Other Checks

Space Temperature Sensor

If the Space Temperature Sensor is not reading a valid temperature, 

first make sure that the modular cable connector is firmly plugged into 

the mating female modular connectors on the board and at the Space 

Temperature Sensor.  Also make sure if a cable coupler is used, that it is 

firmly connected.  If the problem persists, try swapping the sensor with 

a known good Space Temperature Sensor. If that sensor works when 

connected to the VAV/Zone Controller board, you can assume you have 

a defective or damaged sensor.  

Supply Air Temperature Sensor

If you suspect the Supply Air Temperature Sensor is not reading cor-

rectly, make sure the wiring terminal connections are tight and that any 

wiring splices are properly connected. You can check the operation 

of the Supply Air Temperature Sensor by measuring the resistance or 

voltage using a digital multimeter.  Set the meter to DC Volts. Place the 

positive probe on the AIN terminal and the negative probe on the GND 

terminal. Read the DC Volts and find that voltage in 

Table 4

. Read the 

temperature corresponding with that voltage and determine if this is close 

to the actual temperature the sensor is exposed to. If the temperature from 

the chart is different by more than a few degrees, you probably have a 

defective or damaged sensor. You can also check the sensor resistance 

to determine correct operation. To read the resistance, set the meter to 

Ohms. Unplug the sensor connector from the board and measure the 

resistance across the disconnected wires.  This resistance should match 

the corresponding temperature from 

Table 4

.

Airflow Sensor

If the Airflow Sensor seems to be reading incorrectly, first check the 

Airflow Sensor’s modular cable connector and be sure it is firmly con

-

nected to its mating connector on the VAV/Zone Controller board.  

Check the Airflow Sensor tubing connections at the airflow pickup 

tubes.  The high pressure port of the sensor needs to be connected to 

the upstream pickup tube.  The low pressure port of the sensor needs to 

be connected to the downstream pickup tube. 

The “Air Valve Sizing Constant” setting under the configuration settings 

for the VAV/Zone Controller must be set to a number other than 0. This 

number is normally referred to as the “K” factor and is supplied by the 

terminal unit manufacturer. It represents the airflow through the box inlet 

at 1” W.G. constant static pressure. This factor must be entered in the 

configuration screen or the airflow through the box will be incorrect.

If none of the aforementioned procedures solves the problem, remove 

power from the VAV/Zone Controller.  Shut down the HVAC unit sup-

plying the duct that the VAV/Zone damper is located on. Be sure that no 

airflow is present in the duct. Reapply power to the board and wait for 

the VAV/Zone Controller to run through its calibration sequence. Restart 

the HVAC unit and check the VAV/Zone Controller CFM readings. If the 

CFM reading still seems to be in error, you probably have a defective 

Airflow Sensor and will need to replace it.

Actuator

Check the Modular cable between the controller and the actuator. Be sure 

both ends of the cable are firmly connected to the mating connectors on 

the actuator and the VAV/Zone Controller board.  Be sure the damper 

moves freely and is not bound. Do this by pressing the actuator clutch 

button and rotating the damper shaft in both directions to verify smooth 

operation. If binding is present, fix the problem as required. Remove 

power from the VAV/Zone Controller. Reapply power and observe 

the damper rotation. If the actuator does not drive the damper in both 

directions, the actuator is probably defective or damaged. Another test 

that can be performed is to swap cables with another known operating 

actuator to determine if the cable could be bad. If the problem goes 

away, you have a defective cable that must be replaced. You can also try 

swapping a functioning actuator with the suspected defective actuator. If 

this solves the problem, the defective actuator will need to be replaced. 

Expansion Module

If the Expansion Module does not seem to operate correctly, first make 

sure the modular cable between the Expansion Module and the Non-

Modular VAV/Zone Controller Actuator Package is firmly connected 

at both ends. Be sure that the Expansion Module has been configured 

correctly. The expansion board must be configured using the Modular 

Service Tool, Modular System Manager, System Manager TS, or Prism 

computer software for your application before it will operate. You must 

configure the number of heat stages, and if it is a fan terminal you must 

configure whether it is a Series Flow or Parallel Flow Fan Terminal unit. 

