Radian Series Inverter/Charger 

 

 

GS8048

  

 

 

 

Operator’s Manual  

 

Содержание Radian GS8048

Страница 1: ...Radian Series Inverter Charger GS8048 Operator s Manual...

Страница 2: ...OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION b ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE WHETHER DIRECT INDIRECT CONSEQUENTIAL OR INCIDENTAL WHICH MIGHT ARISE OUT...

Страница 3: ...Series Inverter Charger Installation Manual Symbols Used WARNING Hazard to Human Life This type of notation indicates that the hazard could be harmful to human life CAUTION Hazard to Equipment This t...

Страница 4: ...Emitting Diode NEC National Electric Code NEU AC Neutral also known as Common Off grid Utility grid power is not available for use PV Photovoltaic RELAY AUX Auxiliary connection that uses switch rela...

Страница 5: ...Operation 9 Input Modes 9 Generator 9 Support 10 Grid Tied 11 UPS Uninterruptible Power Supply 12 Backup 13 Mini Grid 13 Functions 15 Inverting 15 Search 16 Input 16 Generator 18 Transfer 18 Offset 19...

Страница 6: ...or Troubleshooting 39 Table 4 Warning Troubleshooting 40 Table 5 Disconnect Troubleshooting 42 Table 6 Sell Status Messages 43 Table 7 Electrical Specifications for Model GS8048 45 Table 8 Mechanical...

Страница 7: ...z AC to battery charging from any AC source Uses energy from photovoltaic arrays wind turbines and other renewable resources Use of OutBack FLEXmax charge controllers will optimize power production fr...

Страница 8: ...lation The settings are stored in the non volatile memory of the Radian However it is highly recommended to include a MATE3 as part of the system This provides the means to monitor system performance...

Страница 9: ...t the system 1 Close the main DC circuit breakers or connect the fuses from the battery bank to the inverter Repeat for every inverter present 2 Confirm that the MATE3 is operational if present See th...

Страница 10: ...such as generator start selling or search mode 8 Compare the DVM s readings with the MATE3 meter readings If necessary the system display s readings can be calibrated to match the DVM more accurately...

Страница 11: ...it Connect Delay and so on The following pages compare the various features of each input mode Generator This mode allows the use of any generator even one with a rough or imperfect AC waveform In oth...

Страница 12: ...battery charging cycle After the end of the Float timer it will continue to alternate between Silent and Re Float stages BENEFITS The large loads on the system can be powered while staying connected...

Страница 13: ...ergy raises the batteries above a designated reference point or target the inverter exports power in order to bring the voltage back down or to prevent it from rising further The inverter uses several...

Страница 14: ...deliver no more than 85 of the inverter s specified wattage per inverter in a multi inverter system This recommendation is specifically for the inverter s grid interactive feature In some cases the s...

Страница 15: ...the batteries can be sustained It is expected that the batteries will also be charged from renewable sources such as PV When the batteries become depleted the system reconnects to the utility grid to...

Страница 16: ...ATE3 system display However it is not compatible with HBX mode and cannot be used at the same time When using Mini Grid mode HBX mode should be disabled to prevent conflicts When deciding whether to u...

Страница 17: ...hen the inverter is being supplied by an AC source Low Battery Cut Out This feature prevents the inverter from draining the batteries completely It will stop functioning and give a Low Battery V error...

Страница 18: ...Battery Charging on page 20 Two sets of AC input terminals are available Both inputs are identical and can be used for any AC source However for easy reference the first input has been labeled GRID fo...

Страница 19: ...r will close its transfer relay and accept the input source This occurs after a delay which is specified below If the conditions are not met the inverter will not accept the source If it was previousl...

Страница 20: ...cannot limit the load current An overload condition is possible CAUTION Equipment Damage Current draw in excess of the inverter s transfer relay rating can damage the transfer relay This damage is no...

Страница 21: ...n the Grid Tie Sell menu Unlike the other target voltages the Radian inverter cannot import AC power to raise the batteries to the Sell Voltage set point It can only use excess DC power if it is avail...

Страница 22: ...lified AC source The unit is connected to an AC source but is in a mode or stage that does not use the charger Silent mode is one example The unit is connected to an AC source but the charger has been...

Страница 23: ...charging stages or timers are active This function is described more fully on page 19 Offset is a constant voltage mode of operation The inverter cannot import current to charge the batteries to a ta...

Страница 24: ...ting When the battery voltage decreases to this point the charger becomes active again The default set point is 50 0 Vdc NOTE If the Radian inverter is placed in the Generator input mode the charger s...

Страница 25: ...ugh its full duration The timer will count down whatever time remains from the previous cycle or whatever time it has accumulated since then Absorption Timer The Absorption timer does not reset to its...

Страница 26: ...cation in the electrolyte Equalization follows the same pattern as standard three stage charging as shown in the figures on page 21 However instead of the Absorption voltage and time set points it is...

Страница 27: ...ng of all slaves and all charge controllers See the Radian Series Inverter Charger Installation Manual for locating the RTS port This process is automatic When charging an inverter system with an RTS...

Страница 28: ...iesInverter Charger Installation Manual for more stacking instructions Each inverter needs to be assigned a status master or slave The master is the primary and most heavily used unit Slave inverters...

Страница 29: ...e master The slave inverters can be programmed to activate on demand reducing idle power consumption They will remain off until the loads exceed a certain threshold A two inverter system can continuou...

Страница 30: ...it should not be programmed when other ports are selected The range of rank numbers is 0 to 31 The default value is 0 The master is normally left at this value The second item Slave Power Save Level...

