Orcomm ORC-24F-RS485 Скачать руководство пользователя страница 4

M_V1.0 

 ORC-HC2-24 

 

 

 

 

 

 

 

 

Installer Mode 

Installer Options  

 

Function 

Setting / Option 

Default  

Offset / calibration  

 

-1 

 

Not available  

00 

Lock  

00 = All the buttons are locked except power 
01 = All the buttons are locked  

01 

 

Not available  

01 

Min set Temp 

 

15’C

 

18 

Max set Temp 

 

35’C

 

32 

Time Format 

00 = 12 hour,  01 = 24 hour  

01 

Display Mode 

00 = Set and Room Temperature 
01 = only Set Temperature  

00 

 

Not available  

Address 

Modbus address (HEX) 

01 

B  

Baud Rate 

 

 

Enter Installer Menu  

To Enter installer menu  

1.  Turn off the LRC (Home screen blank) 
2.  Press and hold       and then        until display changes (3 seconds)     
3.  Now choose option to change by using      to toggle through options (note 3 sec time out) 
4.  Change the Default value using                

5.  Then move to next option using 

 

M

    

6.  Setting will auto save when timed out 

Best practice

 

when finished setting up the LRC, turn all power OFF and ON again to allow controls to reset.

   

Cabling  

2 versions of cable entry on rear of unit  

Version 1  

flying lead (RED/WHITE) to connect to for RS485 connection  

Version 2  

terminal on rear for A B  [A = RS485+, B = RS485 -] 

 

 

            

 

Version 1  

 

 

 

Version 2 

Additional notes 

Long cable runs on Modbus will require 120 ohm ¼W end of line resistor. 
BIAS Resistors can be used at the beginning of the bus to help control higher than normal voltages.  
Example 120 ohm across A & B, 1K across A and 12VDC, 1K across B and GND 

 NOTE turn off before 

installing resistors. 

Содержание ORC-24F-RS485

Страница 1: ...85 ORC 24C RS485 ORC 24D RS485 86 x 86 x 15mm Contents Introduction 2 Versions 2 Home Screen 3 Adjusting LRC 3 Desired Room temperature 3 Fan speed 3 Lock Mode optional 3 Enter Lock mode 3 Exit Lock Mode 3 Installer Mode 4 Installer Options 4 Enter Installer Menu 4 Cabling 4 ...

Страница 2: ...H ORC HC2 24D RS485 WH ORC HC2 24D RS485 WHF ORC HC2 24F RS485 WH Screen LCD LCD LCD 24V DC 100mA Power 24V DC 100mA 24V DC 100mA 24V DC 100mA 24V DC 100mA Data RS485 Modbus RS485 Modbus RS485 Modbus RS485 Modbus LRC Ver HC2 HC2 HC2 HC2 Bus filter 12v p p 12v p p 4v p p 4v p p Sensors Internal Internal External Internal Internal Fan control YES YES YES YES UFH Control YES YES YES YES Local Control...

Страница 3: ...to operate the controls The change may take up to 3 minutes before operation starts Fan speed The Home screen will display the current Fan speed OFF LOW MID HIGH AUTO To change the Fan speed press the symbol until the option on the Home screen is correct NOTE If you manually take control of the fan speed it will stay at the speed irrelevant of temperature difference Lock Mode optional Enter Lock m...

Страница 4: ...nds 3 Now choose option to change by using to toggle through options note 3 sec time out 4 Change the Default value using 5 Then move to next option using M 6 Setting will auto save when timed out Best practice when finished setting up the LRC turn all power OFF and ON again to allow controls to reset Cabling 2 versions of cable entry on rear of unit Version 1 flying lead RED WHITE to connect to f...

Отзывы: