OM 502

5 DIGIT PROGRAMMABLE INSTRUMENT

DC VOLTMETER/AMMETER

PROCESS MONITOR

INTEGRATOR

LINEARIZATOR

DISPLAYS FOR LINEAR POTENTIOMETERS 

DISPLAY INSTRUMENT FOR TENSIOMETERS

DISPLAYS FOR LVDT SENSORS

USER MANUAL

148.9~C

-263mm

453mV

Outstanding Measurement Value

Содержание OM 502

Страница 1: ...INSTRUMENT DC VOLTMETER AMMETER PROCESS MONITOR INTEGRATOR LINEARIZATOR DISPLAYS FOR LINEAR POTENTIOMETERS DISPLAY INSTRUMENT FOR TENSIOMETERS DISPLAYS FOR LVDT SENSORS USER MANUAL 148 9 C 263mm 453mV Outstanding Measurement Value ...

Страница 2: ...ation and safety regulations The manufacturer is not liable for damage caused by improper installation configuration maintenance and service The recorder must be installed according to the respective application Incorrect installation can cause a malfunction which can result in damage or accident The recorder uses dangerous voltages that can cause a fatal accident Before you start solving problems...

Страница 3: ...n of PROFI menu 40 6 1 PROFI menu INPUTS 6 1 1 Resetting internal values 42 6 1 2 Setting measuring type range mode rate 43 6 1 3 Setting the Real Time 45 6 1 4 External input function selection 48 6 1 5 Optional accessory functions of the keys 49 6 2 PROFI menu CHANNEL 6 2 1 Setting measuring parameters projection filters decimal point description 57 6 2 2 Setting mathematic functions 57 6 2 3 Se...

Страница 4: ...on may be set for both limit values of the input signal e g input 0 20 mA 0 8500 0 Projection 99999 99999 999999 Integration I with time base 1 s projection of integrated and current value Weighing function T manual or automatic calibration signalization of stabilized equilibrium zero stabilization automatic zero monitoring defined number of sections on the scale Projection T 99999 Mode Standard s...

Страница 5: ...with the option of visualization and archiving in PC The OM Link Standard version has no limitation of the number of instruments connected 2 3 OPTIONS Excitation is suitable for supplying power to sensors and transmitters It has a galvanic separation Comparators are assigned to monitor one two three or four limit values with relay output The user may select limits regime LIMIT DOSING FROM TO The l...

Страница 6: ...ecommend to abide by the above mentioned principles MEASURING RANGES TYPE INPUTS I INPUTS U DC 999 99 µA 9 9999 mA 99 999 mA 999 99 mA 5 0000 A 999 99 mV 999 99 mV 9 9999 V 99 999 V 300 00 V PM 0 5 20 mA 4 20 mA 2 5 10 V I 0 5 20 mA 4 20 mA 2 5 10 V LX 0 5 20 mA 4 20 mA 2 5 10 V DU Linear potentiometer min 500 Ω T 1 4 2 8 4 16 mV V Termination of RS 485 communication line Full Significance Default ...

Страница 7: ...Open collector C 3 E 4 C 4 E 3 3W 5W A B C D E F G H OM 502LVDT Excitationvaluemaybesetbytrimmerabove the terminal block no 17 Signal SENSE measures supply voltage on tensionmeter upon 6 wire connection for 4 wireconnectionjoinbrackets B CandF G directly on the instrument Whenusing the instrument in highly disturbing environemnt we recommend using 4 wire connection Grounding on terminal block 3 ha...

Страница 8: ...l output powered by instrument s excitation Example connection of a 3 wire sensor with current signal output powered by instrument s excitation L N E 1 2 3 14 15 16 17 A B C D E F G H INPUT I Excitation Sensor Sensor L N E 1 2 3 14 15 16 17 A B C D E F G H INPUT I Excitation Output Supply Supply Output GND GND ...

Страница 9: ...M 502 9 INSTRUMENT CONNECTION 3 Example connection of 3 wire sensor with voltage signal output powered by instrument s excitation L N E 1 2 3 14 15 16 17 A B C D E F G H INPUT U Excitation Output Supply Supply Output GND GND ...

Страница 10: ... MENU Tree menu structure SETTING LIGHT For trained users Only items necessary for instrument setting Access is password protected Possibility to arrange items of the USER MENU Linear menu structure SETTING USER For user operation Menu items are set by the user Profi Light as per request Access is not password protected Optional menu structure either tree PROFI or linear LIGHT ...

Страница 11: ...he programming menu LIGHT PROFI which determine the right see or change acces without password Complete instrument operation and setting may be performed via OM Link communication interface which is a standard equip ment of all instruments The operation program is freely accessible www orbit merret eu and the only requirement is the purchase of OML cable to connect the instrument to PC It is manuf...

