background image

For Model ODS-8003HS-14 ODS-9003HS-14 ODS-1109HS ODS-12012HS ODS-15011HS

WARNING

READ AND SAVE THESE INSTRUCTIONS

Installer: Leave this manual with the homeowner.

CAUTION

CLEANING & MAINTENANCE

OPERATION

TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:

1. Use this unit only in the manner intended by the manufacturer. If you have questions, contact the manufacturer at the 

    address or telephone number listed in the warranty.

2. Before servicing or cleaning unit, switch power off at service panel and lock the service disconnecting means to prevent 

    power from being switched on accidentally. When the service disconnecting means cannot be locked, securely fasten

    a prominent warning device, such as a tag, to the service panel.

3. Installation work and electrical wiring must be done by a qualified person(s) in accordance with all applicable codes and 

    standards, including fire-rated construction codes and standards.

4. Sufficient air is needed for proper combustion and exhausting of gases through the flue (chimney) of fuel burning equip-

    ment to prevent backdrafting. Follow the heating equipment manufacturer’s guideline and safety standards such as those

    published by the National Fire Protection Association (NFPA), and the American Society for Heating, Refrigeration and 

    Air Conditioning  Engineers (ASHRAE), and the local code authorities.

5. When cutting or drilling into wall or ceiling, do not damage electrical wiring and other hidden utilities.

6. Ducted fans must always be vented to the outdoors.

7. Acceptable for use over a tub or shower when connected to a GFCI (Ground Fault Circuit Interrupter) - protected branch

    circuit (ceiling installation only).

8. This unit must be grounded.

1. For general ventilating use only. Do not use to exhaust hazardous or explosive materials and vapors.

2. This product is designed for installation in ceilings up to a 12/12 pitch (45 degree angle). Duct connector must point up.

    DO NOT MOUNT THIS PRODUCT IN A WALL.

3. To avoid motor bearing damage and noisy and/or unbalanced impellers, keep drywall spray, construction dust, etc. off

    power unit.

4. Please read specification label on product for further information and requirements.

For quiet and efficient operation, long life, and attractive appearance - lower or remove grille and vacuum interior of unit

with the dusting brush attachment.

The motor is permanently lubricated and never needs oiling. If the motor bearings are making excessive or unusual noi-

ses, replace the motor with the exact service motor. The impeller should also be replaced.

Use an on/off switch to operate this fan. See “Connect Wiring” for details.

The humidity control and fan can be operated separately. Use a 1 or 2 function wall control. Do not use a dimmer switch 

to operate the humidity control or light. See “Connect Wiring” for details.

SENSOR OPERATION

The humidity-sensing fan uses a sophisticated humidity sensor that responds to: (a) rapid to moderate (user-adjustable)

increases in humidity or (b) humidity above a user-adjustable set-point (50%-100% relative humidity). The humidity sen-

sor may occasionally turn the fan ON when environmental conditions change. If the fan continuously responds to chang-

ing environmental conditions, “H” (means “humidity”) adjustment may be required. This figure is factory-set for about 75%

(Ambient temperature of 25

)

.

SENSITIVITY

 

ADJUSTMENT

The “H” has been factory set for most shower applications. However, if the fan is in a tub area or is being used for damp-

ness control, the “H” may need to be increased toward maximum “+”. If the control is responding too often to changing 

environmental conditions, movement toward less “-” “H” may be required.

To adjust the “H”:

1. Disconnect power at service entrance.

2. Through the grille, locate the slot marked “H”.

3. Carefully rotate the “H” adjustment toward “+” or “-”.

1

MODEL: ODS-8003-14         ODS-9003-14         ODS-1109         ODS-12012         ODS-15011

               ODS-8003HS-14    ODS-9003HS-14    ODS-1109HS    ODS-12012HS    ODS-15011HS

VENTILATION FAN

Содержание ODS-8003-14

Страница 1: ...ilings up to a 12 12 pitch 45 degree angle Duct connector must point up DO NOT MOUNT THIS PRODUCT IN A WALL 3 To avoid motor bearing damage and noisy and or unbalanced impellers keep drywall spray con...

Страница 2: ...topped sensing a rise in humidity and the humidity level is below the user adjustable set point To adjust the T 1 Disconnect power at service entrance 2 Through the grille locate the slot marked T 3 C...

Страница 3: ...twork not included to the damper duct connector and run the ductwork to a roof or wall cap not included Using tape not included secure all the ductwork connections so that they are air tight Run 120 V...

Страница 4: ...1 4 1 Isolator Motor Plate Washer Nut Hex Lock Grille Assembly includes part 2 Grille Spring Hanger Bar Kit short Hanger Bar Kit long Screw Humidity Sensor System for sensor model Blower Assembly inc...

Страница 5: ...lez suivre les les tels qu expliqu s par les fabricants d quipement de chauffage tels que publi s Lorsque vous d coupezv lectriques ou autres g n rale seulement N utilisez pas cet jusqu 12 45 degr s a...

Страница 6: ...nsulter l illustration droite Vissez le support de montage au bo tier en utilisant la vis A Distance A Solive 1 Avant l installation veuillez prendre en note les d tails suivants Fig 1 Fig 2 Trou A Tr...

Страница 7: ...in de le placer entre les solives En tenant le bo tier en place assurez vous que celui ci touche le bas de la solive Vissez le bo tier la solive en passant par les trous D et C Vissez le support de mo...

Страница 8: ...bo tier du ventilateur pincez les ressorts se trouvant sur les c t s de la grille puis installez la grille dans le bo tier en ins rant les ressorts dans leurs fentes respectives Poussez la grille vers...

Отзывы: