INSTALLER 

INFORMATION 

 

 

Important Note for the Commonwealth of Massachusetts: 

 

From Massachusetts Rules and Regulations 248 CMR 5.08: 

 

(a) 

For all side wall horizontally vented gas fuelled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the 

area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied. 

 

1. 

INSTALLATION OF CARBON MONOXIDE DETECTORS.  At the time of installation of the side wall horizontal vented gas fuelled equipment, the 

installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the 

gas equipment is to be installed, in addition, the installing plumber or gas fitter shall observe that a battery operated or hard-wired carbon monoxide detector with 

an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fuelled equipment.  It shall be the 

responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard-wired carbon monoxide detectors.   

 

a. 

In the event that the side wall horizontally vented gas fuelled equipment is installed in a crawl space or an attic, the hard-wired carbon monoxide detector 

with alarm and battery back-up may be installed on the next adjacent floor level. 

 

b. 

In the event that the requirements of this subdivision cannot be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall 

be installed. 

 

2. 

APPROVED CARBON MONOXIDE DETECTORS.  Each carbon monoxide detector as required in accordance with the above provisions shall comply 

with NFPA 720 and be ANSI/UL 2034 listed as IAS certified. 

 

3. 

SIGNAGE.  A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above 

grade directly in line with the exhaust vent terminal for the horizontally vented gas fuelled heating appliance or equipment.  The sign shall read, in print size no less 

than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  KEEP CLEAR OF ALL OBSTRUCTIONS”. 

 

4. 

INSPECTION.  The state or local gas inspector of the side wall horizontally vented gas fuelled equipment shall not approve the installation unless, upon 

inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.089(2)(a) 1 through 4. 

 

(b) 

EXEMPTIONS.  The following equipment is exempt from 248 CMR 5.089(2)(a) 1 through 4. 

1. 

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and  

2. 

Product Approved side wall horizontal vented gas fuelled equipment installed in a room or structure separate from the dwelling, building or structure used in 

whole or in part for residential purposes. 

 

(c) 

MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM PROVIDED.  When the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the 

manufacturer for installation of the equipment and the venting system shall include:  

1. 

Detailed instructions for the installation of the venting system design or the venting system components; and 

2. 

A complete parts list for the venting system design or venting system. 

 

(d) 

MANUFACTURER REQUIREMENTS – GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  When the manufacturer of a Product Approved 

side wall horizontally vented gas fuelled equipment does not provide the parts for venting the fuel gases, but identifies “special venting systems”, the following 

requirements shall be satisfied by the manufacturer. 

1. 

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

2. 

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation 

instructions. 

 

(e)) 

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fuelled equipment, all venting instructions, all parts 

lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

Содержание Gmir.Bodya

Страница 1: ...diately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed...

Страница 2: ...ireplace 16 Venting 17 Plumbing and Electrical 19 Gas Supply 20 Gas Pressure Check 20 Gas Pressure Testing Procedure 21 Pilot Adjustment 21 Propane Conversion 22 Door Installation Removal 23 Fan Insta...

Страница 3: ...psi 3 5 kPa This appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressu...

Страница 4: ...ot viewing glass is provided with the appliance and shall be installed If the barrier becomes damaged the barrier shall be replaced with the manufacturers barrier for this appliance Any grill panel or...

Страница 5: ...manual and pay close attention to all Safety Warnings The manual contains important information on the unit s safe operation and maintenance When lit for the first time the fireplace will emit a sligh...

Страница 6: ...gas valve and stepper motor Transmitter Remote Control with LCD Display The Proflame Transmitter uses a streamline design with a simple button layout and informative LCD display Figure 1 The transmit...

Страница 7: ...itter is used then press the button SW1 to exit the synchronization phase The system is now initialized IFC Module The Proflame 2 Integrated Fireplace Control IFC board is a device that allows the aut...

Страница 8: ...of the command Turn off the Appliance With the system ON press the ON OFF key on the transmitter The transmitter LCD display will only show the room temperature At the same time the IFC will be comman...

Страница 9: ...display on the transmitter will change to show that the room thermostat is ON and the set temperature is now displayed Figure 7 To adjust the set point press the up or down arrow keys until the desire...

