COMBUSTION AIR SUPPLY 

For a mobile home installation the stove must be connected to an 
outside source of combustion air. A 3” inside diameter metallic pipe, 
either flexible or rigid, may be attached to the inlet at the stove’s rear 
(refer to figures 4, 5 & 6). A rodent guard (minimum ¼” wire mesh) 
must be used at the terminus (refer to figure 5). All connections 
must be secured and airtight by either using the appropriately sized 
hose clamp and/or UL-181-AP foil tape.  

For mobile home installations only

: No combustion air supply 

may exceed 10 feet. 

Sources of Outside Combustion Air 

 

A hole in floor near stove rear terminating only in a 
ventilated crawl space. 

 

A hole in the wall behind the stove. 

WHEN OUTSIDE AIR IS NOT USED 

If outside air is not used, it is important that combustion air be easily 
available to the air inlet. A closeable outside air register can be used 
in tightly insulated homes. 

VENTING 

The Osburn Hybrid-45 MF is certified for use with a vent certified to 
UL-103 or ULC S629M and a chimney type vent certified to UL-641 
or ULC-S-609-M89 and ULC/ORD C441-M90, with 3” or 4” inner 
diameter. In Canada, we recommend that you use

 

a listed pellet 

vent that meets the ULC S-609-M89 and ULC/ORD C441-M90 
Standards.  For the United States, we recommend that you use a 
listed pellet vent that meets the UL-641, 7

th

 edition Standard.

  

This 

unit can be vented in an existing chimney with the addition of a liner 
if the chimney is more than 4” in diameter.  Class “A” chimney is not 
required. Refer to the instructions provided by the vent or chimney 
manufacturer, especially when passing through a wall, ceiling, or 
roof. 

Your venting system should have at least one foot of vertical 
rise for each foot of horizontal run.  The total vertical rise 
should never be less than 3 feet (see Appendix A).

 

This is a pressurized exhaust system. All vent connector joints must 
be sealed and fastened in accordance with the pellet pipe 
manufacturer's instructions to ensure consistent performance and 
avoid smoke and ash spillage. 

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING 
ANOTHER APPLIANCE. 

DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING 
SYSTEM OF THIS UNIT. 

INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT 
MANUFACTURER. 

WARNING     DO NOT INSTALL IN SLEEPING ROOM 

CAUTION     THE STRUCTURAL INTEGRITY OF THE 
MANUFACTURED HOME FLOOR, WALL, AND CEILING/ROOF 
MUST BE MAINTAINED 

 

 
 

AIR INLET

EXHAUST

 

 
 
 
 
 

TRIM

COLLAR

RODENT

GUARD

 

 
 
 

VENTILATED 

CRAWL SPACE

 

 
 
 
 

INSTALLATION

FIGURE 4 

Rear view 

FIGURE 5 

Fresh air supply 

FIGURE 6 

Fresh air supply 

Содержание HYBRID-45 MF

Страница 1: ...instructions Some surfaces become hot at higher feeding rates To prevent potential burns avoid contact with those areas This heating unit must serve as a supplementary heat source An alternative heat...

Страница 2: ...a freestanding room heater It is also approved as a mobile home heater which is designed for connection to an outside combustion air source The stove will not operate using natural draft or without a...

Страница 3: ...ise to operational levels one of the sensors could then make the stove start on its own It is recommended that the stove be unplugged when not in use for extended amounts of time i e during the summer...

Страница 4: ...lation 16 Please Read This Operating Safety Precautions 18 MAINTENANCE 19 Ash Removal 19 Ash Disposal 19 Vacuum Use 20 Cleaning 20 Blowers 20 Chimney Cleaning 21 Recommended Maintenance Schedule 21 Re...

Страница 5: ...n the USA the unit must be installed on a non combustible floor pad extending at least 6 inches 155 mm in front of the door opening and at least 6 inches 155 mm on each side of the door opening In Can...

Страница 6: ...nt that meets the ULC S 609 M89 and ULC ORD C441 M90 Standards For the United States we recommend that you use a listed pellet vent that meets the UL 641 7 th edition Standard This unit can be vented...

Страница 7: ...h enough piping to penetrate and extend at least 6 inches beyond the exterior wall There should always be at least one foot of vertical rise for each foot of horizontal run see Appendix A At least 3 f...

Страница 8: ...above paved side walk or a paved driveway located on public property 39 100 cm Clearance to property boundary A vent shall not terminate underneath a veranda porch or deck United States Not Less than...

Страница 9: ...in roof always 3 larger all the way around pipe Install upper edge and sides of flashing under roofing materials nail to the roof along upper edge Do not nail lower edge Seal nail heads with flexible...

Страница 10: ...the center of the hole where the pipe is to pierce the masonry chimney 2 It will be necessary to break out the masonry around the location of the pipe center mark Use a 4 inch diameter hole for 3 inch...

