Ouellet OHV Series Скачать руководство пользователя страница 1

180, 3

rd

 Avenue, L’Islet, Quebec, G0R 2C0, CANADA

 Tel.: (418) 247-3947, 1-800-463-7043,  Fax: (418) 247-7801

www.ouellet.com

INSTALLATION INSTRUCTIONS

“OHV” Series 3 kW to 10 kW

WARNING

When using electrical appliances, basic precautions should 

always be followed to reduce the risk of fi re, electrical shock 

and injury to persons, including the following:

Read all instructions before using this heater.

-  This heater is hot when in use. To avoid burns, do not let
  bare skin touch hot surfaces. Keep combustible materials
  at least 5 ft. (1524 mm) from the front of the heater and 
  keep them away from the sides and rear.
-  Do not use outdoors.
-  Do not insert or allow foreign objects to enter any 
  ventilation or exhaust opening as this may cause 
  an electrical shock or fi re, or damage the heater.
-  To prevent a possible fi re, do not block air intakes 
  or exhaust in any manner.  
-  This heater has hot and arcing or sparking parts inside. 
  Do not use it in areas where gasoline, paint or fl ammable 
  liquids are used or stored.
-  Use this heater only as described in this manual. Any 
  other use not recommended by the manufacturer may 
 cause 

fi re, electrical shock, or injury to persons.

-  This heater is not approved for use in corrosive 
  atmospheres, wet or very humid locations such 
  as marine, green house or chemical storage areas.

To reduce the risk of fi re or electrical shock:

-  All wiring must be in accordance with National and 
 Local 

Electrical 

Codes.

-  Heater must be grounded as a precaution against possible
 shock.
-  To avoid possible electrical shock, disconnect all power 
  at the main panel prior to wiring, cleaning or servicing.
-  Verify the power supply voltage coming to the heater 
  matches the heater nameplate rating (on back of heater) 
  before energizing heater.
-  Use minimum 600 Volts, 60 °C wire only.
-  When installed, heater must be electrically grounded
  in accordance with the National Electrical Code.
-  See Figures 1 & 3 and Tables 1 & 3 for minimum 
 mounting 

clearances.

CAUTION

To prevent possible overheating - or damage due 
to overheating - keep at least 5 ft. (1524 mm) clearance 
in front of heater.

See Tables 1 & 3 for side, ceiling and back minimum 
mounting clearances.

Wall / Ceiling structures and anchoring provisions must be 
of suffi cient strength to support the combined weight of the 
heater and mounting bracket. See Table 5.

LOCATE HEATERS PROPERLY

Heaters may be mounted for either horizontal or vertical 
heated air discharge.

Note: 

Install accessories in accordance with their 

installation instructions prior to mounting heater.

  

HEATER INSTALLATION

Horizontal Air Discharge Mounting

The factory supplied wall / ceiling brackets may be used 
or threaded rod (not supplied) may be used. 
See Figure 2 and Table 2 for threaded rod size and spacing.

Table 1 - Minimum Clearances

Heater 

kW

Discharge 

Air

A

Ceiling

B

Side

C

Back

0.5 to

5.0 kW

Horizontal

3-1/2 in.

89 mm

6 in.

152 mm

6 in.

152 mm

5.1 to

10.0 kW

Horizontal

4 in.

102 mm

6 in.

152 mm

6 in.

152 mm

Figure 1 - Minimum Clearances 

Figure 2 - Threaded Rod Spacing Dimensions

Horizontal Air Discharge

Table 2 - Threaded Rod Spacing Dimensions

Horizontal Air Discharge

Heater 

kW

Threaded

Rod

E

F

G

H

0.5 to 

5.0 kW

5/16 - 18

6 1/2 in.
165 mm

4 1/2 in.
115 mm

6 in.

152 mm

7/16 in.

11 mm

5.1 to 

10.0 kW

5/16 - 18

12 in.

305 mm

5 in.

127 mm

6 in.

152 mm

7/16 in.

11 mm

Vertical Air Discharge Mounting

Threaded rod (not supplied) must be used.  
See Figure 4 and Table 4 for threaded rod size and spacing.

If heater is mounted with control compartment toward wall 
insure that heater is mounted with enough clearance to the 
wall (minimum = width of heater) to allow the control 
compartment access door to open.

Table 3 - Minimum Clearances

Heater 

kW

Discharge 

Air

A

Wall

B

Wall

C

Ceiling

D

Wall

0.5 to 

5.0 kW

Vertical

6 in.

152 mm

6 in.

152 mm

6 in.

152 mm

Width of 

heater

5.1 to 

10.0 kW

Vertical

6 in.

152 mm

8 in.

203 mm

10 in.

254 mm

Width of 

heater

Figure 3 - Minimum Clearances

Содержание OHV Series

Страница 1: ... with the National Electrical Code See Figures 1 3 and Tables 1 3 for minimum mounting clearances CAUTION To prevent possible overheating or damage due to overheating keep at least 5 ft 1524 mm clearance in front of heater See Tables 1 3 for side ceiling and back minimum mounting clearances Wall Ceiling structures and anchoring provisions must be of sufficient strength to support the combined weigh...

Страница 2: ... be energized After the elements get warm a short period of time the fan will come on 5 kW and less When the thermostat is satisfied the elements will be deenergized The fan will continue to run until the residual heat is removed from the heater Then the fan will stop Automatic Reset Thermal High Limit OHV heaters have an automatic reset thermal high limit that will deenergize the heating elements ...

Страница 3: ...Use minimum 600 Volt 60 C wire only When installed heater must be electrically grounded in accordance with the National Electrical Code See Figures 1 3 and Tables 1 3 for minimum mounting clearances CAUTION To prevent possible overheating or damage due to overheating keep at least 5 ft 1524 mm clearance in front of heater See Tables 1 3 for side ceiling and back minimum mounting clearances Wall Ce...

Страница 4: ...he fan will continue to run until the residual heat is removed from the heater Then the fan will stop Automatic Reset Thermal High Limit OHV heaters have an automatic reset thermal high limit that will deenergize the heating elements if the interior temperatures of heater exceed its setting The limit will automatically reset when the heater interior temperatures fall below its setting SERVICE The ...

Отзывы: