SECTION 6 - JLG CONTROL SYSTEM
6-26
3121784
CHG Set
For a lithium machine, by this page it's possible to set the
maximum charging current, after having inserted the rele-
vant password “1138”, pressing button n.1 it will be settled
25 Amp, pressing button n.2 it will be settled 18 Amp.
This setting, considering the transformation rate, has to
respect the maximum current available on local electric
plug.
INV Set
For a lithium machine, by this page it's possible to setup
the rpm setting for a new inverter, pressing button n.1 the
rpm setting will be settled according to the machine
model settled by the relevant menu, check chapter
10.1.9.2.
NOTE:
Some pages are not accessible, or could not show
same information, if not after having inserted the
relevant password.
6.5
MASTER BOARD (ECM1) REPLACEMENT AND
SETTING
Machine software contains the software for all the TTC JLG
machine models produced till that moment, so that when
a new master board (ECM1) in installed on a machine, the
machine model need to be selected.
New Master Board
When a new master board (never used) is fitted on the
machine, the remote control need to be connected to its
ground cable and the control position selected accord-
ingly by the control position selector switch.
Then, turning on the main key, it will require the setting of
the machine model and version, as indicated by the here
below procedure.
To set the master board, machine must be closed and
aligned, it has to be make sure that battery is charged
enough or machine need to be plugged to the electric
network.
Here follows the calibration procedure:
1.
Connect the remote control at its ground cable
and select the control position accordingly by
the control position selector switch.
2.
Turn ON the main key and select the correct
machine model with button n.1 (VERSION), the
display shows the machine model selected.
If it appears “MOD.CODE FAIL!”, it means that the
machine model selected is not correct, even if
that alarm does not appear on the display the
machine model selected needs to be check.
CHG SETUP
1 STANDARD
2 1,2 KW
25
9 ESC
INV SETUP
1 SETUP
9 ESC
CONNECTOR ON
REMOTE
CONTROL THE
GROUND CABLE