18 / 120
Climatix HERU® 400-2400
2018-02-13
Flowchart and function descriptions
GTU
Outside temp sensor
EMS-RV
Rotation monitor EMS
RU1
Room unit
GP1
Supply air pressure
sensor
CP1
Circulation pump heating
Supply-EC
Supply air fan (TF) EC motor
GP2
Extract air pressure
sensor
CP2
Circulation pump cooling
Extract-
EC
Extract air fan (FF) EC motor
GP3
Supply air filter sensor SV1
Valve actuator heating
GP4
Extract air filter sensor SV2
Valve actuator cooling
TEMPERATURE REGULATION
The temperature can be regulated as constant supply air regulation or room
regulation/extract air regulation. With constant supply air regulation, the air supply
temperature remains constant. With room regulation, a sensor is placed in the room
to obtain a constant room temperature (suitable when a cooling coil is installed).
Extract air regulation works in a similar way, but with the difference that the
temperature is measured on the
unit’s
extract air side.
The temperature can be regulated in five stages:
1. Cooling re cooling:
The control unit can regulate a cooling coil (e.g.
cooling water from geothermal heating), when the cooling recovery from the rotor is
insufficient.
2. Cooling recovery and/or regulated cool down.
The rotary heat exchanger starts
if the extract air temperature is lower than the outside temperature.
•
Regulated cool down: If the temperature outside is lower than the desired room
temperature and is not sufficient for lowering the room temperature, cool
down will start.
3. Outside temperature = desired temperature:
When the outside temperature is
the same as the desired supply air temperature, the rotor will stop.
4. Heat recovery:
The rotary heat exchanger starts to recover the warmer indoor
temperature.
5. Heat re heating:
In climate zones in which the rotary heat exchanger, in
spite of its high efficiency, is not sufficient to achieve the desired supply air
temperature, the control unit can also regulate either an electric heater or a heating
coil connected to the duct.
“Night
cooling”
is a function which utilizes the cool outdoor temperature and cools
down the building at night without using any other additional energy. The fan speed is
boosted when the ratio between the outside temperature and the extract air
temperature is within the programmed criteria.
Содержание HERU 400-2400 S
Страница 1: ...U S E R M A N U A L E N H E R U 4 0 0 2 4 0 0 T S HERU T HERU S...
Страница 2: ......
Страница 14: ...14 120 Climatix HERU 400 2400 2018 02 13 Scope of assembly installation instructions...
Страница 45: ...45 120 2018 02 13 Climatix HERU 400 2400 External components basic unit...
Страница 65: ...65 120 2018 02 13 Climatix HERU 400 2400 External components basic unit 994020653 CLIMATIX HMI DM Display IP31...
Страница 95: ...95 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Alarm button function Procedure for non saving alarms...
Страница 97: ...97 120 2018 02 13 Climatix HERU 400 2400 Miscellaneous Menu structure Menu overview...
Страница 98: ...98 120 Climatix HERU 400 2400 2018 02 13 Miscellaneous Start page Main index Unit...
Страница 104: ...104 120 Climatix HERU 400 2400 2018 02 13 SERVICE HERU...
Страница 111: ...111 120 2018 02 13 Climatix HERU 400 2400 SERVICE HERU...
Страница 118: ...118 120 2017 11 03 Climatix HERU 400 2400 Troubleshooting...
Страница 119: ......
Страница 120: ......