Table 1-5 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X4-8 Full Rack
Environmental Component
Oracle Exadata Database Machine X4-8
Full Rack
Cooling
See Also: "
(page 1-44)", and "
(page 1-45)"
•
High performance drives
Maximum: 51,200 BTU/hour (54,000 kJ/
hour)
Typical: 36,400 BTU/hour (38,400 kJ/
hour)
•
High capacity drives
Maximum: 49,110 BTU/hour (52,000 kJ/
hour)
Typical: 34,400 BTU/hour (36,300 kJ/
hour)
Air flow front-to-back (subject to actual data
center environment)
See Also: "
(page 1-44)", and "
(page 1-45)"
•
High performance drives
Maximum: Approximately 2,410 CFM
Typical: Approximately 1,700 CFM
•
High capacity drives
Maximum: Approximately 2,280 CFM
Typical: Approximately 1,600 CFM
IP Addresses
See Also: "
Address Requirements for Oracle Exadata
Database Machine
44 for Ethernet network, assuming single
cluster
Up to 36 for InfiniBand network
Network drops
See Also: "
Address Requirements for Oracle Exadata
Database Machine
Minimum of 5 network drops
External connectivity
See Also: "
Address Requirements for Oracle Exadata
Database Machine
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+ ports
12 InfiniBand ports
1.1.7 General Environmental Requirements for Oracle Exadata
Database Machine X3-2
The environmental requirements for Oracle Exadata Database Machine X3-2 depend
on the size of the system.
(page 1-12) shows the general environmental
requirements for Oracle Exadata Database Machine X3-2. The other sections in this
chapter provide detailed information.
Chapter 1
General Environmental Requirements
1-11