background image

 
 
 

Panasonic Electric Works Fire & Security Technology Europe AB 

 

Citadellsvägen 23, SE-211 18 Malmö, Sweden 

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 

[email protected] • www.panasonic-fire-security.com 

 

Fire alarm systems 

External Presentation unit 

1728 

 

For presentation of pre-warnings, fire alarms, faults & disablements 

 

Compact size 

Presentation unit 1728 

This unit (S/W V1.2) is intended for pre-
warning, fire and heavy smoke / heat alarm 

presentation

.  Point or zone alarm 

presentation is like in the c.i.e. it is 
connected to.  You can scroll amongst two 
or more alarms in the system but the fire 
alarms can not be reset via this unit.  All or 
selected alarms will be presented in a 
display (LCD, 2x40 characters with back-
light).  An alarm text will be presented 
together with each alarm, if programmed in 
the c.i.e.  Furthermore, >617 texts for 
selected alarms can be stored in the unit and 
will in such a case be shown, instead of the 
texts sent from the c.i.e. for these alarms.  A 
built-in buzzer will sound like in the c.i.e.  It 
can be silenced but the alarm devices in the 
installation can not be silenced via this unit.  
Any fault in the system will be presented as 
"General fault in system" and the buzzer will 
sound.  It can be silenced.  Any disablement 
in the system will be presented as "General 
disablement in system".  The unit is power 
supplied via the c.i.e. or external power 
supply. 

LEDs, push buttons etc. 

The unit has the following LEDs: 

 

Fire

 (Brand) and 

Alarms queued

 

(Flera larm), indicating pre-warning, 
co-incidence and fire alarms. 

 

Operation

 (Drift), indicating that the 

unit is connected to a c.i.e. and power 
supplied, i.e. it is in operation. 

 

Extinguishing

 (Släckanläggning 

aktiverad), indicating activated output 
for extinguishing equipment. 

 

Ventilation

 (Brandventilation 

aktiverad), indicating activated output 
for ventilation equipment. 

 

Fire brigade tx

 (Larmsändare 

aktiverad), indicating activated output 
for Fire brigade tx (routing equipment). 

The unit has the following push buttons: 

 

Alarms queued

 (Flera larm), used to 

scroll amongst the alarms. 

 

Silence buzzer

 (Summer tyst), used to 

silence the buzzer (it will re-sound for a 
new alarm). 

The designation texts on the front are in 
1728SE in Swedish and in 1728UK in 
English. 

Compact size 

The compact size enclosure is made of grey 
high impact ABS.  Fitted with a supple-
mentary "O" ring gasket, it will comply with 
IP61, in respect of dust and moisture.  The 
push buttons on the front are disabled until 
they are supposed to be used.  The unit shall 
be wall mounted.  Two compression glands 
are attached. 

SW mode and address setting 

The display and the push buttons are used to 
set the 

SW mode

 and 

address

, see the 

opposite side of this page. 

Product application 

The 1728 unit is intended for indoor use and 
in dry premises.  SW mode 

1728 - 1587

 is 

intended to be used in the systems EBL512 
and EBL128 and SW mode 

1728 – 1582

 in 

the systems EBL500 / 512 / 1000 / 2000.   