background image

least 10 feet away from these areas. 

3. Near air returns or heating and cooling supply vents. Install at least 3 feet away from these areas. The air 

could blow smoke away from the detector, interrupting its alarm. 

4. In rooms where temperatures may fall below 4

  or rise above 38

5. In extremely dusty, dirty, or insect-infested areas where loose particles interfere with smoke alarm 

operation. 

WARNING:

 

 

Incorrect orientation will result in a decrease in operational effectiveness.   

HOW TO INSTALL THIS SMOKE ALARM 

 

 

 

 

 

 

 

 

 

 

 

DANGER:  

ELECTRICAL SHOCK HAZARD.

 

Turn off power at the main fuse box or circuit

 

breaker by removing the fuse or

 

switching the circuit 

breaker to the

 

OFF position. 

WARNING:

 

This smoke alarm is mains powered and requires wiring by a qualified electrician in 

accordance with the current IEE Regulations for Electrical Installations (BS7671). 

The circuit used to power the smoke alarm must be a dedicated permanent supply that 

cannot be switched off accidentally by the normal user. Before installing ensure the 

electrical supply is isolated. 

1.

 

From back of smoke alarm, remove the mounting plate by turning it counterclockwise.   

(To later engage tamper-resist feature, twist out and set aside one of the pins molded into plate. Both 

pins are exactly the same.)   

2.

 

Gently pull household wires through center hole of plate. 

3.

 

Secure plate to ceiling or wall with mounting screws.   

4.

 

With a small wire connector, connect white wire from connecter plug to white household wire. 

5.

 

Connect blue wire from connector plug to blue household wire. 

6.

 

If interconnection is desired, connect yellow wire from connector to interconnect wire between smoke 

alarms. See section interconnecting smoke alarms. 

NOTE:

 If this will be used as a single-station smoke alarm, cover yellow wire with electrical tape and tuck 

it into junction box. 

7.

 

Lift open battery pocket door. 

8.

 

Connect new 9-volt battery to battery connector inside battery pocket. Be sure battery is securely 

connected. Smoke alarm may beep briefly when battery is installed.   

9.

 

Close battery pocket door, snapping it into place. 

10.

 

Attach connector plug to pins on back of smoke alarm. Plug will only fit one way and will snap into 

place. 

11.

 

Gently tug connector to be sure it is attached securely.   

Содержание VST-IS5981

Страница 1: ...connector for easy installation Fitting and battery tamper resist feature Inter connectable up to 40 units Alarm and AC power supply indicator Extra loud alarm sound over 85 dB Low battery warning ind...

Страница 2: ...or indoor noise sound sleepers drug or alcohol usage the hard of hearing etc If you suspect that this smoke alarm may not alert a household member install and maintain specialty smoke alarms Househol...

Страница 3: ...moke alarms on walls between 4 and 12 inches from ceiling wall intersections 2 Install a minimum of two smoke alarms in every home no matter how small the home 3 Install a smoke alarm in each room tha...

Страница 4: ...lectrical supply is isolated 1 From back of smoke alarm remove the mounting plate by turning it counterclockwise To later engage tamper resist feature twist out and set aside one of the pins molded in...

Страница 5: ...OKE ALARM Once the smoke alarm has been installed a small GREEN indicator light LED should be visible through the alarm grill indicating that AC supply is healthy A RED indicator light LED should also...

Страница 6: ...nterclockwise to detach it from the mounting plate 3 Gently pull down smoke alarm 4 Remove battery from the compartment 5 Insert a new 9 volt battery to connector NOTE POLARITY OF CONNECTIONS Ensure t...

Страница 7: ...tice fire safety rules and prevent hazardous situations TROUBLESHOOTING WARNING DO NOT disconnect battery to quiet an unwanted alarm This will remove your protection Fan the air or open a window to re...

Отзывы: