15.4.4  H15 (Compressor Temperature Sensor Abnormality) 

Malfunction Decision Conditions 

  During startup and operation of cooling, the temperatures detected by the outdoor compressor temperature 

sensor are used to determine sensor errors. 

 
Malfunction Caused 

 Faulty 

connector 

connection. 

 Faulty 

sensor. 

 Faulty 

PCB. 

 
Troubleshooting 

 

 

 
 

Содержание cs-s9pkv

Страница 1: ...refrigerant circuit WARNING This service information is designed for experienced repair technicians only and is not designed for use by the general public It does not contain warnings or cautions to...

Страница 2: ...ration 69 12 8 Timer Control 70 12 9 Random Auto Restart Control 70 12 10 Indication Panel 70 12 11 nanoe G Operation 71 12 12 In filter Deactivation Operation 73 12 13 Mild Dry Cooling Operation 74 1...

Страница 3: ...lectrical shock or fire 9 This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker ELCB or Residual Current Device RCD Otherwise it may cause electrical shock and fire...

Страница 4: ...24PKV Power supply connection to the room air conditioner Use power supply cord 3 x 1 5 mm 2 1 0 1 5HP or 3 x 2 5 mm 2 2 0 2 5HP type designation 60245 IEC 57 or heavier cord Connect the power supply...

Страница 5: ...4 1 Type Hermetic Motor Rotary Hermetic Motor Rotary Motor Type Brushless 6 poles Brushless 6 poles Compressor Output Power W 500 650 Type Cross Flow Fan Cross Flow Fan Material ASG20K1 ASG20K1 Motor...

Страница 6: ...ter mm 16 7 16 7 Drain Hose Length mm 550 550 Fin Material Aluminium Pre coated Aluminium Pre coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 15 21 2 15 21 Indoor Heat Exchanger Size W x H x L m...

Страница 7: ...ess 6 poles Compressor Output Power W 900 900 Type Cross Flow Fan Cross Flow Fan Material ASG30K1 ASG30K1 Motor Type DC Transistor 8 poles DC Transistor 8 poles Input Power W 94 8 94 8 Output Power W...

Страница 8: ...luminium Pre Coated Fin Type Slit Fin Slit Fin Row x Stage x FPI 2 15 17 2 15 21 Indoor Heat Exchanger Size W x H x L mm 810 315 25 4 810 315 25 4 Fin Material Aluminium Blue Coated Aluminium Blue Coa...

Страница 9: ...4 poles Compressor Output Power W 1 70k Type Cross Flow Fan Material ASG30K1 Motor Type DC Transistor 8 poles Input Power W 94 8 Output Power W 40 QLo rpm 910 Lo rpm 1000 Me rpm 1270 Hi rpm 1540 Indoo...

Страница 10: ...minium Pre Coated Fin Type Slit Fin Row x Stage x FPI 2 15 21 Indoor Heat Exchanger Size W x H x L mm 810 315 25 4 Fin Material Aluminium Blue Coated Fin Type Slit Fin Row x Stage x FPI 2 36 17 Outdoo...

Страница 11: ...ontrol is misplaced or a malfunction occurs Horizontal airflow direction louver Do not adjust by hand POWE R TIM ER AUTO C OMFO RT NANOE G POWE RFUL QUIE T Air Filters nanoe G GENERATOR Do not touch d...

Страница 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9PKV CS S12PKV...

Страница 13: ...13 4 1 2 CS S18PKV CS S24PKV CS S28PKV...

Страница 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9PKV 4 2 2 CU S12PKV 542...

Страница 15: ...15 4 2 3 CU S18PKV CU S24PKV...

Страница 16: ...16 4 2 4 CU S28PKV...

Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9PKV CU S9PKV CS S12PKV CU S12PKV...

Страница 18: ...18 5 2 CS S18PKV CU S18PKV CS S24PKV CU S24PKV...

Страница 19: ...19 5 3 CS S28PKV CU S28PKV...

Страница 20: ...20 6 Block Diagram 6 1 CS S9PKV CU S9PKV...

