Climatix HERU® 400-2400
Miscellaneous
POL63x.00/STD
used for Pressure sensor
or
Internal Modbus Slave
Used for BMS (if Pressure
sensor not used)
Internal Modbus
TCP/IP
PROC1 Climatix
POL63x.00/STD
Internal Modbus slave via
RJ45/Ethernet connection
labelled T-IP
Main index > System overview > Communications > Modbus
Parameter
Value
Function
Communication
–
OK
–
Alarm
–
Status for Modbus communication.
Internal
–
None
–
Master
–
Slave
Activation and type of MODBUS function:
–
Internal interface disabled.
–
Master, used for Modbus pressure sensor.
–
Internal interface as slave, designed for
communication to BMS
Internal slave adr
0…247
Address of controller on the bus.
Internal settings
RS485
–
-
Go to parameter page for RS485 settings.
TCP/IP
–
-
Go to parameter page for TCP/IP settings.
Module 1 Modbus
–
-
Go to page for Modbus module settings.
Module 2 Modbus
–
-
–
Go to parameter page for Modbus module
settings.
Module 3 Modbus
–
-
–
Go to parameter page for Modbus module
settings.
Main index > System overview > Communications > Modbus > RS485
Parameter
Value
Function
Baud rate
–
2400
–
4800
–
9600
DEFAULT
–
19200
–
38400
Bus transfer speed. All units
must have the same setting.
Parity
–
Even
–
Uneven
–
None
DEFAULT
Parity. All units must have the
same setting.
Stop bit
–
One
DEFAULT
–
Two
Number of stop bits. All units
must have the same setting.
Delay.time
–
0…2147483647
[ms]
–
O mS
DEFAULT
–
Delay of response time to
master.
Response timeout
–
0…2147483647
[ms]
–
O mS
DEFAULT
Setting of max response time
for master.
Information must be read
within this time; otherwise
an alarm will be triggered.
Termination
–
Passive
DEFAULT
–
Active
Internal bus connection for
controller:
–
No bus connection
resistance.
–
With bus connection
resistance.
Parameter settings for
MODBUS
Parameter settings for
MODBUS RS485
Содержание HERU 400-2400 S
Страница 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Страница 2: ......
Страница 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Страница 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Страница 65: ...65 120 2018 02 13 Climatix HERU 400 2400 External components basic unit 994020653 CLIMATIX HMI DM Display IP31...
Страница 95: ...95 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Alarm button function Procedure for non saving alarms...
Страница 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Страница 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Страница 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Страница 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Страница 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Страница 119: ......
Страница 120: ......