Mantel
(Reference point)
36” Min.
26” Min.
louvered
surround
Top of glass
(Reference point)
Figure 22: Minimum distance from top of the glass to ceiling.
36” Min.
Figure 23: Front and side
dimensions.
Clearances to Combustibles
Minimum Clearance to Combustible Materials
ENCLOSED SIDE WALL
1.75”
ENCLOSED BACK WALL
NCR*
ENCLOSED CEILING
4”
ECLOSED FRONT WALL
24” From top of the glass
EXPOSED SIDE WALL
8” From side of the glass
VENT ENCLOSURE
1”
EXTERIOR SOFIT
16”
*NCR STANDS FOR NO CLEARANCE REQUIRED; YOU MAY USE COMBUSTIBLE
CONSTRUCTION MATERIALS IN DIRECT CONTACT WITH THE APPLIANCE ON THESE
SURFACES.
When the appliance is installed directly on carpeting, tile or other combustible material other
than wood flooring, the appliance shall be installed on a metal or wood panel extending the full
width and depth of the appliance. Specified clearances shall be maintained from the top surface
of carpeting, tile, etc.
Front of the appliance is an open side of the combustion chamber covered with the glass.
Facing the front of the appliance side from left is the left side of the appliance and side from right is
the right side of the appliance.
17
280617-40
5056.201-A