General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Recommended sequence of operations
5.6.4. Side incoming earthing function
cgm
.3-huv-lv
The -huv cubicle model incorporates earthing of the rise
side incoming cable.
Figure 5.52.
Side incoming earthing detail
Opening operation from side incoming earthing position
Initial conditions: circuit-breaker open and earthing switch
S1 closed.
1.
Select using the lever or check the position of the
selector handle in position S1.
Figure 5.53.
Selector handle detail