Install the Backplane Power Cable
■
“Component Locations (Storage, Power, and Fan Modules)” on page 14
■
“Preparing for Service” on page 61
■
“Returning the Server to Operation” on page 247
Install the Backplane Power Cable
Installing a cable is a cold-service operation. You must power off the server before installing the
cable.
1.
Consider your first step.
■
If you are replacing a cable, remove the faulty or obsolete cable first, then return to this
procedure,
See
“Remove the Backplane Power Cable” on page 161
■
If you are installing a cable as part of another component's removal or installation
2.
Connect the backplane power cable to the motherboard connector.
3.
Route the cable into the cable clamp and against the chassis wall.
4.
Review this information, and complete these prerequisites in this order.
Servicing the System Cables
163
Содержание netra X5-2
Страница 1: ...Netra Server X5 2 Service Manual Part No E53601 03 October 2016 ...
Страница 2: ......
Страница 12: ...12 Netra Server X5 2 Service Manual October 2016 ...
Страница 20: ...20 Netra Server X5 2 Service Manual October 2016 ...
Страница 59: ...Using the Server Fault Remind Button Detecting and Managing Faults 59 ...
Страница 60: ...60 Netra Server X5 2 Service Manual October 2016 ...
Страница 123: ...Remove a Power Supply 4 Press the release tab to the left and pull on the handle Servicing Power Supplies 123 ...
Страница 128: ...128 Netra Server X5 2 Service Manual October 2016 ...
Страница 144: ...144 Netra Server X5 2 Service Manual October 2016 ...
Страница 148: ...148 Netra Server X5 2 Service Manual October 2016 ...
Страница 154: ...154 Netra Server X5 2 Service Manual October 2016 ...
Страница 180: ...180 Netra Server X5 2 Service Manual October 2016 ...
Страница 210: ...210 Netra Server X5 2 Service Manual October 2016 ...
Страница 226: ...226 Netra Server X5 2 Service Manual October 2016 ...
Страница 266: ...266 Netra Server X5 2 Service Manual October 2016 ...
Страница 274: ...274 Netra Server X5 2 Service Manual October 2016 ...