Страница 21: ...21 6 2 CS S12PKV CU S12PKV...

Страница 22: ...CS S24PKV CU S24PKV SINGLE PHASE POWER SUPPLY INDOOR UNIT OUTDOOR UNIT NOISE FILTER FUSE301 FUSE3 CT400 C FM C205 RY C RY FM CR6 CR4 REACTOR RY PWR RY PWR PTC PTC1 PTC2 TEMP FUSE SC SC M M 1 MS 3 1 2...

Страница 23: ...23 6 4 CS S28PKV CU S28PKV POWER SUPPLY INDOOR UNIT OUTDOOR UNIT NOISE FILTER SC FM SSR FUSE 1 2 3 FUSE REACTOR FUSE COMP L N...

Страница 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9PKV CS S18PKV CS S24PKV...

Страница 25: ...25 7 1 2 CS S12PKV Resistance of Indoor Fan Motor Windings MODEL CS S12PKV CONNECTION CWA921443 YELLOW BLUE 182 0 YELLOW RED 226 8 Winding Resistance at 20 C...

Страница 26: ...26 7 1 3 CS S28PKV...

Страница 27: ...MP TERMINAL Resistance of Compressor Windings MODEL CU S9PKV CONNECTION 5S2072XGA21 U V 3 034 U W 3 021 V W 3 009 Winding Resistance at 20 C Resistance of Outdoor Fan Motor Windings MODEL CU S9PKV CON...

Страница 28: ...Windings MODEL CU S12PKV CONNECTION 5RS092XCE21 U V 1 152 U W 1 152 V W 1 152 Winding Resistance at 20 C Resistance of Outdoor Fan Motor Windings MODEL CU S12PKV CONNECTION CWA951466 YELLOW BLUE 262 7...

Страница 29: ...0 MS 3 P N SWITCHING POWER SUPPLY CIRCUIT RECTIFICATION CIRCUIT FUSE2 T3 15A L250V BLU RED YLW FAN MOTOR CIRCUIT FUSE3 20A 250V RED RED TRADE MARK BLUE BLU YELLOW YLW COMP TERMINAL 3 RED 2 WHITE 1 BL...

Страница 30: ...ORE CORE CORE COMPRESSOR SENSOR COMPLETE OUTDOOR AIR TEMPERATURE SENSOR THERMISTOR OUTDOOR AIR HEAT EXCHANGER TEMPERATURE SENSOR THERMISTOR SENSOR COMPLETE COIL COMPLETE EXPAND VALVE OUTDOOR COMPRESSO...

Страница 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9PKV CS S18PKV CS S24PKV...

Страница 32: ...32 8 1 2 CS S12PKV...

Страница 33: ...33 8 1 3 CS S28PKV...

Страница 34: ...istics 70 60 50 40 30 20 10 0 10 0 10 Temperature o C Resistance k 20 30 40 50 1 2 1 2 Outdoor Air Sensor Outdoor Heat Exchanger Sensor Compressor Temp Sensor Thermistor Characteristics 70 60 50 40 30...

Страница 35: ...35 8 2 2 CU S12PKV...

Страница 36: ...RCUIT PFC CIRCUIT PIPING TEMP SENSOR1 3 4 CN TH1 WHT OUTDOOR TEMP SENSOR 1 2 R101 C46 C45 R100 5V TANK TEMP SENSOR 1 3 CN TANK WHT 5V R410 C49 SWITCHING POWER SUPPLY CIRCUIT COMPRESSOR RED BLU YLW MS...

Страница 37: ...GE TEMP SENSOR 50k Ohm 3950 CORE CAPACITOR 460V 3 5 F CORE REACTOR WHT BLK WHT AC BLK AC WHT RY PWR2 RY PWR1 RY HL RY C CN BLK CN WHT CN COM YLW CN COM YLW CN ACFM WHT CN DIS WHT 1 1 3 1 3 4 3 2 CN TH...

Страница 38: ...38 9 Printed Circuit Board 9 1 Indoor Unit 9 1 1 Main Printed Circuit Board 9 1 1 1 CS S9PKV CS S18PKV CS S24PKV CS S28PKV...

