Prepare the location
Version 1.3, 2021-12-14
39
1
2
3
4
5
-
Power supply to the external fuse.
-
4x0.75 mm
2
(shielded) cabling to and between OxyConnect the thermostats
and the IntrCooll®s.
Note
The gateway control box must be placed indoors.
3.16.3
Control by a Building Management System
IntrCooll® can be connected to a Modbus RTU (RS485) Building Management
System (BMS) as slave device.
The contractor must take care of the control system that regulates the
temperature control, fan speed and operation mode.
The Modbus interface information is available in a separate document. This can
be requested at Oxycom.
3.16.4
Control by an air handling unit
For pre-cooling purposes, the IntrCooll® can be controlled by and synchronized
with an air handling unit (AHU). There are two different control options:
-
Modbus RTU (RS485)
-
Analog control (6 wire cable)
3.16.4.1
Modbus RTU (RS485)
Controller I/0
I/0 type
I/0 function
Protocol
Connection type
Connection
J17
Isolated RS485 port
Modbus control
Modbus RTU
2-wire
Pin 1) A-
Pin 3) B+
3.16.4.2
Analog control (6-wire cable)
Controller I/0
I/0 type
I/0 function
Signal type
Connection type
Connection
J6
Analog input
Fan speed input 0-10V
0 V = 0% fan speed
2-wire
Pin 1) 0 V
10 V = 100% fan speed
Pin 3) 0 V - 10
V input
J12
Digital input
Cooling On/Off
Off (no circuit) = Free Cooling
2-wire
Pin 1) +24
VDC output
On (circuit) = Cooling
Pin 3) Input
J23
Potential free contact
Alarm contact N.O.
Open (no circuit) = No alarm
2-wire
Pin 1) N.O.
Closed (circuit) = Active alarm
Pin 2) P
For the analog control method IntrCooll® PCB must switched to AHU Pre-cooling
mode. The following will apply:
-
J6: When the speed input signal of the external fan is less than 0.2V the unit
will go to stand-by.
Содержание 3800OXYSTD
Страница 2: ......
Страница 4: ...4 ...
Страница 10: ...10 ...
Страница 12: ...Sticker manuals inside 12 ...
Страница 40: ... J12 0 no circuit Free Cooling 1 circuit Cooling J23 Alarm signal collective feedback to AHU 40 ...
Страница 52: ...52 ...
Страница 67: ...Version 1 3 2021 12 14 67 Appendices ...
Страница 68: ...68 ...