Страница 31: ...tallation Manual for more information on hooking up each set of terminals See the MATE3 Owner s Manual for instructions on programming each function The AUX terminals have a series of set points which...

Страница 32: ...the AUX output in response to a high DC battery voltage set point It can run a small fan to ventilate the battery compartment to eliminate gases that result from battery charging When the voltage fal...

Страница 33: ...gy from the renewable source if necessary Diversion will turn off following a delay when a low DC voltage setting is reached The AUX output will automatically turn on to run the loads if the inverter...

Страница 34: ...the batteries become depleted the system reconnects to the AC source to operate the loads The batteries may be recharged during this time using the renewable source When the batteries are recharged t...

Страница 35: ...off No MATE3 present initial install J3 confirmed present The Radian inverter is given an initial OFF command in the factory With DC present use narrow pliers to remove jumper J3 from its pins Once re...

Страница 36: ...er soft key from the Home screen Confirm source voltage and frequency AC source meets requirements but is noisy or irregular MATE3 system display only The Generator input mode can accept irregular AC...

Страница 37: ...e hot line reads 60 75 Vac and the neutral reads 45 60 Vac with respect to ground Unusual and different voltages on AC hot input lines Input neutral is not connected correctly The inverter also may no...

Страница 38: ...he unit can transfer more power than it can invert If loads are oversized the unit will falter or crash when switching to batteries Reduce the size of the loads Loads drop out or crash during transfer...

Страница 39: ...tion is On and the device still does not work then there is an external connection problem If the proper results are not present with the function On the AUX circuit may be damaged Contact OutBack Tec...

Страница 40: ...Troubleshooting 38 900 0020 01 00 Rev A NOTES...

Страница 41: ...er If an AC source is present shut it off Stacking Error Programming problem among stacked units Often occurs if there is no master Can also occur when AC Output Backfeed occurs Check stacking program...

Страница 42: ...s below the lower acceptable frequency limit 54 Hz and prevents connection Check the AC source If it is a generator increase its speed Voltage Too High The AC source is above the upper acceptable volt...

Страница 43: ...ts of the test NOTE The system can continue to operate if the inverter can be run at reasonable levels External cooling may also be applied Transformer in Temps menu Displays the ambient temperature a...

Страница 44: ...as exceeded 140 Vac default value on either L1 or L2 Check AC source The inverter s acceptance range is adjustable NOTE Adjusting the range may accommodate a problematic AC source but it will not fix...

Страница 45: ...for brief fluctuations to occur that are too fast to be seen on a DVM If this happens the appropriate message will still appear on the system display for a short time to help troubleshoot the problem...

Страница 46: ...Troubleshooting 44 900 0020 01 00 Rev A NOTES...

Страница 47: ...nsumption Search Mode 9 9 watts AC Input Voltage Range Adjustable L1 or L2 108 132 Vac AC Input Frequency Range 54 66 Hz AC Input Current Maximum 55 Aac at 240 Vac Grid Interactive Voltage Range Defau...

Страница 48: ...ve been validated through compliance testing and refer to exporting power to a simulated utility source of less than 1 voltage total harmonic distortion THD The output of the Radian series exceeds the...

Страница 49: ...ut Priority Grid Grid or Gen Grid Input AC Limit 50 Aac 5 Aac 55 Aac Gen Input AC Limit 50 Aac 5 Aac 55 Aac AC Input and Current Limit Charger AC Limit 30 Aac 0 Aac 30 Aac Input Mode Grid Tied Generat...

Страница 50: ...trol Off Off Auto or On Aux Mode Gen Alert Load Shed Gen Alert Fault Vent Fan Cool Fan DC Divert IEEE Source Status AC Divert Load Shed ON Batt 56 Vdc 40 Vdc 72 Vdc Load Shed ON Delay 30 Secs 6 Secs 1...

Страница 51: ...tration can be done as follows Go to the following web site 100H101Hhttp www outbackpower com resources warranty or Fill out the information on this form pages 49 and 50 and return a paper copy using...

Страница 52: ...nteractive Capability Product Reputation Back up Capability Reputation of OutBack Power Technologies Value Looks Other Extended Warranty For areas where it is a requirement of local programs OutBack P...

Страница 53: ...nt not foreseeable by OutBack OutBack s liability for any defective Product or any Product part shall be limited to the repair or replacement of the Product at OutBack s discretion OutBack does not wa...

Страница 54: ...OutBack Technical Support representative to perform the necessary troubleshooting This is a required step before a return can be performed Troubleshooting requires a qualified technician to be present...

Страница 55: ...freight prepaid non expedited using a carrier of OutBack s choice where applicable If Product fails in ninety 90 or fewer days from original purchase date OutBack will replace with a new Product If P...

Страница 56: ...Warranty 54 900 0020 01 00 Rev A THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 57: ...h 22 C Charging Absorption Stage 21 Float Stage 23 Float Timer 24 New Bulk 24 None 21 Compliance Testing 46 Cool Fan 30 CSA 2 46 D Default Settings 47 Definitions 2 Design 16 Disconnect 42 Diversion 3...

Страница 58: ...1 General 3 Search 17 Sell Status 43 Settings 47 Silent 23 29 Specifications Electrical 45 Mechanical 45 Environmental 46 Regulatory 46 Stacking 27 Parallel 28 Startup 9 Support 12 Symbols Used 1 Sys...

Страница 59: ...900 0020 01 00 Rev A 57 THIS PAGE INTENTIONALLY LEFT BLANK...