWE14C1090 40 AIR FILTER 2 CWD001279 O 41 SCREW FRONT GRILLE 2 XTT4 16CFJ 42 CAP FRONT GRILLE 2 CWH52...

Страница 111: ...PTION QTY CS YE9QKE CS YE12QKE REMARK 61 INSTALLATION INSTRUCTION 1 CWF616280 62 OPERATING INSTRUCTION 1 CWF569460 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 112: ...8 CWE241374 30 CONNECTING BAR 2 CWE261251 33 AIR SWING MOTOR 1 CWA981264 O 34 CAP DRAIN TRAY 1 CWH521259 35 HORIZONTAL VANE COMPLETE 1 CWE24C1385 36 REMOTE CONTROL COMPLETE 1 CWA75C4455 O 37 FRONT GRILLE COMPLETE 1 CWE11C5836 O 38 INTAKE GRILLE COMPLETE 1 CWE22C1861 39 GRILLE DOOR COMPLETE 1 CWE14C1090 40 AIR FILTER 2 CWD001279 O 41 SCREW FRONT GRILLE 2 XTT4 16CFJ 42 CAP FRONT GRILLE 2 CWH521227 4...

Страница 113: ...CS UE12QKE REMARK 60 INSTALLATION INSTRUCTION 1 CWF616279 61 INSTALLATION INSTRUCTION 1 CWF616280 62 OPERATING INSTRUCTION 1 CWF569460 NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 114: ...I I 60 I I 61 I I 59 2 5 40 45 44 1 27 13 23 11 16 24 24a 15 12 25 33 26 34 28 28 29 30 31 32 35 42 41 37 38 39 7 53 52 51 50 36 CWH55025 J CWH55051 J 62 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 115: ...CAL VANE 11 CWE241374 30 CONNECTING BAR 1 CWE261257 31 CONNECTING BAR 1 CWE261258 32 AIR SWING MOTOR 1 CWA98K1018 O 33 AIR SWING MOTOR 1 CWA981241 O 34 CAP DRAIN TRAY 1 CWH521259 35 HORIZONTAL VANE COMPLETE 1 CWE24C1392 36 REMOTE CONTROL COMPLETE 1 CWA75C4297 O 37 FRONT GRILLE COMPLETE 1 CWE11C5837 O 38 INTAKE GRILLE COMPLETE 1 CWE22C1888 39 GRILLE DOOR COMPLETE 1 CWE14C1090 40 AIR FILTER 2 CWD001...

Страница 116: ...1 CWF616277 59 INSTALLATION INSTRUCTION 1 CWF616278 60 INSTALLATION INSTRUCTION 1 CWF616279 61 INSTALLATION INSTRUCTION 1 CWF616280 62 ANTI BACTERIAL FILTER 1 CWD00C1280 O NOTE All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 117: ...5 3 6 5 8 7 27 28 32 30 17 16 10 11 4 12 22 21 19 26 25 38 39 9 2 1 23A 23B 31 35 33 20 14 24 29 55 53 54 51 52 23C 41 13 43 42 50 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 118: ...CWH7080300J 22 SOUND PROOF BOARD 1 CWH151172 23A SOUND PROOF MATERIAL 1 CWG302315 23B SOUND PROOF MATERIAL 1 CWG302316 23C SOUND PROOF MATERIAL 1 CWG302317 24 SENSOR CO COMP TEMP 1 CWA50C2205 O 25 CONTROL BOARD COVER TOP 1 CWH131264 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C8416R CWA73C8417R O 27 TERMINAL BOARD ASSY 1 CWA28K1036J O 28 CABINET SIDE PLATE CO RIGHT 1 CWE04C1512 29 SENSOR CO AIR TEMP AND ...

Страница 119: ...ME DESCRIPTION QTY CU YE9QKE CU YE12QKE REMARK 54 SHOCK ABSORBER LEFT 1 CWG712970 55 C C CASE 1 CWG568356 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 120: ...CWH7080300J 22 SOUND PROOF BOARD 1 CWH151172 23A SOUND PROOF MATERIAL 1 CWG302315 23B SOUND PROOF MATERIAL 1 CWG302316 23C SOUND PROOF MATERIAL 1 CWG302317 24 SENSOR CO COMP TEMP 1 CWA50C2205 O 25 CONTROL BOARD COVER TOP 1 CWH131264 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C8416R CWA73C8417R O 27 TERMINAL BOARD ASSY 1 CWA28K1036J O 28 CABINET SIDE PLATE CO RIGHT 1 CWE04C1512 29 SENSOR CO AIR TEMP AND ...

Страница 121: ...ME DESCRIPTION QTY CU YE9QKE CU YE12QKE REMARK 54 SHOCK ABSORBER LEFT 1 CWG712970 55 C C CASE 1 CWG568356 Note All parts are supplied from PAPAMY Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in stock ...

Страница 122: ...21 20 9 31 11 10 15 1 16 17 4 23A 23B 23C 22 2 3 8 7 5 30 12 24 29 41 43 13 6 47 46 48 49 50 25 45 14 42 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts ...

Страница 123: ...3B SOUND PROOF MATERIAL 1 CWG302741 23C SOUND PROOF MATERIAL 1 CWG302740 24 SENSOR COMPLETE COMP TEMP 1 CWA50C2894 O 25 CONTROL BOARD COVER TOP 1 CWH131473 26 ELECTRONIC CONTROLLER MAIN 1 CWA73C8121R O 27 TERMINAL BOARD ASSY 1 CWA28K1036J 28 CABINET SIDE PLATE CO RIGHT 1 CWE04C1481 29 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2893 O 30 CABINET SIDE PLATE 1 CWE041616A 31 CABINET FRONT PLATE CO 1 CWE...