77
12.14.1.7 Setting Position Judgment
According to installation position when there is only one activity area detected, the horizontal airflow direction
louver position is fixed according to chart below:
Horizontal airflow direction louver position
Target area
Left installation
Center installation
Right installation
A 3 2 2
B 1 1 1
C 5 5 4
Louver position refer to horizontal airflow direction control.
When 2 activity areas have been detected, according to Human Activity Level, the timing of horizontal airflow
direction louver steps at the targeted activity areas is judged.
Operation Mode
Activity level difference
Louver stop time
Higher Activity level
≈
60 seconds
1 level
Lower Activity level
≈
30 seconds
Higher Activity level
≈
60 seconds
Cooling
2 levels
Lower Activity level
≈
8 seconds
When 3 activity areas have been detected, according to Human Activity Level the timing of horizontal airflow
louver steps at the targeted activity areas is judged.
Operation Mode
Activity level
Louver stop time
Hi
≈
45 seconds
Me
≈
30 seconds
Cooling
Lo
≈
20 seconds
When 3 activity areas have same activity level, the horizontal airflow direction louver will swing left and right.
12.14.1.8 Setting Temperature and Fan Speed Shift
Cooling Dual Sensor
* During low activity, fan speed 1 tap up for first 15 minutes or until set temperature is reached.
** During human absence, maximum fan speed for COOL/DRY mode is medium fan.
Содержание cs-s9pkv
Страница 12: ...12 4 Dimensions 4 1 Indoor Unit 4 1 1 CS S9PKV CS S12PKV...
Страница 13: ...13 4 1 2 CS S18PKV CS S24PKV CS S28PKV...
Страница 14: ...14 4 2 Outdoor Unit 4 2 1 CU S9PKV 4 2 2 CU S12PKV 542...
Страница 15: ...15 4 2 3 CU S18PKV CU S24PKV...
Страница 16: ...16 4 2 4 CU S28PKV...
Страница 17: ...17 5 Refrigeration Cycle Diagram 5 1 CS S9PKV CU S9PKV CS S12PKV CU S12PKV...
Страница 18: ...18 5 2 CS S18PKV CU S18PKV CS S24PKV CU S24PKV...
Страница 19: ...19 5 3 CS S28PKV CU S28PKV...
Страница 20: ...20 6 Block Diagram 6 1 CS S9PKV CU S9PKV...
Страница 21: ...21 6 2 CS S12PKV CU S12PKV...
Страница 24: ...24 7 Wiring Connection Diagram 7 1 Indoor Unit 7 1 1 CS S9PKV CS S18PKV CS S24PKV...
Страница 26: ...26 7 1 3 CS S28PKV...
Страница 31: ...31 8 Electronic Circuit Diagram 8 1 Indoor Unit 8 1 1 CS S9PKV CS S18PKV CS S24PKV...
Страница 32: ...32 8 1 2 CS S12PKV...
Страница 33: ...33 8 1 3 CS S28PKV...
Страница 35: ...35 8 2 2 CU S12PKV...
Страница 39: ...39 9 1 1 2 CS S12PKV...
Страница 41: ...41 9 1 5 Human Activity Sensor Printed Circuit Board...
Страница 42: ...42 9 2 Outdoor Unit 9 2 1 Main Printed Circuit Board 9 2 1 1 CU S9PK...
Страница 43: ...43 9 2 1 2 CU S12PK...
Страница 44: ...44 9 2 1 3 CU S18PK CU S24PK...
Страница 45: ...45 9 2 1 4 CU S28PK...
Страница 46: ...46 9 2 2 Noise Filter Printed Circuit Board 9 2 2 1 CU S9PKV...
Страница 47: ...47 9 2 2 2 CU S28PKV...
Страница 51: ...51...
Страница 60: ...60...
Страница 121: ...121 Figure 3 Figure 4 16 1 1 3 To Remove Discharge Grille Figure 5...
Страница 122: ...122 16 1 1 4 To Remove Control Board Figure 6 16 1 1 5 To Remove Cross Flow Fan and Indoor Fan Motor Figure 7 Figure 8...
Страница 123: ...123 Figure 9 Figure 10...
Страница 125: ...125 16 2 1 3 To Remove Power Electronic Controller Figure 13 Figure 14 Figure 15...
Страница 127: ...127 Figure 19 Figure 20 Figure 21...