Страница 12: ...not be stored after pressing the key the set value will be stored 30 continues on page 30 Setting the decimal point and the minus sign DECIMAL POINT Its selection in the menu upon modification of the number to be adjusted it is performed by the control key with transition beyond the highest decade when the decimal point starts flashing Positioning is performed by THE MINUS SIGN Setting the minus s...

Страница 13: ...T MENU SETTING NUMBERS SELECTION access into USER menu exit menu quit editing programmable key function back to previous level move to higher decade programmable key function move to previous item move down programmable key function move to next item move up programmable key function confirm selection confirm setting selection numeric value is set to zero access into LIGHT PROFI menu direct access...

Страница 14: ...etting Access is password protected Possibility to arrange items of the USER MENU Linear menu structure Upon delay exceeding 60 s the program ming mode is automatically discontinued and the instrument itself restores the measuring mode Password 0 Menu LIGHT USER menu off Setting the items DEF Preset from manufacture ...

Страница 15: ...e Setting projection and tensionemeter sensitivity DU 100 00 MAX A FORM A 0000 oo 0 00 MIN A Setting projection LX 0 00 MAX A MAX A 100 00 4 20mA MODE Selecting measuring range Projection setting Table selection TAB x TAB 0 0000 oo FORM A I 0 00 MAX A MAX A 100 00 4 20mA MODE Selecting measuring range Projection setting Setting multiplying and dividing constanty SCALE 1 1 DIVID 0000 oo FORM A DC 1...

Страница 16: ...e LVDT 30 142 8 PASSW 0 Entering access password for access into the menu PASSW Access into instrument menu PAS 0 access into menu is unrestricted after releasing keys you automaticaly move to first item of the menu PAS 0 access into menu is protected ny number code Set Password 42 Example 0 1 2 02 12 42 22 32 TYPE ...

Страница 17: ...INSTRUCTIONS FOR USE OM 502 17 SETTING LIGHT 5 ...

Страница 18: ...ede DEF 0 Projection for 0 mV MIN A 25 Example 0 Setting for minimum input signal MIN A 100 MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of the DP does not affect display projection the DP is automatically shifted after the value is confirmede DEF 100 Setting for maximum input signal MAX A Projection for 999 9 mV MAX A 3500 Exa...

Страница 19: ...P on display 00000 o Example FORM A Setting projection of the decimal point positioning of the DP is set here in the measuring mode DEF 0000 oo FORM A MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo 00000 o 32 subsequent item on the menu depends on instrument equipment ...

Страница 20: ...after the value is confirmede DEF 0 Setting for minimum input signal MIN A Projection for 0 mA MIN A 25 Example 0 MAX A 1 05 5 4 3 2 05 5 15 25 MODE Selection of the instrument measuring range DEF 4 20 mA MODE Menu Range 0 5mA 0 5 mA 0 20mA 0 20 mA 4 20mA 4 20 mA 0 2 V 2 V 0 5 V 5 V 0 10 V 10 V Er 4 20 4 20 mA with error statement of underfl ow upon signal smaller than 3 36 mA Range 0 20 mA Exampl...

Страница 21: ...e setting 99999 99999 999999 position of the DP does not affect display projection the DP is automatically shifted after the value is confirmede DEF 100 Setting for maximum input signal MAX A Projection for 20 mA MAX A 2500 Example 100 100 100 400 300 200 FORM A 500 1500 2500 0500 Projection of DP on display 00000 o Example FORM A MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo ...

Страница 22: ...MODE Menu Range 0 5mA 0 5 mA 0 20mA 0 20 mA 4 20mA 4 20 mA 0 2 V 2 V 0 5 V 5 V 0 10 V 10 V Er 4 20 4 20 mA with error statement of underfl ow upon signal smaller than 3 36 mA Range 0 20 mA Example 4 20mA 0 20mA MIN A 0 5mA 0 20mA 4 20mA 0 10 V 0 40 V Er 4 20 MODE 0 MAX A 00 10 100 MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of...

Страница 23: ...iding constant range 1 10 60 100 1 000 3 600 by using the multiplying and dividing constant it is easy to set the displayed value for required time period DEF 1 SETTING LIGHT 5 FOR INSTRUMENT OM 502I Projection of DP on display 00000 o Example FORM I MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo 00000 o 32 1 Setting the multiplying constant SCALE Multiplying constant 1 SCALE 1...

Страница 24: ...MODE Menu Range 0 5mA 0 5 mA 0 20mA 0 20 mA 4 20mA 4 20 mA 0 2 V 2 V 0 5 V 5 V 0 10 V 10 V Er 4 20 4 20 mA with error statement of underfl ow upon signal smaller than 3 36 mA Range 0 20 mA Example 4 20mA 0 20mA MIN A 0 5mA 0 20mA 4 20mA 0 10 V 0 40 V Er 4 20 MODE 0 MAX A 00 10 100 MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of...

