Returning the Server to Operation
Returning the Server to Operation
These topics explain how to return the server to operation after you have performed service
procedures.
■
“Switch on PDU Circuit Breakers” on page 73
■
“Restart the Server or Host (Oracle ILOM)” on page 74
Switch on PDU Circuit Breakers
Note -
The sequence in this section, where power is restored first to the odd numbered
power supplies, and then to the even numbered power supplies, applies to factory-installed
configurations with a SPARC M8-8 or SPARC M7-8 server in the bottom of an Oracle rack.
In other configurations, where a SPARC M8-8 or SPARC M7-8 server might be installed
in a different location in the rack, power is still restored first to the odd numbered power
supplies (1, 3, 5), and then to the even numbered power supplies (0, 2, 4). See
for detailed steps for various configurations.
1.
Notify users that you are preparing to apply power to the server.
2.
Turn breakers on in the following sequence.
■
For SPARC M8-8 and SPARC M7-8 servers:
■
L2, L1, L0
■
R6, R7, R8
■
For a SPARC M7-16 server:
■
R4, R5, L5, L4
■
R0, R1, R2, L8, L7, L6
■
R6, R7, R8, L2, L1, L0
where R indicates the right PDU from the rear of the server (PDU B), L indicates the left PDU
from the rear of the server (PDU A), and the number represents the PDU group number.
Note -
As soon as PDU circuit breakers are switched on, standby power is applied, and the SP
boots.
3.
Start the system.
“Restart the Server or Host (Oracle ILOM)” on page 74
Controlling the Server and Domains
73
Содержание SPARC M7
Страница 1: ...SPARC M8 and SPARC M7 Servers Service Manual Part No E55215 06 September 2017 ...
Страница 2: ......
Страница 12: ...12 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 14: ...14 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 34: ...34 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 66: ...66 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 78: ...78 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 116: ...116 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 140: ...140 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 187: ...Install a Fan Module Switch Chassis Switch Chassis Cooling Zones on page 31 Servicing Fan Modules Switch Chassis 187 ...
Страница 188: ...188 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 216: ...216 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 226: ...226 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 234: ...234 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 242: ...242 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 252: ...252 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 268: ...268 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 296: ...296 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...
Страница 316: ...316 SPARC M8 and SPARC M7 Servers Service Manual September 2017 ...