Access the CMC From the Serial Management Port
1. Identify the prerequisite and subsequent tasks you must perform in
conjunction with this procedure, to install the switch.
See the table in
“Installation Sequence” on page 20
.
2. If you have not already done so, connect a serial terminal, terminal server, or
workstation with a TIP connection to the serial management port of the CMC.
Configure the terminal or terminal emulator with these settings:
■
115200 baud
■
8 bits
■
No parity
■
1 Stop bit
■
No handshaking
3. Press the Return or Enter key several times to synchronize the connection.
You might see text similar to the following:
If you do not see the text, still progress to
4. Type
root
for the login name followed by the
root
password.
The
#
prompt is displayed.
shmm1500 login:
shmm1500 login:
root
Password:
password
#