23
INSTALLER
INFORMATION
Servicing of the appliance can be performed from the front of the unit by removing the door and the gas tray from the
unit.
Caution
: The gas line should be installed by a qualified service person in accordance with all building codes. This
section is intended as a guide for qualified technicians installing this appliance. Consult local and/or national building
codes before proceeding.
Gas supply line connection is located on the side of the fireplace. Gas
connection accepts a ½” NPT fitting.
Correct gas line diameter must be used to assure proper operation and pressure.
The fireplace input rating is shown in the chart below.
A drip leg must be installed in the gas supply line going to the gas control valve to minimize the possibility of
any loose scale or dirt within the gas supply line from entering the control valve.
Check local codes for additional requirements.
Turn on the gas supply and check that all connections are tight and leak free.
WARNING: The gas tray including gasket must be reinstalled after
conversion/installation or servicing has been completed.
Gas Pressure Check
Please refer to following page for gas pressure testing procedure.
Gas Supply
Gas pressure requirements
Input Pressure
Natural Gas
Propane
Minimum
5.0" WC
12.5" WC
Maximum
13.9" WC
13.9" WC
Manifold Pressure
High
3.5" WC
10" WC
Low
1.6" WC
6.4" WC
Esteem
Gas
Orifice Output
AFUE
NG
1.98mm 18,000 btu/hr
76%
LP
1.25mm 17,000 btu/hr
76%
Estate
Gas
Orifice Output
AFUE
NG
2.55mm 30,000 btu/hr
75%
LP
1.52mm 26,000 btu/hr
75%