Страница 39: ...39 9 1 1 2 CS S12PKV...

Страница 40: ...40 9 1 2 Indicator Printed Circuit Board CN DISP 9 1 3 High Voltage Power Supply Printed Circuit Board GND 9 1 4 Comparator Printed Circuit Board CN SENS2 CN SENS1 CN MSENS...

Страница 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...

Страница 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9PK...

Страница 43: ...43 9 2 1 2 CU S12PK...

Страница 44: ...44 9 2 1 3 CU S18PK CU S24PK...

Страница 45: ...45 9 2 1 4 CU S28PK...

Страница 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9PKV...

Страница 47: ...47 9 2 2 2 CU S28PKV...

Страница 48: ...or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot air discharged Keep the spaces indicated by arrows f...

Страница 49: ...o Always mount the installation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Line according t...

Страница 50: ...1 6 Indoor Unit Installation 10 1 6 1 For the Right Rear Piping 10 1 6 2 For the Right and Right Bottom Piping 10 1 6 3 For the Embedded Piping This can be used for left rear piping and bottom piping...

Страница 51: ...51...

Страница 52: ...joint connection cable Replace the wire if the existing wire from concealed wiring or otherwise is too short o Secure the connection cable onto the control board with the holder Note Isolating Device...

Страница 53: ...iping 1 Please cut using pipe cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder e...

Страница 54: ...oint portion of tube assembly onto the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the fl...

Страница 55: ...ely five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighte...

Страница 56: ...ontrol board with the holder clamper 4 Attach the control board cover back to the original position with screw 5 For wire stripping and connection requirement refer to instruction 10 1 7 of indoor uni...

Страница 57: ...ing is built over the unit to prevent direct sunlight or rain be careful that heat radiation from the condenser is not obstructed There should not be any animal or plant which could be affected by hot...

Страница 58: ...allation plate horizontally by aligning the marking off line with the thread and using a level gauge 2 Drill the piping plate hole with 70 mm hole core drill o Putting measuring tape at position as sh...

Страница 59: ...1 6 Indoor Unit Installation 11 1 6 1 For the Right Rear Piping 11 1 6 2 For the Right and Right Bottom Piping 11 1 6 3 For the Embedded Piping This can be used for left rear piping and bottom piping...

Страница 60: ...60...

Страница 61: ...rd 3 Bind all the indoor and outdoor connection cable with tape and route the connection cable via the escapement 4 Remove the tapes and connect the connection cable between indoor unit and outdoor un...

Страница 62: ...iping 1 Please cut using pipe cutter and then remove the burrs 2 Remove the burrs by using reamer If burrs is not removed gas leakage may be caused Turn the piping end down to avoid the metal powder e...

Страница 63: ...the copper pipe In case of using long piping Connect the piping Align the center of piping and sufficiently tighten the flare nut with fingers Further tighten the flare nut with torque wrench in spec...

Страница 64: ...ely five minutes Note BE SURE TO TAKE THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE 5 Disconnect the charging hose from the vacuum pump and from the service port of the 3 way valve 6 Tighte...

Страница 65: ...mm2 flexible cord type designation 60245 IEC 57 or heavier cord Do not use joint connection cable Replace the wire if the existing wire from concealed wiring or otherwise is too short 4 Connect the p...

Страница 66: ...at control Compressor is OFF when intake Air Temperature Internal Setting Temperature 0 5 C Compressor is ON after waiting for 3 minutes if the Intake Temperature Internal Setting Temperature Compress...

Страница 67: ...error counter increased to 7 then H19 fan motor error is detected Operation stopped and could not be restarted 12 3 Outdoor Fan Motor Operation For S9 12 18PK Outdoor fan motor is operated with one fa...

Страница 68: ...l airflow direction can be set using remote control the vane swings up and down within the angles as stated above It does not swing during fan motor stop When the air conditioner is stopped using remo...

Страница 69: ...ted to quiet operation of the new fan speed When operation mode is changed quiet operation is shifted to quiet operation of the new mode During quiet operation if ON timer activates quiet operation ma...