On a single duct non-fan terminal unit when a call for heat is initiated, 

the LED labeled RLY2 should light up. If the Expansion Module is 

configured as a fan terminal, on a call for the fan, the LED labeled RLY1 

should light up. If the LEDs do not light up, the Expansion Module is 

probably defective and must be replaced.

Diagnostics

29

Non-Modular ZCAP Technical Guide

                         Troubleshooting

Содержание OE742-32-VAVZ

Страница 1: ...Non Modular VAV Zone Controller Actuator Package www orioncontrols com...

Страница 2: ...16 Addressing Powering Up 17 General 17 Controller Addressing 17 Power Wiring 17 Initialization and Programming 18 Initialization 18 Programming the Controller 18 VAV Zone Configuration 19 VAV Zone C...

Страница 3: ...oused in a plastic enclosure The VAV Zone Controller is a program mable digital controller which allows for program setpoints to be stored in non volatile memory The controller is connected to a room...

Страница 4: ...Figure 1 OE742 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P D Non Modular VAV Zone Controller Actuator Package Dim P D 4 Non Modular ZCAP Technical Guide Overview...

Страница 5: ...Non Modular VAV Zone Controller Actuator Pkg P I Figure 2 OE744 32 VAVZ Non Modular VAV Zone Controller Actuator Package Dimensions P I 5 Non Modular ZCAP Technical Guide Overview...

Страница 6: ...ar VAV Zone Controller Actuator Pkg Components Non Modular VAV Zone Controller Actuator Package Components Figure 4 OE744 32 Pressure Independent Non Modular VAV Zone Controller Actuator Pkg Component...

Страница 7: ...5 01 Zone Controller Expansion Module Dimensions Figure 6 OE325 01 Zone Controller Expansion Module Components Zone Controller Expansion Module Dimensions and Components 7 Non Modular ZCAP Technical G...

Страница 8: ...is used for connecting the communica tions wiring between each Non Modular VAV Zone ControllerActuator Package and or to the MiniLink Polling Device CommLink HVAC Unit Controller or other controller...

Страница 9: ...mounting bracket nuts on the ends of the universal mounting clamp enough to slide the entire actuator and plastic enclosure assembly over the terminal unit damper shaft Rotate the enclosure base actu...

Страница 10: ...onents when mounting the controller Remove the controller from its snap track mount Mark the control enclosure base using the snap track as a template Drill pilot holes in the enclosure base and secur...

Страница 11: ...Zone Controller Expansion Module Wiring Figure 8 Zone Controller Expansion Module Wiring Fan Terminals And Or Staged Electric Heat 11 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 12: ...igure 10 Zone Controller Expansion Module Wiring Fan Terminals And Or 2 Position HW Heat Figure 9 Zone Controller Expansion Module Wiring Fan Terminals And Or Modulating Hot Water Heat 12 Non Modular...

Страница 13: ...Figure 12 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary Electric Heat Figure 11 Zone Controller Expansion Module Wiring Fan Terminals And Or SCR Electric Heat 13 Non Modular Z...

Страница 14: ...munications Wiring Figure 13 Zone Controller Expansion Module Wiring Fan Terminals And Or Auxiliary 2 Position HW Heat Figure 14 Communication Power Wiring Diagram 14 Non Modular ZCAP Technical Guide...

Страница 15: ...Non Modular Devices Transformer Sizing Figure 15 Non Modular VAV Zone Controller Actuator Package Transformer Sizing 15 Non Modular ZCAP Technical Guide Installation Wiring...

Страница 16: ...slave wiring inter face card and modular cable are supplied with the OE523 Round Slaved Zone Damper OE738 Slaved VAV Zone Rectangular Damper Kit and the OE282 03 Slaved VAV Zone Damper Kit These are r...

Страница 17: ...d information regarding communication wiring and connec tion for Interconnected and Networked systems please see the Orion System Installation Troubleshooting Guide Power Wiring One of the most import...

Страница 18: ...ntroller The next step is programming the controller for your specific require ments In order to configure and program the Non Modular VAV Zone ControllerActuator Package you must have a central opera...

