Display Faults (
show faulty
Command)
Display Faults (
show faulty
Command)
1.
Access Oracle ILOM.
“Access the SP (Oracle ILOM)” on page 28
2.
Display faulty components.
->
show faulty
Target | Property | Value
--------------------+------------------------+---------------------------------
->
If a fault is found, information about the fault is displayed under three columns:
■
Target
– A numerical subtarget of the
/SP/faultmgmt
fault management instance. For
example,
/SP/faultmgmt/0/faults/0
.
■
Property
– FRUID-type properties or parameters of the faulted component or the fault
itself. For example, FRU, class, MSGID, UUID, timestamp, and so on.
■
Value
– The value of the property. For example, the IPMI name, fault class categorization,
message ID, and so on.
This is an example of a faulty power supply:
Note -
The characters
SPT
at the beginning of the message ID indicate that the fault was
detected by Oracle ILOM.
Note -
The
component
property provides the Oracle ILOM target of the component that
faulted and might need to be replaced. You can use the information in the table of
to further identify the component that faulted.
->
show faulty
Target | Property | Value
--------------------+------------------------+-------------------------------
/SP/faultmgmt/0 | fru | /SYS/PS0
/SP/faultmgmt/0/ | class | fault.chassis.power.fail
faults/0 | |
/SP/faultmgmt/0/ | sunw-msg-id | SPT-8000-MJ
faults/0 | |
/SP/faultmgmt/0/ | component | /SYS/PS0
faults/0 | |
/SP/faultmgmt/0/ | uuid | d7d67b9b-ba67-e257-8d8d-bcef2db2
faults/0 | | 971b
/SP/faultmgmt/0/ | timestamp | 2011-09-13/15:47:41
faults/0 | |
/SP/faultmgmt/0/ | fru_part_number | 300-2304
Detecting and Managing Faults
47
Содержание netra X5-2
Страница 1: ...Netra Server X5 2 Service Manual Part No E53601 03 October 2016 ...
Страница 2: ......
Страница 12: ...12 Netra Server X5 2 Service Manual October 2016 ...
Страница 20: ...20 Netra Server X5 2 Service Manual October 2016 ...
Страница 59: ...Using the Server Fault Remind Button Detecting and Managing Faults 59 ...
Страница 60: ...60 Netra Server X5 2 Service Manual October 2016 ...
Страница 123: ...Remove a Power Supply 4 Press the release tab to the left and pull on the handle Servicing Power Supplies 123 ...
Страница 128: ...128 Netra Server X5 2 Service Manual October 2016 ...
Страница 144: ...144 Netra Server X5 2 Service Manual October 2016 ...
Страница 148: ...148 Netra Server X5 2 Service Manual October 2016 ...
Страница 154: ...154 Netra Server X5 2 Service Manual October 2016 ...
Страница 180: ...180 Netra Server X5 2 Service Manual October 2016 ...
Страница 210: ...210 Netra Server X5 2 Service Manual October 2016 ...
Страница 226: ...226 Netra Server X5 2 Service Manual October 2016 ...
Страница 266: ...266 Netra Server X5 2 Service Manual October 2016 ...
Страница 274: ...274 Netra Server X5 2 Service Manual October 2016 ...