IG-308-EN version 01; 03/06/2022
26
Installation
General instructions
cgm
.3-huv system: Fully gas-insulated
medium-voltage switchgear
4.8.1. Bottom front connection
1.
Close the earthing switch.
2.
Remove the cover to access the cable compartment.
Figure 4.13.
Cable compartment detail
3.
Connect the cable connectors on the front bushings
and secure the cables using the cable bracket and
clamp.
The clamp has two positions, depending on the cable
diameter.
Specific cable brackets should be used for cable
diameters above 49
mm. Please check with
Ormazabal
.
Figure 4.14.
Cable connector connection detail