3-3. Link Controller Initialization
U3-1021
3-6
11/98
Westinghouse Proprietary Class 2C
9. Copy any programs and files necessary for the operation of the LC application
to Drive A from Drive B. These may include the following:
— Any applicable LC executable programs.
— RLCFLASH.EXE program (if desired, and if there is sufficient space on the
LC’s internal Drive A).
— Any applicable configuration files.
— Custom AUTOEXEC.BAT file (typically required to auto-start an LC
application upon reset or power up of the LC). Do not place this file on the
LC card until the application has been tested.
10. Enter the following command to save the current configuration of the LC’s
internal disk:
B:\>RLCFLASH
OR
B:\>A:\RLCFLASH
Caution
It is extremely important to run the RLCFLASH.EXE
program at this time. If this is not done, then the data on
the LC internal disk will be lost.
11. To auto-start the application, reboot the LC by removing it from the Base Unit
and then replacing it, or by pressing
Control-Shift-Delete
.
After initial configuration of the LC card, it is still recommended that the LC
card be operated from a floppy disk. This will avoid any potential problems with
the hard disk drive.
12. The LC operates as an IBM-compatible personal computer. Executable files
which are copied to (or created on) the RAM disk can be executed by entering
the program name.
13. To exit the RLCEXTPC.EXE program at the external personal computer, press
Control-Break
.
For general information on the recommended LC programming approach, as well
as application notes which may be helpful in programming the LC, refer to
Section 4. For additional information on IBM-PC programming, refer to the
applicable IBM and DOS documentation.