Страница 70: ...ing will not be cancelled 2 To cancel the previous timer setting press CANCEL button 3 To activate the previous timer setting press SET button 4 If main power supply is switched off the Timer setting...

Страница 71: ...ly Auto Fan Speed and no Powerful operation is allowed Even if Fan Speed button is pressed no signal is sent to the unit and no change on remote control display Auto Fan Speed for nanoe G operation ch...

Страница 72: ...operation the nanoe G system has abnormal discharge due to short circuit caused by water or dust adhesion and so forth with Lo feedback voltage at microcontroller When abnormal discharge occurred ever...

Страница 73: ...ss than 2 hours In filter deactivation stop condition o The unit is turned on o nanoe G generator operation time during in filter deactivation operation has achieved 120 minutes o The unit received di...

Страница 74: ...4 AUTO COMFORT and ECONAVI Operation Area of human availability activity level and absent is judged based on pulses by using 2 infrared sensors The internal setting temperature shift fan speed and hor...

Страница 75: ...ure shift fan speed and horizontal airflow direction are adjusted in order to provide comfort environment while maintain the energy saving level AUTO COMFORT ECONAVI initialization Initialize indicati...

Страница 76: ...ss Non Living Area near windows wall etc 12 14 1 4 Human Position Analysis According to Area of Living frequency of activity and indoor unit intake temperature the system will analyze the human positi...

Страница 77: ...level difference Louver stop time Higher Activity level 60 seconds 1 level Lower Activity level 30 seconds Higher Activity level 60 seconds Cooling 2 levels Lower Activity level 8 seconds When 3 acti...

Страница 78: ...ECONAVI or AUTO COMFORT operation and o Human activity sensor detects low activity level continuously for 60 minutes and o ON Timer is not activated Stop condition o Unit is off or o ECONAVI or AUTO...

Страница 79: ...Infrared Sensor Human Activity Indicator Sensor 1 Sensor 2 Left Center Right Vane Position Fan Speed 1 0 5 HI 1 1 Auto Swing HI 0 1 1 HI 0 0 Auto Swing LO The target area will maintain for 5 seconds b...

Страница 80: ...reset When abnormality counter reached 4 times H59 occurred No TIMER indicator blinking When error code happened the unit is able to operate without AUTO COMFORT ECONAVI 12 14 1 12 Human Activity Sens...

Страница 81: ...ates between sunny and cloudy or night to further optimize energy saving by adjusting the temperature Sunlight judgment is as following 12 14 2 1 Sunlight Intensity Reset The sunlight intensity will t...

Страница 82: ...ntensity database The sunlight sensor sensitivity could be adjusted 12 14 2 3 Judge Ambient Condition According to sunlight intensity over a period of time the system will analyze the ambient conditio...

Страница 83: ...unlight sensor check mode o After check mode is ended 5 minutes counter elapsed press AUTO OFF ON button at indoor unit o If the sunlight sensor detected sunlight intensity is at abnormal range the ch...

Страница 84: ...cy instructed will be increased However if total outdoor unit running current exceeds Y value compressor will be stopped immediately for 3 minutes Model S9 S12 S18 S24 S28 Operation Mode X A Y A X A Y...

Страница 85: ...within 20 minutes the unit will Stop operation Timer LED blinks and F91 indicated 13 7 Compressor Tank Temperature Rise Protection Control Control start conditions o For 5 minutes the compressor cont...

Страница 86: ...her than 5 C At the same time indoor fan speed will be higher than during its normal operation If indoor heat exchanger is higher than 5 C for 5 minutes the fan speed will return to its normal operati...

Страница 87: ...ontrol and timer preliminary operation this control is not applicable o Control content Depends on compressor conditions 1 Compressor OFF Compressor ON The indoor unit fan stops temporarily and then s...

Страница 88: ...control to transmit and store the desired transmission code to the EEPROM There are 4 types of remote control transmission code could be selected The indoor unit will only operate when received signa...

