PanaFlow™ MV80, MV82 & MV84 User’s Manual
107
Chapter 4. Serial Communications
4.2.4
Wiring
An RS485 daisy chained network configuration, as shown in
below, is recommended. Do not use a star, ring,
or cluster arrangement.
RS-485 –
RS-485 +
RS-485 GND
RS-485 –
RS-485 +
RS-485 GND
RS-485 –
RS-485 +
RS-485 GND
RS-485 –
RS-485 +
RS-485 GND
RS-485 Master
Other Device 1
Vortex Meter
Other Device 2, etc.
Figure 119: RS-485 Modbus Wiring
4.2.5
Pin Labeling Among Devices
•
RS-485 –
= “A” = “TxD–/RxD–” = “Inverting pin”
•
RS-485 +
= “B” = “TxD+/RxD+” = “Non-Inverting pin”
•
RS-485 GND
= “GND” = “G” = “SC” = “Reference”
Содержание PanaFlow MV80
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 20: ...Chapter 1 Introduction 8 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 108: ...Chapter 3 Operating Instructions 96 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 140: ...Chapter 4 Serial Communications 128 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 166: ...Appendix A Product Specifications 154 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 168: ...Appendix B Approvals 156 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 176: ...Appendix C Flow Meter Calculations 164 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 180: ...Appendix D Glossary 168 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 182: ...Warranty 170 PanaFlow MV80 MV82 MV84 User s Manual no content intended for this page...
Страница 183: ......