1.
Navigate to
MANAGEMENT > OTHER: Disciplining
.
2.
Click the GEAR icon at the top of the
Status
panel. The
Oscillators Settings
win-
dow will display:
3.
Populate the fields:
Maximum TFOM for Sync
: When TFOM (Time Figure of Merit, see also
"Time Figure of Merit (TFOM)" on the facing page
) is greater than Max
TFOM, disciplining will still be attempted against the selected reference to
improve the TFOM. If the condition persists, the system will transition to hold-
over, and eventually out of sync. When disciplining is performed such that
TFOM is no longer greater than max TFOM, the system will transition back
into sync.
Holdover Timeout(s)
: The default is 7200 s (= 2 hours).
For more information on holdover timeouts, see
. For additional information on holdover, see
"Holdover Timeout"?" on page 149
Phase Error Limit
: [Default=0 (disables this feature)]. Setting a Limit (valid
for +/-) for the Phase Error between an external 1PPS reference and the Sys-
tem 1PPS will cause the disciplining tracking to restart automatically (after a
few minutes delay) if that limit is exceeded. This will help to quickly re-align
the System 1PPS with a reference.
When using a Host Reference as a primary or backup reference, for improved
performance it is recommended to set the phase error limit for NTP to a sug-
gested value of 100000 ns (= 1 µ second). Adjust this value as needed, based
on your accuracy requirements.
154
CHAPTER
3
•
VelaSync 1232 User Manual Rev. 4
3.4 Managing the Oscillator
Содержание Spectracom VelaSync 1232
Страница 2: ......
Страница 4: ...Blank page II VelaSync 1232 User Manual...
Страница 12: ...BLANK PAGE X VelaSync 1232 User Manual TABLE OF CONTENTS...
Страница 28: ...16 CHAPTER 1 VelaSync 1232 User Manual Rev 4 1 7 The VelaSync Web UI...
Страница 34: ...BLANK PAGE 1 9 Regulatory Compliance 22 CHAPTER 1 VelaSync 1232 User Manual Rev 4...
Страница 264: ...BLANK PAGE 252 VelaSync 1232 User Manual...