Страница 11: ...that came with your owner s manual Fix the two brackets using the same screws you have removed Lay the log set inside the firebox as shown on figure 14d 14e SCREWS SCREWS LOG SUPPORT LOG SUPPORT LOG...

Страница 12: ...lar basis as per our recommended maintenance schedule This is particularly critical if you have animals in your house such as a dog or a cat Filters that are not cleaned can clog up and cause your sto...

Страница 13: ...ash content should be indicated on the bag by the pellet manufacturer PRE START UP CHECK Remove burn pot making sure it is clean and none of the air holes are plugged Clean the firebox and then reins...

Страница 14: ...e fuel feed rate When the NOISE REDUCER button is pushed the convection blower will switch to its lowest speed The convection blower will remain at its lowest speed unless the stove reaches a certain...

Страница 15: ...EDURE Turning your Osburn stove off is a matter of pressing the MODE control panel switch until the OFF led goes on The blowers will continue to operate until internal firebox temperatures have fallen...

Страница 16: ...fort and efficiency from you Hybrid 45 MF The thermostat should be mounted 50 inch from the floor on a wall located 15 to 20 feet from the stove You should avoid an installation directly in front of t...

Страница 17: ...ard to let you know that you are in the PILOT ON mode If you wish to go back to the default thermostatic mode i e the unit shuts down after 45 minutes if the thermostat does not call for heat simply p...

Страница 18: ...ambient air in a confined room becomes to hot the stove may overheat and the thermal protection on the combustion exhaust motor may be activated causing the motor to stop d KEEP ALL LOOSE OR MOVEABLE...

Страница 19: ...ure 18 19 d Open the door and remove the burn pot by grasping it and pulling straight out Scrape the burn pot with a scraper if necessary Make sure that the burn pot holes are not plugged Empty ashes...

Страница 20: ...AT THIS OPERATION AT LEAST ONCE PER TON OF PELLETS BURNED UNTIL YOU ARE FAMILIAR WITH HOW ASHES ACCUMULATE WITH YOUR OPERATING PRACTICES BLOWERS DANGER RISK OF ELECTRIC SHOCK DISCONNECT POWER BEFORE S...

Страница 21: ...fied chimney sweep can perform this service It is also recommended that before each heating season the entire system be professionally inspected cleaned and if necessary repaired To clean the chimney...

Страница 22: ...alled Check to make sure vent pipe installation meets the criteria in the owner s manual as well as the pipe manufacturer s recommendations 4 The airflow pressure switch wire connections are faulty Ch...

Страница 23: ...ft from the auger housing Start by emptying the hopper Take the rear panel off the stove body Then take the auger motor off by removing the screws that hold the motor to the auger shaft Once the motor...

Страница 24: ...d the unit will stop after the ignition cycle If this situation occurs call your dealer or technician 5 The control board is not sending power to the igniter Check the voltage going to the igniter dur...

Страница 25: ...ain SMOKE SMELL COMING BACK INTO THE HOME Possible Causes Possible Remedies 1 There is a leak in the vent pipe system Inspect all vent pipe connections This is a pressurized exhaust system All vent co...

Страница 26: ...ately 3000 RPM You will need a technician to perform this test 7 Bad pellets Applies to GLASS SOOTS UP AT A VERY FAST RATE Only The brand of pellets or the batch of pellets that are being used may be...

Страница 27: ...id stay open more than 3 minutes Inverted polarity in power outlet Power outage Igniter fuse is burnt out SMOKE SMELL OR SOOT BUILD UP Because it is a wood burning device your Osburn Hybrid 45 MF may...

Страница 28: ...TION BLOWER SWITCH L 250 HIGH TEMPERATURE MANUAL RESET HIGH TEMPERATURE SWITCH F 160 SWITCH L 250 AUTOMATIC HIGH TEMPERATURE CONTROL AIR SUPPLY INTAKE FRESH AIR COMBUSTION EXHAUST BLOWER MOTOR CLEANIN...

Страница 29: ...ide SE52710 Exhaust Adapter 3 SE52572 Hot Rod Igniter 44030 Thermistor 44095 F 160 Convection blower heat sensor 44058 L 250 Automatic High Temp Switch 44059 L 250 Manual Reset High Temp Switch 44041...

Страница 30: ...al vent coming out at the back of the stove on a total distance of 4 feet followed by a Tee and a 6 foot vertical rise it would be acceptable The installation would end be within the allowable configu...

Страница 31: ...valent vent lenght calculation table DRAW YOUR INSTALLATION 1 SQUARE 1 F00T PART DAILY 10 bags 25 bags E xchanger Baffle Left interior channel Hopper Evacuation blower Blower blades Pressure system Bu...

Страница 32: ...osts covered by this warranty are limited according to the table below The manufacturer at its discretion may decide to repair or replace any part or unit after inspection and investigation of the def...

Отзывы: