15
Troubleshooting
Symptom
Possible Cause
Repair
System does not run
Alarm Condition
-
Message in alarm log
Resolve alarm condition
No Power
Check and repair incoming power
External stop contacts
Ensure external contacts are open
Flow less than 5 gpm flow switch not ac-
tive
Increase water flow
Low dissolved ozone levels
Water is contaminated
Check water quality, repair upstream deficiencies
Water is too warm
Lower water temperature
Dissolved ozone reading is inaccurate
Check dissolved ozone level against another
standard
Oxygen flow is too low
Increase oxygen flow
Water flow is too high
Decrease water flow
Ozone Output is low
Increase ozone generator output
ORP high
Check ORP Set
-
points
Low outlet pressure
Increase inlet flow/pressure or decrease outlet
flow
Low O2 flow
Low O2 Pressure
See section above
Flow restriction
Open needle valve or dislodge restriction
Venturi pressure differential too low
Check water pressure being too high, check in-
jector & water pump operation
Damaged O2 Regulation Valve
Replace regulation valve
Low Air Pressure
Air leak inside ozone generator
Find and repair air leak
Pressure regulator requires adjustment
Adjust pressure regulator
Low O2 Pressure
O2 or O3 Leak
Find and repair leak
Air Pressure Low
See low air pressure