Страница 10: ...0 Use the Up Down Arrow Keys Figure 1 to turn on off or adjust the fan speed Figure 10 A single beep will confirm reception of the command Continuous Pilot Intermittent Pilot CPI IPI selection With th...

Страница 11: ...point etc When the IFC batteries are low a double beep will be emitted from the IFC board when it receives a command from the transmitter This is an alert for a low battery condition for the IFC boar...

Страница 12: ...r assemblies for soot buildup If excessive buildup of soot is present have a qualified service person inspect and adjust unit for proper combustion Clean burners with a brush or vacuum cleaner paying...

Страница 13: ...13 OWNER S INFORMATION Section 2 Lighting Instructions...

Страница 14: ...ve grade directly in line with the exhaust vent terminal for the horizontally vented gas fuelled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size...

Страница 15: ...R SIDE WALL 4 INTERIOR BACK WALL 4 INTERIOR CEILING 4 IN FRONT OF APPLIANCE 36 EXTERIOR SIDE WALL 8 VENTING CLEARANCE 1 EXTERIOR SOFFIT 30 NCR STANDS FOR NO CLEARANCE REQUIRED YOU MAY USE COMBUSTIBLE...

Страница 16: ...is to be installed location of vent system and where gas supply piping may be plumbed Various installations are possible such as next to an existing wall a corner an alcove or a wall projection Due to...

Страница 17: ...st be constrained to the boundaries of this chart A Maximum of three 3 90 elbows may be used Only one 1 90 elbow or combination of other elbows equalling 90 can be used without reducing horizontal run...

Страница 18: ...gure 17 Venting This fireplace is certified for use with 4 x 6 5 8 coaxial venting components only It is permitted to only use certified venting for this appliance See charts on page 29 for a list of...

Страница 19: ...ections start by positioning the gas fireplace Connect the gas supply line to the 1 2 flare fitting at the rear of the unit as seen in Figure 16 Please see the gas supply section of the manual for req...

Страница 20: ...ply line going to the gas control valve to minimize the possibility of any loose scale or dirt within the gas supply line from entering the control valve It is essential that a union or flanged connec...

Страница 21: ...ints on the valve which can be seen in Figure 18 After locating test ports loosen the screws within the ports using a flat tip screwdriver 3 Attach pressure gauge to the test ports 4 Turn gas supply b...

Страница 22: ...to ensure a proper seal when installed To replace the pilot orifice you will need to remove the pilot hood which is held in place by a spring First remove the spring and then remove the hood by pulli...

Страница 23: ...al Installation 1 Connect wiring to the fan and insert into the fireplace through the side of the unit 2 Insert both screws into the fan access panel to attach the fan to the unit as in Figure 24 3 Re...

Страница 24: ...the second side panel Removal 1 Remove first side panel by pulling the top edge of panel into the firebox chamber until there is enough room to move the panel away from the wall When you have enough...

Страница 25: ...Burner Tray Glass Kit Installation To install the glass evenly spread a thin layer of crushed glass across the entire burner pan as seen in Figure 30 Figure 30 Glass Installation Log Set Installation...

Страница 26: ...n in Figure 37 6 Slide front side of left side cladding into front clamps as shown in Figure 38 Secure back with hex bolts as shown in Figure 39 7 Repeat step 6 for the right side cladding Removal 1 U...

Страница 27: ...27 INSTALLER INFORMATION Figure 36 Front Cladding Securement Figure 37 Side Cladding Stand Figure 38 Side Cladding Figure 39 Side Cladding Securement...

Страница 28: ...5002 50 10 Replacement Aluker Panel Set GMIR 5099 G958 Aesthetic Components Description Order Number Exterior Ceramic Panels by Piazzetta Mirage Surround Classic Bordeaux PZSY P958CBX Mirage Surround...

Страница 29: ...MATION NOTE Mixing venting components from different manufacturers is inadvisable Figure 40 4 x6 5 8 Rigid Piping Cross Reference Chart Figure 41 4 x6 5 8 Rigid Pipe Components Cross Reference Chart V...

Страница 30: ...NSTALLER INFORMATION Caution Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Wiring Diag...

Страница 31: ...______ __________________________________________________________________________________________________ ______________________________________________________________________________________________...

Страница 32: ......

Отзывы: