Operation procedures
Version 1.3, 2021-12-14
61
1
2
3
4
5
Status value
Reading
Unit
Brief description
W27:A-ExhaustAir
Status
Output value for building exhaust output (optional damper, fan or
Natural Ventilator box) (0% to 100% = 0 V to 10 V).
W28:A-OutdoorAir
Status
Output value for outdoor air/ventilation output (optional damper)
(0% to 100% = 0 V to 10 V)
(0% = closed / recirculation to 100% = 100% fresh air).
W29:A-AirOptimiz
Status
Output value for AirOptimizer (optional) exhaust output (damper or
fan) (0% to 100% = 0 V to 10 V)
( 0% = heating 'vertical' to 100% = cooling 'horizontal').
W30:A-Heating
Status
Output value for required heating capacity (external heat source)
(0% to 100% = 0 V to 10 V).
W31:Error codes
Status
Active errors (01 = only error code 01 and 01,03,06 = error codes 1, 3
and 6).
W32:Time
-
hh:mm:ss
Local time derived from thermostat.
W33:Software version
-
Shows the current software version on the Oxylogic.
5.2.4
Operating modes
Operating modes
Operating mode
Description
Heat reclaim
Unit is in heating mode (only when Heat Reclaim is activated).
Free cooling
Unit is in free cooling mode (cooling with outdoor air without water).
Standby
Stand-by.
Tank fill
Unit is filling the water tank.
Pre-wet
Unit is soaking the evaporative media (fans at low speed).
Cooling
Unit is in cooling mode.
OverflowProt
Drain valve open (short) to prevent tank overflow.
Drain
Unit drains the tank.
Rinse
Unit rinses/flushes the tank.
Hygiene dry-out
Unit is in hygiene dry-out mode.
System locked
Unit is locked. Error type A active.
5.2.5
Settings menu
To change a setting follow the procedure below::
1. Activate the settings menu: Press navigation button [1] and [2]
simultaneously for two seconds.
2. Scroll to setting to be changed: Press navigation button [2].
3. Edit setting: Press navigation button [1].
Содержание 3800OXYSTD
Страница 2: ......
Страница 4: ...4 ...
Страница 10: ...10 ...
Страница 12: ...Sticker manuals inside 12 ...
Страница 40: ... J12 0 no circuit Free Cooling 1 circuit Cooling J23 Alarm signal collective feedback to AHU 40 ...
Страница 52: ...52 ...
Страница 67: ...Version 1 3 2021 12 14 67 Appendices ...
Страница 68: ...68 ...