Страница 89: ...returns to original display after 2 seconds o LCD returns to original display if remote control does not operate for 30 seconds 14 2 2 RESET RC To clear and restore the remote control setting to facto...

Страница 90: ...Mpa kg cm 2 G Outlet air Temperature C Cooling Mode 0 9 1 2 9 12 12 16 Condition Indoor fan speed High Outdoor temperature 35 C at cooling mode Compressor operate at rated frequency Different in the i...

Страница 91: ...w Pressure High Pressure Electric current during operation Insufficient refrigerant gas leakage Clogged capillary tube or strainer Short circuit in the indoor unit Heat radiation deficiency of the out...

Страница 92: ...2 3 To Display Memorized Error Code Protective Operation 1 Turn power on 2 Press the CHECK button on the remote control 3 will be displayed on the remote control display Note Display only for No sign...

Страница 93: ...5 days Light sensor defective or disconnected H97 Outdoor fan lock abnormality 2 occurrences within 30 minutes Outdoor fan motor locked H98 Indoor temperature rise abnormality Air filter dirty Air cir...

Страница 94: ...mission is checked whether it is normal Malfunction Caused Faulty indoor unit PCB Faulty outdoor unit PCB Indoor unit outdoor unit signal transmission error due to wrong wiring Indoor unit outdoor uni...

Страница 95: ...re interconnected Malfunction Caused Wrong models interconnected Wrong indoor unit or outdoor unit PCBs mounted Indoor unit or outdoor unit PCBs defective Indoor outdoor unit signal transmission error...

Страница 96: ...alfunction Decision Conditions During startup and operation of cooling the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors Malfunction Caused Faul...

Страница 97: ...nction Decision Conditions During startup and operation of cooling the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors Malfunction Caused Faulty...

Страница 98: ...ons A current transformer CT is detected by checking the compressor running frequency rated frequency and CT detected input current less than 1 14 A for continuously 20 seconds Malfunction Caused CT d...

Страница 99: ...ermine abnormal fan motor feedback of rotation 2550 rpm or 50 rpm Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside th...

Страница 100: ...ction Decision Conditions During startup and operation of cooling the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors Malfunction Caused Fault...

Страница 101: ...System Abnormal Malfunction Decision Conditions During standby of cooling operation nanoe G breakdown occurs and air conditioner stops operation Malfunction Caused Faulty indoor main PCB Faulty indoor...

Страница 102: ...alfunction Decision Conditions During startup and operation of cooling the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors Malfunction Caused Faulty con...

Страница 103: ...Malfunction Decision Conditions During startup and operation of cooling the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors Malfunction Caused Faulty c...

Страница 104: ...alfunction Decision Conditions During startup and operation of cooling the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors Malfunction Caused...

Страница 105: ...alfunction Decision Conditions The supply power is detected for its requirement by the indoor outdoor transmission Malfunction Caused Wrong models interconnected Wrong indoor unit and outdoor unit PCB...

Страница 106: ...sion Conditions Feedback signal of human activity sensor Malfunction Caused Feedback signal is fixed at 0 VDc or 5 VDc continuously for 25 seconds during ECONAVI or AUTO COMFORT operation Feedback sig...

Страница 107: ...107 15 4 14 H70 Light Sensor Abnormality Malfunction Decision Conditions Feedback signal of light sensor Malfunction Caused Feedback value is 0 VDC continuously Troubleshooting...

Страница 108: ...ration is used to determine abnormal fan motor Malfunction Caused Operation stops due to short circuit inside the fan motor winding Operation stops due to breaking of wire inside the fan motor Operati...

Страница 109: ...n Conditions The temperature detected by the indoor pipe temperature sensor is abnormal Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air...

Страница 110: ...on control takes place when indoor pipe temperature is lower than 2 C Malfunction Caused Clogged air filter of the indoor unit Dust accumulation on the indoor unit heat exchanger Air short circuit Det...

Страница 111: ...function Decision Conditions When cooling operation when indoor pipe temperature or indoor heat exchanger temperature sensor is above 45 C Malfunction Caused Faulty connector connection Faulty indoor...

