IG-308-EN version 01; 03/06/2022
31
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
Recommended sequence of operations
5. Recommended sequence of operations
Before carrying out any operation when voltage is
present, we recommend checking the SF
6
gas pressure
using the pressure gauge.
5.1. Checking the gas pressure
Each tank has a pressure gauge for checking the gas
pressure, which can easily be seen from outside the cubicle.
The pressure gauge scale is divided into different colours:
red, grey and green. For safe operation, the needle must be
in the green area of the relevant temperature band.
DO NOT REMOVE THE PLUG from the pressure gauge.
Figure 5.1.
Do not remove the pressure gauge cap
Figure 5.2.
Pressure gauge