8.7 Facing
Non-combustible finishing materials such as brick or ceramic can be glued to the facade of the
fireplace. Do not put a seal between the faceplate and the finishing material to facilitate the
removal of the faceplate if necessary.
1 1/2"
38mm
1 1/2"
38mm
8.8 Combustible Shelf Installation
A combustible shelf with a depth of 6" (152 mm)
(C)
can be installed at least 58" (1,47 m)
(B)
from the base of the fireplace.
Different shelf sizes are listed in the following table.
POSITIONING AND DEPTH
OF THE SHELF
B
C
58" (1,47 m)
6" (152 mm)
60" (1,52 m)
8" (203 mm)
62" (1,58 m)
10" (254 mm)
64" (1,63 m)
12" (305 mm)
For a shelf dimension that does not appear in the
table, add 52" (1,32 m) to the depth of the shelf
to find the safe position of the shelf. The height
(A)
should always be 80" (2.03 m) from the base
of the fireplace.
B
B
45°
C
C
A
A
48"
1219mm
Combustibles
materials
allowed in this zone
Non combustible
material
only in this zone