Страница 112: ...and operation of cooling when Power Factor Correction PFC protection circuitry at the outdoor unit main PCB senses abnormal high DC voltage level Malfunction Caused DC voltage peak due to power suppl...

Страница 113: ...cooling and heating operation running current 0 65 A I 1 65 A During cooling indoor intake indoor pipe 4 C Malfunction Caused Refrigerant shortage refrigerant leakage Poor compression performance of c...

Страница 114: ...lfunction Decision Conditions A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit Malfunction Caused Compressor terminal disco...

Страница 115: ...detected by the outdoor pipe temperature sensor Malfunction Caused Outdoor pipe temperature rise due to short circuit of hot discharge air flow Outdoor pipe temperature rise due to defective of outdo...

Страница 116: ...ata 100 C is detected by the IPM temperature sensor Malfunction Caused IPM overheats due to short circuit of hot discharge air flow IPM overheats due to defective of outdoor fan motor IPM overheats du...

Страница 117: ...peration of cooling when compressor tank temperature data 112 C is detected by the compressor tank temperature sensor Malfunction Caused Refrigerant shortage refrigerant leakage 2 3 way valve closed D...

Страница 118: ...being detected by current transformer CT with the compressor running Malfunction Caused Over current due to compressor failure Over current due to defective outdoor unit PCB Over current due to defect...

Страница 119: ...when inverter DC peak data is received by the outdoor internal DC peak sensing circuitry Malfunction Caused DC current peak due to compressor failure DC current peak due to defective power transistor...

Страница 120: ...apacitor has discharged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 16 1 CS S9PK CS S12PK 16 1 1 Indoor Electronic Controllers Cross Flow...

Страница 121: ...121 Figure 3 Figure 4 16 1 1 3 To Remove Discharge Grille Figure 5...

Страница 122: ...122 16 1 1 4 To Remove Control Board Figure 6 16 1 1 5 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 Figure 8...

Страница 123: ...123 Figure 9 Figure 10...

Страница 124: ...ged sufficiently before proceeding with repair work Failure to heed this caution may result in electric shocks 16 2 CS S18PK CS S24PK CS S28PK 16 2 1 Indoor Electronic Controllers Cross Flow Fan and I...

Страница 125: ...125 16 2 1 3 To Remove Power Electronic Controller Figure 13 Figure 14 Figure 15...

Страница 126: ...126 16 2 1 4 To Remove Discharge Grille Figure 16 16 2 1 5 To Remove Control Board Figure 17 16 2 1 6 To Remove Cross Flow Fan and Indoor Fan Motor Figure 18...

Страница 127: ...127 Figure 19 Figure 20 Figure 21...

Страница 128: ...nical Data 17 1 Operation Characteristics 17 1 1 CS S9PKV CU S9PKV Cooling Characteristic o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Piping length 7 5m o Compressor Fr...

Страница 129: ...129 Piping Length Characteristic Cooling o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Outdoor temperature 35 C DBT 24 C WBT o Compressor Frequency Fc...

Страница 130: ...130 17 1 2 CS S12PKV CU S12PKV Cooling Characteristic o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Piping length 7 5m o Compressor Frequency Fc...

Страница 131: ...131 Piping Length Characteristic Cooling o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Outdoor temperature 35 C DBT 24 C WBT o Compressor Frequency Fc...

Страница 132: ...132 17 1 3 CS S18PKV CU S18PKV Cooling Characteristic o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Piping length 5m o Compressor Frequency Fc...

Страница 133: ...133 Piping Length Characteristic Cooling o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Outdoor temperature 35 C DBT 24 C WBT o Compressor Frequency Fc...

Страница 134: ...134 17 1 4 CS S24PKV CU S24PKV Cooling Characteristic o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Piping length 5m o Compressor Frequency Fc...

Страница 135: ...135 Piping Length Characteristic Cooling o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Outdoor temperature 35 C DBT 24 C WBT o Compressor Frequency Fc...

Страница 136: ...136 17 1 5 CS S28PKV CU S28PKV Cooling Characteristic o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Piping length 5m o Compressor Frequency Fc...

