6.2 Electronic Pumps Controlled by UPC
The FSC3000
™
controller has been enhanced to support product restriction. The FSC3000
™
controller
requires the UPC software to meet or exceed the following versions:
Gilbarco – 6.21A or greater
Tokheim – 1.03B or greater
Wayne – 7.05C or greater
Ruby CI / Commander – Base 40 or greater
6.2.1 Configure PCT # (# = 1 to 4)
The
Configure PCT #
allows for communication to a pump console or controller to control electronic pumps
through a device called a UPC (Universal Pump Controller). The UPC can emulate up to four (4) PCTs at
once. The interface uses a UPC to control the pumps. All system configurations will be referred to as a PCT.
If using a UPC as the PCT (Electronic):
Type:
Configure PCT #
Is this a K800 PCT or PCM (Y/N)? N
Is this a UPC/DPC (Y/N)? Y
6.2.2 Configure PCT # POS #
PCT 1 Position 1 (Indicates the position being configured)
Enter Pump #: 1 (Enter the pump # that is connected to this PCT POS)
Enter Pulses Per GALLONS: 100 (set to 1000)
MAX Fuel to be dispensed per transaction: 10 (Largest tank to be filled for this
pump)
Pump Sentry Options (Y/N)? Y (Protects against pulser/wire failure)
Pump Sentry: ENABLED
Maximum time allowed for fueling (Minutes): 5
Maximum time allowed to retrieve pump handle (Seconds): 60
Maximum time allowed to detect first fueling pulse (Secs): 60
Maximum time allowed between fueling pulses (Secs): 30
Set Up Hose 1 (Y/N)? y
Enter Fueltype Code #: 1 (Enter the fuel type code)
Enter Tank #: 1 (Enter Tank number – not required for proper operation)
Clear Pump Totals (Y/N)? N
Enter Totalizer Value: 0.0 (Should set to match fueling point totalizer)
Set Up Hose 2 (Y/N)? N (Only required if pump has more than 1 grade!)
Set Up Hose 3 (Y/N)? N (Must match how the console reports hoses to the UPC)
Set Up Hose 4 (Y/N)? N
Set Up Hose 5 (Y/N)? N
Set Up Hose 6 (Y/N)? N
Set Up Hose 7 (Y/N)? N
Set Up Hose 8 (Y/N)? N
Repeat the process to configure each position that is wired to a fueling point.
6.2.3 Install PCT # POS # (PCT 1 to 4 and POS 1 to 8)
The
Install PCT # POS #
command tells the system that a PCT position will be used.
Repeat the process to install each configured position.
Doc. No.: M00-051.00 Rev.: 10
Page 41 of 181
Содержание M00-051.00 FSC3000
Страница 60: ...Doc No M00 051 00 Rev 10 Page 60 of 181...
Страница 63: ...Doc No M00 051 00 Rev 10 Page 63 of 181...
Страница 69: ...Doc No M00 051 00 Rev 10 Page 69 of 181...
Страница 99: ...Doc No M00 051 00 Rev 10 Page 99 of 181...
Страница 105: ...CFN Product Codes Code Description 96 WASHROOM FACILITIES 97 LODGING Doc No M00 051 00 Rev 10 Page 105 of 181...
Страница 129: ...Petrol Training Screens Doc No M00 051 00 Rev 10 Page 129 of 181...
Страница 130: ...CNG Training Screens Doc No M00 051 00 Rev 10 Page 130 of 181...
Страница 133: ...034 ULS Premium Diesel 010 Bio Diesel2 011 Bio Diesel5 012 Bio Diesel10 Doc No M00 051 00 Rev 10 Page 133 of 181...
Страница 181: ......