Страница 25: ...oo TAB X Selection of the linearization table DEF TAB 0 FOR INSTRUMENT OM 502LX 5 SETTING LIGHT Projection of DP on display 00000 o Example FORM M MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo 00000 o 32 TAB X Selection of the linearization table Table no 1 TAB 1 Example FORM M TAB 0 TAB 1 subsequent item on the menu depends on instrument equipment ...

Страница 26: ...is confirmede DEF 0 Projection for the beginning MIN A 0 Example 0 Setting for minimum input signal MIN A 100 MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of the DP does not affect display projection the DP is automatically shifted after the value is confirmede DEF 100 Setting for maximum input signal MAX A Projection for the e...

Страница 27: ...of the DP is set here in the measuring mode DEF 0000 oo Projection of DP on display 00000 o Example FORM A MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo 00000 o 32 Calibration of the beginning and the end of range of linear potentiometer is on page 35 subsequent item on the menu depends on instrument equipment ...

Страница 28: ...used by load cell deformation automatic zeroing of thare after weight is taken off the scales defined number of scale divisions DEF STAND MODE Menu Measuring mode STAND Standard WEIGHT Weighing function SETTING LIGHT 5 FOR INSTRUMENT OM 502T Mode WEIGHT Example MODE STAND MAX A WEIGHT STAND WEIGHT RANGE Selection of measuring range DEF 2 mV V RANGE Menu Measuringrange 2 mV V 0 2 4 mV V 4 mV V 0 4 ...

Страница 29: ...000 o Example FORM A MENU 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P 0000 oo 00000 o subsequent item on the menu depends on instrument equipment MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of the DP does not affect display projection the DP is automatically shifted after the value is confirmede DEF 100 100 Setting t...

Страница 30: ... WIRE 3 wire 5 WIRE 5 wire Mode 5 WIRE Example 3 WIRE 5 WIRE GAIN 3 WIRE 5 WIRE MODE GAIN Input gain selection gain of input section it is advisable to use gain to such a degree when input does not overflow DEF GAIN 1 GAIN Menu Gain GAIN 1 1x GAIN 2 2x GAIN 6 6x GAIN 12 12x GAIN GAIN GAIN 2 Example GAIN 1 MAX A GAIN 2 GAIN 1 GAIN 2 GAIN 6 GAIN 12 ...

Страница 31: ...put signal range of the setting 99999 99999 999999 position of the DP does not affect display projection the DP is automatically shifted after the value is confirmede DEF 0 Projection for the beginning MIN A 0 Example 0 Setting for minimum input signal MIN A 100 MAX A Setting display projection for maximum value of input signal range of the setting 99999 99999 999999 position of the DP does not af...

Страница 32: ...ange of the setting 99999 999999 contingent modification of hysteresis or delay may be performed in PROFI menu DEF 40 DEF Hystresis 0 Delay 0 Setting boundary for limit 2 Setting limit 2 L 2 53 1 Example 40 41 41 131 031 31 331 MENU Setting limit 1 L 1 32 Example 20 22 21 32 22 MENU 00531 0531 531 431 000531 000531 00053 1 231 DISPLAYED ONLY WITH OPTIONS COMPARATORS subsequent item on the menu dep...

Страница 33: ...etting boundary for limit 4 range of the setting 99999 999999 contingent modification of hysteresis or delay may be performed in PROFI menu DEF 80 DEF Hystresis 0 Delay 0 Setting boundary for limit 4 Setting limit 4 L 4 103 Example 80 82 81 93 83 83 003 MENU Setting limit 3 L 3 85 Example 60 62 61 64 63 103 03 65 75 65 85 MENU subsequent item on the menu depends on instrument equipment subsequent ...

Страница 34: ...ange Description 0 20mA 0 20 mA Er 4 T 4 20 mA with error message indication and broken loop indication 3 6 mA 4 20T 4 20 mA with broken loop indication 3 6 mA Er 4 20 4 20 mA with indication of error statement 3 6 mA 4 20mA 4 20 mA 0 5mA 0 5 mA 0 2 V 0 2 V 0 5 V 0 5 V 0 10 V 0 10 V 10 V 10 V DEF 4 20 mA Type of analog output 0 10 V TYP A O 0 10 V Example 4 20mA 0 2 V 0 5mA 0 10 V 0 5 V MIN A O 0 ...

Страница 35: ...g the display value to the end of the AO range range of the setting 99999 999999 DEF 100 100 Assigning the display value to the end of the AO range Display value for the end of the AO range MAX A O 120 Example 100 100 120 110 MENU DISPLAYED ONLY WITH OPTIONS ANALOG OUTPUT ...

Страница 36: ...easible to restore manufacture calibration Prior to execution of any modifications you will be asked to confirm your selection YES RE CAL Restoration of manufacture setting RE CAL Example RE CAL RE SET YES YES RE SET Restoration of manufacture instrument setting in the event of error setting the manufacture setting may be restored restorationisperformedforthecurrentlyselected type of the instrumen...

