background image

Controller Installation & Wiring

General

Correct wiring of the VAV/Zone Controller is the most important factor 

in the overall success of the controller installation process. The VAV/

Zone Controller wiring has been simplified by the use of modular con

-

nectors and prefabricated modular cables.

Controller Mounting

If you purchased the Round Zone Damper or Rectangular Zone Damper 

Kits from WattMaster, the controller and actuator are factory mounted 

and wired in the damper control enclosure. If your VAV/Zone Control-

lers are pressure independent, an airflow probe and pressure sensor will 

also be factory mounted and wired. 

Most terminal unit manufacturers will offer the option of factory mount-

ing the Orion controls in their terminal units for an additional charge. 

An installation worksheet and instructions are available for the Orion 

VAV/Zone Controller package which can be shipped with the VAV/Zone 

control(s) to the terminal unit manufacturer to simplify factory mounting 

and wiring of the controller. 

 

When the Non-Modular VAV/Zone Controller Actuator Package is to be 

field mounted, it is important to mount it in a location that is free from 

extreme high or low temperatures, moisture, dust, and dirt. 

1.  Leave the enclosure cover on the Non-Modular VAV/Zone 

Controller Actuator Package circuit board during installation 

to protect the circuit board from damage. The damper actuator 

is factory mounted for what we refer to as right-hand terminal 

unit mounting. This assumes you are standing downstream of 

the terminal unit with air hitting you in the face. The side of the 

unit towards your right arm would be the right side of the unit 

and where the standard configuration Zone Controller Actuator 

Package would be mounted over the damper shaft. If you have a 

left-hand terminal unit, the actuator will need to be rotated 180 

degrees within the plastic enclosure and the enclosure assembly 

flipped over to mount over the damper shaft on the left side of 

the terminal unit. The enclosure base is designed with the appro-

priate holes and cutouts to allow for these two mounting options. 

A left-hand label is also included with the actuator and can be 

applied over the right-hand label for left-hand control locations 

when desired. 

2.  If you need to rotate the damper actuator from its factory  

supplied position, first unplug the actuator cable from the actua

-

tor, then remove the (3) screws on the back side of the enclosure 

base that secure the actuator to the enclosure’s base. Rotate 

the actuator 180 degrees and re-install the (3) screws you just 

removed into the mating holes on the enclosure base and tighten 

them to secure the actuator to the base.   

3.  Turn the enclosure base/actuator assembly back over to its 

original mounting position so the actuator is facing up. All instal-

lation instructions are based on the damper moving clockwise to 

open (see the note below if your damper requires counterclock

-

wise-to-open rotation). Check the damper for proper rotation and 

mark the end of the damper shaft to indicate open and closed 

positions. Loosen the (2) shaft mounting bracket nuts on the 

ends of the universal mounting clamp enough to slide the entire 

actuator and plastic enclosure assembly over the terminal unit 

damper shaft. Rotate the enclosure base/actuator assembly until 

it is approximately level and perpendicular with the terminal 

unit mounting surface or enclosure side walls. Use the included 

self-tapping mounting screw to secure the enclosure base to the 

terminal unit sheet metal or terminal unit control enclosure sur-

face. This is done by inserting the screw through the anti-rotation 

bushing, centering it and the bushing in the mounting slot, and 

using a battery powered drill to tighten it until the screw head 

is flush with the top surface of the anti-rotation bushing. Do not 

over tighten the screw! 

4.  Turn the damper blade to its fully closed position. With the man-

ual override clutch button depressed, rotate the actuator clamp 

to within approximately 

1

/

16

 in. to ⅛ in. of the distance between 

the actuator stop and the clamp. This varies depending on the 

damper seal design and thickness. Finger-tighten the universal 

clamp mounting nuts. Then tighten the two nuts again with an 

8 millimeter wrench to approximately 3-5 ft./lb. of torque. On 

dampers with edge seals, the actuator will compress the damper 

blade seal when reaching the end position. Adjust the end stops, 

if required. Re-attach the actuator cable removed in step #1 to 

the actuator. 

Note:

  

If the damper on the terminal unit cannot be installed for 

clockwise-to-open operation, the Non-Modular VAV/

Zone Controller Actuator Package can be configured for 

counterclockwise-to-open operation via the operator in-

terface or through the Prism software program. It must be 

changed prior to system start-up for the designated units 

for the zone damper to function properly. 

See page 19

 

of this manual for detailed, reverse acting configuration 

information. Installation for reverse acting configurations 

is the same as for clockwise-to-open units except all refer-

ences to clockwise will now be in the counter-clockwise 

direction.

Important Wiring Considerations

Please carefully read and apply the following information when wiring 

the Non-Modular VAV/Zone Controller Actuator Package. 

See

 

Figure 

7

 for Non-Modular VAV/Zone Controller Actuator Package wiring and 

connections. 

See Figure 14

 for connecting and wiring multiple Non-

Modular VAV/Zone Controller Actuator Packages in a system.

1.  Size and wire the transformer to be used for powering the Non-

Modular VAV/Zone Controller Actuator Package(s) per the  

instructions. Failure to size the transformer and/or wire the Non-

Modular VAV/Zone Controller Actuator Package(s) correctly 

may cause the VAV/Zone Controller Actuator Package to operate 

erratically or not at all. See 

Figure 15

 for wiring and transformer 

sizing information. 

2.  If a Supply Air Temperature Sensor is to be connected, the  

 

minimum wire size used should be 24 gauge.  

3.  Do not pry on the connectors when connecting or 

disconnecting the modular cables. Be sure to push in on the  

 

connector release clip and then pull straight up. 

4.  Communications wiring should be 18 gauge 2 conductor twisted 

pair with shield Belden #82760 or its equivalent. This type of 

wire is available form WattMaster.

9

Non-Modular ZCAP Technical Guide

                  Installation & Wiring

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: