Rotate the Drive Cage to the Service Position
Rotate the Drive Cage to the Service Position
1.
Complete these prerequisites in this order.
■
“Remove the Top Cover” on page 77
■
“Remove a Fan Module” on page 132
Remove all fan modules.
■
“Remove the Fan Tray” on page 80
2.
Disconnect the cables attached to the drive backplane, and the cable attached to
the USB board.
The cables are shown in the illustration in
“System Cable Configuration” on page 156
Note -
Depending on your server's configuration, you might not have the DVD SATA cable,or
the NVMe drive cables as seen in the illustration.
3.
Fully loosen the four screws securing the drive cage to the chassis.
82
Netra Server X5-2 Service Manual • October 2016
Содержание netra X5-2
Страница 1: ...Netra Server X5 2 Service Manual Part No E53601 03 October 2016 ...
Страница 2: ......
Страница 12: ...12 Netra Server X5 2 Service Manual October 2016 ...
Страница 20: ...20 Netra Server X5 2 Service Manual October 2016 ...
Страница 59: ...Using the Server Fault Remind Button Detecting and Managing Faults 59 ...
Страница 60: ...60 Netra Server X5 2 Service Manual October 2016 ...
Страница 123: ...Remove a Power Supply 4 Press the release tab to the left and pull on the handle Servicing Power Supplies 123 ...
Страница 128: ...128 Netra Server X5 2 Service Manual October 2016 ...
Страница 144: ...144 Netra Server X5 2 Service Manual October 2016 ...
Страница 148: ...148 Netra Server X5 2 Service Manual October 2016 ...
Страница 154: ...154 Netra Server X5 2 Service Manual October 2016 ...
Страница 180: ...180 Netra Server X5 2 Service Manual October 2016 ...
Страница 210: ...210 Netra Server X5 2 Service Manual October 2016 ...
Страница 226: ...226 Netra Server X5 2 Service Manual October 2016 ...
Страница 266: ...266 Netra Server X5 2 Service Manual October 2016 ...
Страница 274: ...274 Netra Server X5 2 Service Manual October 2016 ...