77 / 120
2018-02-13
Climatix HERU® 400-2400
Expansion module with outer components
Connection in EXP1
83
84
85
External s etpoint
Temp.
GND
0-10V DC
TU1
:37
24V
For activation/configuration:
Parameter name
Area
Select
Main index > Configuration > Configuration 1
Expansion module
No, One, Two
One
External setpoint
No / Volt / Ohm / QAA27 / BSG21
Select Volt
Restart
Execute
Alarm input heating/cooling
This function is only used in combination with EXP1.
Via the expansion module, it is possible to use input monitoring of heating and/or
cooling. The input can be used for various purposes.
The function can be used for heating or for cooling.
Examples of different monitoring actions:
•
Heating
-
Alarm circulation pumpwater heating
•
Cooling
-
Alarm circulation pump water cooling
-
Alarm DX cooling
-
Alarm cooling unit
The signal input can be used via an auxiliary contact in the operating switch (safety
switch) and alarm contact in the circulation pump; an alarm is triggered if the
operating switch is switched off or if there is an alarm on the pump.
Connected as follows:
88
Alarm Heating
86
87
89
EXP1
Alarm Cooling / DX
For activation/configuration of cooling:
Parameter name
Area
Select
Main index > Configuration > Configuration 2
Pump Alarm
cooling
No / Alarm / Return / Alarm+Return
Select: Alarm
Alarm DX cooling
No / Alarm / Return / Alarm+Return
Select: Alarm
Pump Alarm
heating
No / Alarm / Return / Alarm+Return
Select Alarm after return
Restart
Execute
Return or Alarm + Return not applicable to HERU® CX.
Signal input Contact function can be changed to NC (normally closed).
This is done under Unit > Inputs.
Connection
Parameter
Alarm/return
Heating/cooling
Important!
Connection
Parameter
Содержание HERU 400-2400 S
Страница 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Страница 2: ......
Страница 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Страница 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Страница 65: ...65 120 2018 02 13 Climatix HERU 400 2400 External components basic unit 994020653 CLIMATIX HMI DM Display IP31...
Страница 95: ...95 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Alarm button function Procedure for non saving alarms...
Страница 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Страница 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Страница 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Страница 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Страница 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Страница 119: ......
Страница 120: ......