Страница 37: ...libration of input range the potentiometer sensor traveller in end position prior confirming the flashing YES sign the potentiometer sensor traveller has to be in given idle position Calibration of the end of the range C MAX Example Calibration of the beginning of the range C MIN Example C MAX YES flashing legend C MIN YES flashing legend YES C MAX Only for type DU and LVDT YES LANG Type DU and LV...

Страница 38: ...S LI ENGL 0 Setting new access password PAS LI PAS LI Setting new access password access password for menu LIGHT range of the number code 0 9999 upon setting the password to 0000 the access to menu LIGHT is free without prompt to enter it in case the password is lost please contact the adminstrator of this device DEF 0 New password 341 PAS LI 341 Example 0 IDENT 1 01 11 21 31 41 041 341 241 141 CZ...

Страница 39: ... SW version and current input setting Mode if SW version contains a letter in first position then it is a customer SW after the identification is completed the menu is automatically exited and the instrument restores the measuring mode YES OM 502PM 90 001 4 20mA SW version setting the input range instrument type 142 8 Return to measuring mode ...

Страница 40: ...umber code designed for expert users preset from manufacture is menu LIGHT Switching over to PROFI menu access to PROFI menu authorization for access to PROFI menu does not depend on setting under item SERVIC MENU password protected access unless set as follows under the item SERVIC N PASS PROFI 0 access to menu selected under item SERVIC MENU LIGHT PROFI password protected access unless set as fo...

Страница 41: ...INSTRUCTIONS FOR USE OM 502 41 6 SETTING PROFI ...

Страница 42: ...C OUTPUT CLEAR EXT IN CONFIG KEYS INPUTS CL TAR CL M M RTC CL INT CL MEM CL SUM CLEAR Resetting internal values CL TAR Tare resetting CL M M Resetting min max value resetting memory for the storage of minimum and maximum value achieved during measurement CL INT Resetting integrated value only for instrument OM 502I CL SUM Resetting the sum summation serves for cummulative totals of values e g shif...

Страница 43: ...00 0 100 0 measurement s 66 7 66 7 measurement s 50 0 50 0 measurement s 25 0 25 0 measurement s 12 5 12 5 measurement s 10 0 10 0 measurement s 8 0 8 0 measurement s 4 0 4 0 measurement s 2 0 2 0 measurement s 1 0 1 0 measurement s 0 5 0 5 measurement s 0 3 0 3 measurement s 0 1 0 1 measurement s CHANNE SERVIC OUTPUT CLEAR EXT IN KONFIG KEYS INPUTS READ S RTC A ZERO TRACE 0 RANGE 2 mV V 8 mV V 4 ...

Страница 44: ...Voltage range after automatic calibration MODE Menu Measuring range STAND Standard mode WEIGHT Weighing mode MODE Menu Connection 3 WIRE 3 wire 5 WIRE 5 wire WEIGHT CHANNE SERVIC OUTPUT CLEAR EXT IN KONFIG KEYS INPUTS READ S RTC A ZERO TRACE 0 MODE NO YES DEF RANGE TRACE 0 Selection of automatic zero monitoring NO Function is off YES Function is on in 4 ofthemeasuringrangezeroautomatically faces t...

Страница 45: ... with adjustable frequency 2 5 5 10 kHz 5V xx Power supply 5 V with adjustable frequency 2 5 5 10 kHz CHANNE SERVIC OUTPUT CLEAR EXT IN CONFIG KEYS INPUTS READ S RTC GAIN PRIMAR GAIN 1 GAIN 2 DEF MODE GAIN 12 GAIN 6 GAIN Input gain selection gain of input section it is advisable to use gain to such a degree when input does not overflow GAIN 1 1x GAIN 2 2x GAIN 6 6x only for 3 wire sensors GAIN 12 ...

Страница 46: ...UMA TIME 00 00 00 DATE 00 00 00 LOG M NO ALL IN OUT LOG I NO ALL IN OUT DESC I 0 FORM I 000000 00000 o FLOA P INTEG INP I DIVID 1 SCALE 1 NO YES SUBTR UNSEN 0 NO CHAN A FIL A MAT FN MAT FN CHANNE P TAR A 0 MAX A 100 SET A CHAN A MIN A 0 FORM A 000000 00000 o FLOA P INP M M MIN MAX NO CHAN A FIL A MAT FN LOG A NO ALL IN OUT DESC A 0 MOD F A CON F A 0 NO ROUND FILTER MAX W 100 E 1 1 SENSE 2 CON F 0 ...