Страница 19: ...ional hot water valve this must be set for 0 Options available are 0 No Staging 1 1 Stage of Reheat 2 2 Stages of Reheat 3 3 Stages of Reheat Proportional Heating Signal If the box has hot water rehea...

Страница 20: ...ain fan and provide cooling or heating if so configured It will re main on until the override broadcast has not been detected for at least 2 consecutive minutes Modes of Operation There are 7 possible...

Страница 21: ...VAV Zone Controller detects that the HVAC unit is in Supply Air Heating mode indicating that the air handler has activated its heat the heating airflow minimum will be substituted for the vent minimum...

Страница 22: ...ing This prevents stages from activating at the same time Once a heating stage has been activated it must remain on for at least one minute Once it has been deactivated it must remain off for at least...

Страница 23: ...nal window starting 0 5 F below the cooling setpoint to 1 5 F above the cooling setpoint The damper airflow is never allowed to modulate outside the user adjusted minimum and the maximum setpoints The...

Страница 24: ...ng setpoints The Auxiliary Heat Relay energizes at 0 5 F below the Auxiliary Heat Setpoint and de energizes 0 5 F above the Auxiliary Heat Setpoint The Auxiliary Heat will continue to function regardl...

Страница 25: ...all amount of damper error On pressure independent terminal units the airflow is maintained to within roughly 3 of the terminal unit size constant but no tighter than 16 CFM on the smallest terminal u...

Страница 26: ...clared Maverick by the MiniLink Polling Device The zone has been configured as a VOTING zone If all the above tests are passed the zone temperature and setpoints are then included in the HVAC Mode dec...

Страница 27: ...ime so that the VAV Zone Controllers can read it and use it in their tenant and trend logs Caution These logs are subject to loss if a power outage occurs because there is no battery backed memory on...

Страница 28: ...light up the board is probably defective STAT LED Operations As previously described when the board is first powered up the LED will do the following Flashes Once Off for 5 seconds STAT LED blinks th...

Страница 29: ...entered in the configuration screen or the airflow through the box will be incorrect If none of the aforementioned procedures solves the problem remove power from the VAV Zone Controller Shut down the...

Страница 30: ...33 4 620 5 80531 4 550 0 69822 4 474 5 60552 4 390 10 52500 4 297 15 45902 4 200 20 40147 4 095 25 35165 3 982 30 30805 3 862 35 27140 3 737 40 23874 3 605 45 21094 3 470 50 18655 3 330 52 17799 3 275...

Страница 31: ...Modular and Digital Room Sensor Testing Figure 20 Testing Resistance Voltage On Modular Digital Room Sensors 31 Non Modular ZCAP Technical Guide Troubleshooting...

Страница 32: ...Method 19 C C1 8 C2 8 C3 8 CFM Factor 19 Clockwise to Open Damper 19 Components Pressure Dependent VAV Zone Controller Actuator Package 6 Pressure Independent VAV Zone Controller Actuator Package 6 Zo...

Страница 33: ...25 Connecting to Power Comm Board 15 Modes of Operation 20 Modular Connectors Actuator 8 Power Comm 8 Modular Devices Transformer Sizing 15 Modular Room Sensor Override Button 20 Modular Service Tool...

Страница 34: ...pplications 8 Analog Output 8 Auxiliary Heat 8 Fan Enable 8 Heating Stage 1 8 Heating Stage 2 8 Relay Sequencing 8 Relay Staging 22 Resistance Testing Digital Room Sensor 31 Modular Room Sensor 31 Rev...

Страница 35: ...scribed 3 Vent Minimum 21 Voltage Testing Digital Room Sensor 31 Modular Room Sensor 31 Voting 26 Voting Zone 19 W Wiring 2 Position HW Heat 12 Auxiliary 2 Position HW Heat 14 Auxiliary Electric Heat...

Страница 36: ...NMZCAP TGD 01D Printed in the USA November 2015 All rights reserved Copyright 2014 WattMaster Controls Inc 8500 NW River Park Drive Parkville MO 64152 Phone 816 505 1100 www orioncontrols com Fax 816...

Отзывы: