WARNING
Single Pole Timers
MODEL
HET06-R
PLEASE READ INSTRUCTION BEFORE COMMENCING INSTALLATION AND RETAIN FOR FUTURE REFERENCES.
Electrical products can cause death or injury, or damage to property.
If in any doubt about the installation or
use of this product, consult a competent electrician.
INSTALLATION GUIDE
WARNING — THE INSTALLATION MUST BE CARRIED OUT BY
A QUALIFIED
ELECTRICIAN.
CAUTION
1. These Single Pole Timers
are suitable for
indoor use only
2.
Please keep the
Single Pole Timers
a
way
from any corrosive substance, and please
use
dry
cloth
when you clean it
3. Single Pole Timers
can only be installed by a qualified electrician
4.
Before installation or maintenance, please
turn off the circuit breaker
Instruction Manual
1-888-543-6473
1-888-541-6474
13376 Comber Way
Surrey BC V3W 5V9
[email protected]
www.ortechindustries.com
375 Admiral Blvd
Missis
s
auga
,
ON L5T 2N1
Application Notice
1. For your safety, connecting a proper ground to the timer switch provides protection against electrical shock in the event of
certain fault conditions
2. If a proper ground is not available, consult with a qualified electrician before continuing installation
3. Only connect the HET06-R to a Single Pole Circuit. The HET06-R is not suitable for 3-way switching.
4. If the existing wiring does not match the description for a Single Pole Circuit, you should consult with a qualified electrician
Wire the timer switch
•
Twist the existing wires together with the wire leads on the timer switch as indicated in the drawing above.
Cap them securely using the wire nuts provided
•
Connect the green or non-insulated (copper) GROUND wire from the circuit to the GROUND wire on the HET06-R
•
Connect the power wire from the circuit (HOT) to the black wire on the HET06-R
•
Connect the power wire to the lamp or fan (LOAD) to the red wire on the HET06-R
•
Connect the NEUTRAL wires from the circuit (NEUTRAL) to the white wire on the HET06-R
•
Please check the presence of neutral wire, and do not connect neutral with load wire together