Страница 47: ... OUTPUT LIMITY LIM 1 LIM 4 INP L 1 MOD L 1 TYP L 1 ON L 1 OFF L 1 PER L 1 0 0 0 HYS L 1 0 LIM L 1 20 0 TIM L 1 HYSTER FROM DOSING CLOSE OPEN NO CHAN A FIL A INTEG ADDR 0 DATA DAUB 600 1200 2400 115200 230400 PROT ASCII M BUS MODBUS 100 MAX A O 0 MIN A O AN OUT INP A O NO CHAN A FIL A MIN MAX INTEG TYP A O 0 20mA Er 4 T 4 20 T Er 4 20 4 20mA 0 5mA 0 2V 0 5V 0 10V 10V DISP PERM CHAN A FIL A MAT FN M...

Страница 48: ... programming menu LIGHT PROFI TARE Tare activation CL TAR Tare resetting CL M M Resetting min max value SAVE Activation of the measured data record into instrument memory not in standard equipment CL INT Resetting integrated value only for instrument OM 502I CL SUM Resetting the sum only for instrument OM 502I CL MEM Clearing memory for option FAST RTC CHAN A Displaying value of Channel A FIL A Di...

Страница 49: ...ction CL M M Resetting min max value CL TAR Tare resetting MENU Direct access into menu on selected item after confirmation of this selection the MNU LE item is displayed on superior menu level where required selection is performed TEMP V Temporary projection of selected values after confirmation of this selection the item TMP LE is displayed on superior menu level whererequired selection is perfo...

Страница 50: ...HAN A Temporary projection of Channel A value FIL A Temporary projection of Channel A value after processing digital filters MAT FN Temporary projection of Mathematic functions value MIN Temporary projection of Min value MAX Temporary projection of Max value INTEG Temporary projection of Integrated value LIM 1 Temporary projection of Limit 1 value LIM 2 Temporary projection of Limit 2 value LIM 3 ...

Страница 51: ...tem LIM 1 Direct access to item LIM 1 LIM 2 Direct access to item LIM 2 LIM 3 Direct access to item LIM 3 LIM 4 Direct access to item LIM 4 HYS 1 Direct access to item HYS 1 HYS 2 Direct access to item HYS 2 HYS 3 Direct access to item HYS 3 HYS 4 Direct access to item HYS 4 ON 1 Direct access to item ON 1 ON 2 Direct access to item ON 2 ON 3 Direct access to item ON 3 ON 4 Direct access to item O...

Страница 52: ...tting parameters for integrator OM 502I MIN MAX Selection of access and evaluation of Min max value CHANNE SERVIC OUTPUT CHAN A INTEGR MAT FN INPUTS FILTER FORM A SET A P TAR A MAX A MIN A LOG A DESC A 0 00 MIN MAX SET A Setting display projection MIN A Setting display projection for minimum value of input signal range of the setting is 99999 999999 menu is dynamic after using automatic calibratio...

Страница 53: ...m is displayed only in automatic calibration E 1 Setting the size of sections for projection range 0 001 0 002 0 005 0 01 100 MAX W Setting the upper weighing limit range of the setting is 99999 999999 0 00 LOG A DESC A CHANNE SERVIC OUTPUT CHAN A INTEGR MAT FN INPUTS FILTER FORM A SET A P TAR A MAX A MIN A MIN MAX P TAR A Setting Fixed tare value setting is designed for the event when it is neces...

Страница 54: ...average from given number CON F A of measured data and updates with each measured value range 2 30 EXPON Selection of exponential filter integration filter of first prvního grade with time constant CON F A measurement range 2 100 ROUND Measured value rounding is entered by any number which determines the projection step e g CON F A 2 5 display 0 2 5 5 CON F A Setting constants this menu item is al...

Страница 55: ...ts most exact form FLOAT P 000000 Setting DP XXXXXX 00000 o Setting DP XXXXX x 0000 oo Setting DP XXXX xx DEF 000 ooo Setting DP XXX xxx 00 oooo Setting DP XX xxxx 0 ooooo Setting DP X xxxxx FLOA P Floating DP INTEGR CHANNE SERVIC OUTPUT INPUTS FILTER SET A FORM A DESC A LOG A CHAN A MIN MAX MAT FN 00 DESC A Setting projection of descript for Channel A projection of mesured data may be extended at...

Страница 56: ...ory by selection in this item you allow to register values into instrument memory another setting in item OUTPUT MEMORY not in standard experiment NO Measured data is not stored ALL Measured data is stored in memory IN Only data measured within the set interval is stored in memory OUT Only data measured outside the set interval is stored in memory FROM A Setting the initial interval value setting ...

Страница 57: ... Mathematic functions are off MULTIN Multinominal F Ex Dx Cx Bx Ax 2 3 4 5 1 MUL 1 x F x E x D x C x B x A 5 2 3 4 LOGAR Logarithm F E Dx C Bx A ln EXPON Exponenciál F e A E Dx C Bx POWER Power F C Bx A E Dx ROOT Root F E Dx C Bx A SIN X Sin x F E D C B A sinx x sin x sin x sin x sin 2 3 4 5 TAB X Switching on linearization table this menu can only be accessed in OM 502LX CON Setting constants for...

