Operation
„Aktor M ST L Modbus“
12
101274584-V01.11.2019
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
Bit 7
Illust. 5: DIP switch panel
5.3.1 Assignment
Function
Switch position
OFF
ON
BIT 0
0
1
BIT 1
0
1
BIT 2
0
1
BIT 3
0
1
BIT 4
0
1
BIT 5
0
1
BIT 6 The baud rate is reset to 38.400,8,N,2 by
switching back and forth
BIT 7 Terminal
resistance
Inactive
Active
5.3.2
Address configuration
Address
BIT
5
[32]
BIT
4
[16]
BIT
3
[8]
BIT
2
[4]
BIT
1
[2]
BIT
0
[1]
1
0
0
0
0
0
1
2
0
0
0
0
1
0
3
0
0
0
0
1
1
4
0
0
0
1
0
0
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
63
1
1
1
1
1
1
f
Set the addresses of your actuators as desired.
Each address must only be used once in a
Modbus network.
Z
The actuator will automatically perform an initialisa
-
tion run after setting of the Modbus addresses.
Z
After completion of the initialisation run and com-
missioning of the Modbus interface, the actuator will
follow the control signals.
6. Operation
6.1 Status LED
The status LED is located under the casing cover
above the terminal on the right hand side and dis-
plays the operating status of the actuator.
The status LED is visible even when the
cover is
closed.
Status LED Meaning
Lit green
Normal operation
Flashing
green quick-
ly
Mounting position switch position 0
(switches 1 to 6 set to OFF)
Flashing
green
Initialisation run
Flickering
green
Modbus communication
Flashing
yellow
Manual setting (stem fully extended)
Lit red
Valve adaptation error (initialisation run
without valve)
Off
Operating voltage interrupted
6.2 Parametrization of the bus failure
detection via Modbus
Register
address
Name
Bus com-
munication
Values
133
Bus failure
function
Configura
-
tion
See register
address 133
in section
10.2 on
page 15.
134
Emergency
position
Configura
-
tion
0..100%
If the value 3 has been configured in the register
address 133, the valve emergency position (0-
100 %) configured in the register address 134
will be approached in case of a bus failure (no
query by the Modbus Master for 120s).
Once the bus communication has been re-
stored, the valve will again be controlled auto
-
matically according to the set operating mode.