Fire alarm systems 

Address setting tool 

4414 

 

Used for COM loop address and mode settings 

COM loop address setting 

Address  setting  tool  4414  is  used  to  set  the 
COM  loop  unit's 

address

  (001-255)  on  the 

analog detector types 33xx / 430x / 440x and 
all other addressable COM loop units (33xx 
/ 43xx / 44xx). 

Mode setting 

The address setting tool 4414 is also used to 
set the COM loop unit's 

mode

:   

M0

 = NORMAL mode   

M1

 = 2330 mode     

(COM loop address 001-127)

 

M2

 = 2312 mode     

(COM loop address 001-127)

 

M3

 = Advanced mode   

See  instructions  for  the  COM  loop  unit 
respectively.   

Connection cable 

Some units have flying leads and some units 
only  screw  terminals.    A  connection  cable 
with  insulated  crocodile  clips  and  push-on 
terminals is supplied with the address setting 
tool, to be used for the COM loop units that 
cannot be plugged directly on the tool. 

User friendly 

The address setting tool is powered by four 
1.5 V Alkaline batteries  (LR6 / AA).  
Battery life time is approx. 250 hours or up 
to 50000 readings / writings. 

An analog detector's contact pins (SA / SB) 
are  plugged  into  the  address  setting  tool's 
snap connectors (SA / SB).  The connection 
cable is used to connect to other units. 

The  tool  is  turned  on  by  the 

On/Off  /  CLR

 

button.    "

"  and  a  blinking  cursor  will  be 

shown in the display. 

How to read: 

 

Turn on the tool. 

 

Press the 

Read

 button.   

 

Wait  for a  beep  ("

READ

" will  be  shown 

in the display). 

 

"

OK

",  the  address  and  the  mode  will  be 

shown in the display. 

How to write: 

 

Turn on the tool. 

 

Default mode is M0 (NORMAL mode).  
The  mode  can  be  changed  by  pressing 
the 

Write

  and 

Read

  buttons  at  the  same 

time and then select a mode (0-3). 

 

Type the COM loop address (001-255) 

 

Press the 

Write

 button.   

 

Wait for a beep ("

WRITE

" will be shown 

in the display). 

 

"

OK

",  the  address  and  the  mode  will  be 

shown in the display. 

Write the COM loop address on the Address 
label on the COM loop unit respectively.  

If  the  tool  is  not  used  for  approx.  20 
seconds,  it  will  be  automatically  turned  off 
in order to save the batteries. 

Product applications 

Used  for  address  and  mode  settings  when 
analog detectors and other addressable COM 
loop  units  are  to  be  used  in  the  systems 
EBL128 / 512 / 512 G3. 

4414  has  to  be  used  to  set  the  analog 
detectors 440x in Advanced mode. 