Страница 58: ...umber 14 TAB 15 Table number 15 CHANNE SERVIC OUTPUT INPUTS MIN MAX CHAN A MAT FN MATH F CON A CON B CON C CON D CON E CON F DESC M FORM M LOG M 000000 FLOA P 0 ooooo 00 oooo 000 ooo 0000 oo 00000 o INTEGR TAB X FORM M Selection of decimal point the instrument allows for classic projection of a number with positioning of the DP as well as projection with floating DP allowing to display a number in...

Страница 59: ...de in period 0 95 description is cancelled by code 00 DEF no description Table of signs on page 85 TAB X DEF NO TO M FROM M SAVE M OUT IN ALL INTEGR CHAN A MAT FN CHANNE SERVIC OUTPUT INPUTS MATH F CON A CON B CON C CON D CON E CON F DESC M FORM M LOG M MIN MAX LOG M Selection of storing data into instrument memory by selection in this item you allow to register values into instrument memory anoth...

Страница 60: ...FIL A From Channel A after modification by dig fiter MAT FN From Mathematic functions CHANNE SERVIC OUTPUT CHAN A MIN MAX MAT FN INPUTS INP I INTEGR UNSEN DESC I FORM I CLEAR SUBTR DIVID SCALE LOG I SCALE Setting the multiplying constant through multiplying constant we may further mathematically adjust the data display projection range of the setting is 1 100 000 DEF 1 DIVID Setting the dividing c...

Страница 61: ...y setting this item it is possible to extend Zero and thus achieve integration of the input signal from the set value range of the setting is 0 100 000 DEF 0 CHANNE SERVIC OUTPUT CHAN A MIN MAX MAT FN INPUTS INP I INTEGR UNSEN DESC I FORM I CLEAR SUBTR DIVID SCALE LOG I DEF YES NO SUBTR Selection of the type of integration the selection allows to suppress the negative value of input signal i e the...

Страница 62: ... enabled upon display overflow the instrument is automatically reset to zero and proceeds in continuous measuring CHANNE SERVIC OUTPUT CHAN A MIN MAX MAT FN INPUTS INP I INTEGR UNSEN DESC I FORM I CLEAR SUBTR DIVID SCALE LOG I DEF 000000 00000 o 0000 oo 000 ooo 00 oooo 0 ooooo FLOA P FORM I Selection of decimal point the instrument allows for classic projection of a number with positioning of the ...

Страница 63: ...eriod 0 95 description is cancelled by code 00 DEF no description Table of signs on page 85 DEF NO TO I FROM I SAVE I OUT IN ALL CHANNE SERVIC OUTPUT CHAN A MIN MAX MAT FN INPUTS INP I INTEGR UNSEN DESC I FORM I CLEAR SUBTR DIVID SCALE LOG I LOG I Selection of storing data into instrument memory by selection in this item you allow to register values into instrument memory another setting in item O...

Страница 64: ...IN MAX MAT FN INPUTS INP M M NO CHAN A FIL A MAT FN DEF INTEGR INP M M Selection of evaluation of min max value selection of value from which the min max value will be calculated NO Evaluation of min max value is off CHAN A From Channel A FIL A From Channel A after digital filters processing MAT FN From Mathematic functions ...

Страница 65: ...INSTRUCTIONS FOR USE OM 502 65 6 SETTING PROFI ...

Страница 66: ...o memory LIMITS Setting type and parameters of limits DATA Setting type and parameters of data output AN OUT Setting type and parameters of analog output DISP Setting display projection and brightness CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY YES NO DEF START REWRIT TRIGER STOP PERIOD REWRIT Selection of the mode of data logging selection of the mode in the event of full instrumen...

Страница 67: ...ory ext input button LED M flashes after reading TRIGGER memoryispermanentlyshining InROLLflashes constantly 2 Triggering external input button after the memory LED is full M turns off in the ROLL mode the trigger ends datalogging and LED turns off 3 Termination ext input button or reading data via RS The lowest recording rate possible is once a day the highest is every second Under exceptional ci...

Страница 68: ...witch off Switch on relay Switch off relay TYPE SWITCH ON TYPE SWITCH OFF LED signalization LED signalization JNJU JNJU IZTUFSFTJT EFMBZ 0 i 45 3w axis x LIM L limit H 2 hysteresis Z 0 Switch on relay TYPE SWITCH ON Z 0 Switch on relay TYPE SWITCH OFF LED signalization LED signalization Z 0 Switch off relay TYPE SWITCH ON LED signalization z z z z z z z z Switch off relay TYPE SWITCH OFF LED signa...