Страница 137: ...137 Piping Length Characteristic Cooling o Room temperature 27 C DBT 19 C WBT o Operation condition High fan speed o Outdoor temperature 35 C DBT 24 C WBT Compressor Frequency Fc...

Страница 138: ...w and Replacement Parts List 18 1 Indoor Unit 18 1 1 CS S9PKV CS S12PKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as stan...

Страница 139: ...CWA746653 O 21 LEAD WIRE PCB ECO 1 CWA67C9785 22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407 23 CONTROL BOARD TOP COVER 1 CWH131467 24 INDICATOR HOLDER 1 CWD933406 25 CONTROL BOARD FRONT COVER CO 1 C...

Страница 140: ...S S12PKV REMARK 50 BAG 1 CWG861497 51 SHOCK ABSORBER L 1 CWG713386 52 SHOCK ABSORBER R 1 CWG713387 53 C C CASE 1 CWG568976 CWG568977 Note All parts are supplied from PAPAMY Malaysia Vendor Code 000294...

Страница 141: ...141 18 1 2 CS S18PKV CS S24PKV CS S28PKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 142: ...ENSOR 1 CWA746206 O 20 ELECTRONIC CONTROLLER COMPARATOR 1 CWA746653 O 21 LEAD WIRE PCB ECO 1 CWA67C9934 22 CONTROL BOARD CASING FOR PCB ECO 1 CWD933407A 23 CONTROL BOARD TOP COVER 1 CWH131467 24 INDIC...

Страница 143: ...5730 CWF615732 49 POWER SUPPLY CORD COMPLETE 1 CWA20C2851 CWA20C2853 50 BAG 1 CWG861498 51 SHOCK ABSORBER L 1 CWG713402 52 SHOCK ABSORBER R 1 CWG713403 53 C C CASE 1 CWG568978 CWG568979 CWG568980 Note...

Страница 144: ...144 18 2 Outdoor Unit 18 2 1 CU S9PKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 145: ...ND PROOF MATERIAL 1 CWG302700 22 SENSOR CO COMP TEMP 1 CWA50C3062 O 23 CONTROL BOARD COVER TOP 1 CWH131324 24 ELECTRONIC CONTROLLER MAIN 1 CWA73C7401R O 25 ELECTRONIC CONTROLLER NF 1 CWH14C7640 O 26 T...

Страница 146: ...146 18 2 2 CU S12PKV 41 42 39 40 37 38 Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 147: ...F BOARD 1 CWH151172 21 SOUND PROOF MATERIAL 1 CWG302431 22 SENSOR CO COMP TEMP 1 CWA50C2205 O 23 CONTROL BOARD COVER TOP 1 CWH131264 24 ELECTRONIC CONTROLLER MAIN 1 CWA73C7366R O 26 TERMINAL BOARD ASS...

Страница 148: ...148 18 2 3 CU S18PKV CU S24PKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 149: ...TERMINAL COVER 1 CWH7080300J 22 SENSOR CO COMP TEMP 1 CWA50C2185 O 26 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2517 O 28 REACTOR 1 G0C153J00005 O 29 TERMINAL BOARD ASSY 1 CWA28K1036J O 30 ELECTRONIC C...

Страница 150: ...150 18 2 4 CU S28PKV Note The above exploded view is for the purpose of parts disassembly and replacement The non numbered parts are not kept as standard service parts...

Страница 151: ...L COVER 1 CWH171039A 25 NUT TERMINAL COVER 1 CWH7080300J 30 SENSOR CO COMP TEMP 1 CWA50C2656 O 31 SENSOR CO AIR TEMP AND PIPE TEMP 1 CWA50C2517 O 32 REACTOR 1 G0C452J00002 O 33 CONTROL BOARD COVER 1 C...

Страница 152: ...RIPTION QTY CU S28PKV REMARK 59 SHOCK ABSORBER 1 CWG712880 60 C C CASE 1 CWG568834 Note All parts are supplied from PHAAM Malaysia Vendor Code 00029488 O marked parts are recommended to be kept in sto...

Отзывы: