Model CTF878 Startup Guide
5
Chapter 2.
Chapter 2.
2.1
Install
2.1.1
Introduction
To ensure safe and reliable operation of the CTF878 Clamp-on Tag Flowmeter, the system must be installed in
accordance with the guidelines set forth in this manual. Those guidelines, which are explained in detail in this
chapter, include the following topics:
•
Unpacking
•
System Parts
•
Tools for Installation
•
Installing the Electronics Console
•
Installing a CFT-V Clamping Fixture
•
Installing a CFT-PI Clamping Fixture
•
Installing Transducers
•
Installing Temperature and Pressure Transmitters
•
PC Board Connections
•
Option Card Wiring
WARNING!
The CTF878 flowmeter can measure the flow rate of many gases, some of which are potentially
hazardous. In such cases, the importance of proper safety practices
cannot be overemphasized.
Be sure to follow all applicable local safety codes and regulations for installing electrical equipment
and working with hazardous gases or flow conditions. Consult company safety personnel or local
safety authorities to verify the safety of any procedure or practice.
WARNING!
In order to meet CE Mark requirements, all wiring connections must be made in accordance with the
instructions in Appendix A,
CE Mark Compliance
.
2.1.2
Unpacking
Carefully remove the electronics console, the clamping fixture, the transducers, the cables, and any other equipment
ordered from the shipping containers (see Figure 2 on page 6). Before discarding any of the packing materials,
account for all components and documentation listed on the packing slip. The discarding of an important item along
with the packing materials is all too common. If anything is missing or damaged, contact the factory immediately for
assistance.
2.1.3
System Parts
The following is a list of parts required for a typical CTF878 system. Figure 2 below displays several system
components.
•
CTF878 Flowmeter
•
Clamping Fixture
•
CFT-V8 for pipes between 6” and 8”, or
•
CFT-V12 for pipes between 8” and 12”, or
•
CFT-PI for pipes larger than 12”
•
2 Straps or Chains (to install a CFT-PI Clamping Fixture only)
•
4 Transducers
•
4 Conduit Boxes (2 with internal preamplifiers and 2 without)
•
4 Cables with integral BNC connectors (not shown)
•
Damping Material (not shown)
Содержание CTF878
Страница 1: ...panametrics com Flow 910 254U Rev A AUG 2021 Model CTF878 Clamp On Tag Flowmeter Startup Guide...
Страница 2: ......
Страница 4: ...ii no content intended for this page...
Страница 6: ...Warranty iv Model CTF878 Startup Guide no content intended for this page...
Страница 8: ...Contents vi Model CTF878 Startup Guide...
Страница 76: ...Model CTF878 Startup Guide 68...
Страница 96: ...Appendix A 88 Model CTF878 Startup Guide...
Страница 99: ...Model CTF878 Startup Guide 91 Appendix B 9 21 10 22 11 23 12 24...
Страница 100: ...Appendix B 92 Model CTF878 Startup Guide...
Страница 104: ...Index 96 Doc Tittle Manual Type...
Страница 106: ......
Страница 107: ......