Страница 69: ...ed value Setting is identical for LIM 1 LIM 2 LIM 3 and LIM 4 CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY LIM 3 LIM 2 LIM 1 LIM 4 INP L 1 MOD L 1 TYP L 1 LIM L 1 HYS L 1 ON L 1 OFF L 1 PER L 1 TIM L 1 HYSTER DOSING FROM DEF MOD L 1 Selection the type of limit HYSTER Limit is in mode Limit hysteresis delay for this mode the parameters of LIM L 1 are set at which the limit will shall ...

Страница 70: ...D L 1 TYP L 1 LIM L 1 HYS L 1 ON L 1 OFF L 1 PER L 1 TIM L 1 LIM L 1 Setting limit for switch on for type HYSTER HYS L 1 Setting hysteresis for type HYSTER indicates the range around the limit in both directions LIM 1 2 HYS ON L 1 Setting the outset of the interval of limit switch on for type FROM OFF L 1 Setting the end of the interval of limit switch on for type FROM PER L 1 Setting the period o...

Страница 71: ...00 Rate 600 Baud 1200 Rate 1 200 Baud 2400 Rate 2 400 Baud 4800 Rate 4 800 Baud 9600 Rate 9 600 Baud 19200 Rate 19 200 Baud 38400 Rate 38 400 Baud 57600 Rate 57 600 Baud 115200 Rate 115 200 Baud 230400 Rate 230 400 Baud CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY BAUD PROT ADDR AD MOD ADR P B 0 ADDR Setting instrument address setting in range 0 31 DEF 00 AD MOD Setting instrument ad...

Страница 72: ...tocol MODBUS RTU option is available only for RS 485 CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY INP A O TYP A O MIN A O MAX A O NO FIL A MAT FN CHAN A DEF MAX MIN INTEG INP A O Selection evaluation analog output selectionofvaluefromwhichtheanalogoutput will be evaluated NO AO evaluation is off CHAN A AO evaluation from Channel A FIL A AO evaluation from Channel A after digital filt...

Страница 73: ...3 6 mA Er 4 20 Type 4 20 mA with indication with indic of error statement 3 6 mA 4 20mA Type 4 20 mA 0 5mA Type 0 5 mA 0 2V Type 0 2 V 0 5V Type 0 5 V 0 10V Type 0 10 V 10V Type 10 V CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY INP AO TYP A O MIN A O MAX A O 0 0 AN OUT Setting the analog output range analog output is isolated and its value corresponds with displayed data It is fully ...

Страница 74: ...Channel A after digital filters processing MAT FN Projection of values from Math functions MIN Projection of values from Min value MAX Projection of values from Max value INTEG Projection of values from Integrated value CHANNE SERVIC OUTPUT LIMITS AN OUT DATA DISP INPUTS MEMORY PERM BRIGHT 100 50 25 75 DEF 0 BRIGHT Selection of display brightness by selecting display brightness we may appropriatel...

Страница 75: ...INSTRUCTIONS FOR USE OM 502 75 6 SETTING PROFI ...

Страница 76: ...ion LANG Language version of instrument menu N PASS Setting new access password IDENT Instrument identification CHANNE SERVIC OUTPUT MENU RESTOR LANG INPUTS N PASS LIGHT PROFI DEF CALIB IDENT MENU Selection of menu type LIGHT PROFI enablessettingthemenucomplexityaccording to user needs and skills LIGHT Active LIGHT menu simpleprogrammingmenu containsonlyitems necessary for configuration and instru...

Страница 77: ...SET Restoration of instrument manufacture setting TYPE Restoration of instrument manufacture setting generating the manufacture setting for currently selected type of instrument items marked DEF STAND Restoration of instrument manufacture setting generating the manufacture setting for currently selected type of instrument items marked DEF only for OM 502T WEIGHT Restoration of instrument manufactu...

Страница 78: ... OUTPUT MENU RESTOR N PASS INPUTS IDENT CALIB C MIN MIN C MAX LANG EDIT MAX EDIT Modification of internal calibration constants this option is designed solely for contingent metrological examination and protocol item is availale after aut calibration MIN Minimum calibration range range 99 0000 MAX Maximum calibration range range 99 0000 After incorrect client calibration it is always possible to r...

Страница 79: ...S LI N PASS Setting new password for access to LIGHT and PROFI menu this option allows to change the numeric code whichblockstheaccessintoLIGHTand PROFI menu numerci code range 0 9999 universal passwords in the event of loss LIGHT Menu 8177 PROFI Menu 7915 CHANNE SERVIC OUTPUT MENU RESTOR N PASS INPUTS IDENT CALIB LANG 90 001 OM 502PM 4 20mA IDENT Projection of instrument SW version display shows ...

Страница 80: ...g without the option to change the primary instrument setting e g repeated change of limit setting there are no items from manufacture permitted in USER menu on items indicated by inverse triangle LIM 1 setting may be performed in LIGHT or PROFI menu with the USER menu then overtaking the given menu structure Setting NO item will not be displayed in USER menu YES item will be displayed in USER men...

Страница 81: ...s pressed the display will read LIM L 1 By pressing button you confirm your selection and then you can set the desired limit value or by pressing the button you can go to setting of LIM L 2 where you can proceed identically as with Limit one You can exit the setting by pressing the button by which you store the latest setting and pressing the button will take you back to the measuring mode 142 8 P...

Страница 82: ...TOCOL TRANSMITTED DATA Data solicitation PC 232 ASCII A A CR MessBus No data is transmitted permanently 485 ASCII A A CR MessBus SADR ENQ Data transmission instrument 232 ASCII D D D D D D D D D D CR MessBus STX D D D D D D D D D D ETX BCC 485 ASCII D D D D D D D D D D CR MessBus STX D D D D D D D D D D ETX BCC Confirmation of data acceptannce PC OK 485 MessBus DLE 1 Confirmation of data acceptanc...

Страница 83: ...2H Beginning of text ETX 3 03H End of text SADR adresa 60H Prompt to send from address EADR adresa 40H Prompt to accept command at address ENQ 5 05H Terminate address DLE 1 16 49 10H 31H Confirm correct statement NAK 21 15H Confirm error statement BCC Check sum XOR RELAY TARE SIGN RELAY 1 RELAY 2 TARE CHANGE RELAY 3 4 P 0 0 0 0 Q 1 0 0 0 R 0 1 0 0 S 1 1 0 0 T 0 0 1 0 U 1 0 1 0 V 0 1 1 0 W 1 1 1 0 ...

Страница 84: ...uantity range change input signal value or input range setting E INP Input quantity is larger than permitted input quantity range change input signal value or input range setting E Hw A part of the instrument does not work properly send the instrument for repair E EE Data in EEPROM corrupted perform restoration of manufacture setting upon repeated error statement send instrument for repair E SET D...

Страница 85: ...of displayed places The setting is performed by means of a shifted ASCII code Upon modification the first two places display the entered characters and the last two places the code of the relevant symbol from 0 to 95 Numeric value of given character equals the sum of the numbers on both axes of the table Description is cancelled by entering characters with code 00 ...

Страница 86: ... VDC max load 65 Ω Connection 3 5 wire LVDT Gain 1x 2x 6x 12x Power supply 1 3 5 VAC with frequency 2 5 5 10 kHz PROJECTION Display 999999 intensive red or green 14 ti segment LED digit height 14mm Projection 99999 99999 999999 Decimal point adjustable in menu Brightness adjustbale in menu INSTRUMENT ACCURACY TC 50 ppm C Accuracy 0 02 of range 1 digit 0 05 of range 1 digit DU T Above accuracies ap...

Страница 87: ...ords s Transmission via data output RS 232 485 or via OM Link EXCITATION Adjustbale 5 24 VDC max 1 2 W isolated Fixed 10 VDC maximal load is 65 Ω T POWER SUPPLY Options 10 30 V AC DC 13 5 VA PF 0 4 ISTP 40 A 1 ms isolated fuse inside T 4000 mA 80 250 V AC DC 13 5 VA PF 0 4 ISTP 40 A 1 ms isolated fuse inside T 630 mA MECHANIC PROPERTIES Material Noryl GFN2 SE1 incombustible UL 94 V I Dimensions 96...

Страница 88: ... A D C Panel cut Side view Front view 1 1 2 2 1 2 INSTRUMENT INSTALLATION 1 insert the instrument into the panel cut out 2 fit both travellers on the box 3 press the travellers close to the panel INSTRUMENT DISASSEMBLY 1 slide a screw driver under the traveller wing 2 turn the screw driver and remove the traveller 3 take the instrument out of the panel ...

Страница 89: ... for use The guarantee shall not apply to defects caused by mechanic damage transportation intervention of unqualified person incl the user unavoidable event other unprofessional interventions The manufacturer performs guarantee and post guarantee repairs unless provided for otherwise Stamp signature WA R R A N T Y d f 60 th f th d t f l t th li t thi i t t f 60 th f th d t f l t th li t thi i t Y...

Страница 90: ... electrical equipment directive no 2014 35 EU Electromagnetic compatibility directive no 2014 30 EU The product qualities are in conformity with harmonized standard el bezpečnost EN 61010 1 EMC EN 61326 1 Electronic measuring control and laboratory devices Requirements for EMC Industrial use EN 50131 1 chap 14 and chap 15 EN 50130 4 chap 7 EN 50130 4 chap 8 EN 61000 4 11 ed 2 EN 50130 4 chap 9 EN ...

Страница 91: ...ORBIT MERRET spol s r o Vodňanská 675 30 198 00 Praha 9 Czech Republic tel 420 281 040 200 fax 420 281 040 299 orbit merret eu www orbit merret eu TECHDOK OM 502 2019 4v0 en ...