C200
S
OFTWARE
Instruction Manual C200 Part2 A1.doc
optek Danulat GmbH
•
D-45356 Essen
•
Germany
page 49
5.1.5 Configure Alarms
Configure Alarm 1
Alarms 2 and 3 configuration (and Alarms 4 and 5 if option board fitted
and analog features enabled – see Section 6.1.3) is identical to Alarm 1
configuration.
Alarm 3 can also be configured as a Wash alarm if A3: Type is set to
Wash – see following frame.
Alarm 1 Type
Select the type of alarm required:
Off
– The alarm is disabled, the alarm LED is off and the relay is de-energized
at all times.
Alarm
– The analyzer is configured using the Assign frame (following) to generate
an alarm in response to a specified high or low pH, Redox (ORP) or
process temperature sensor reading.
Status
– An alarm is generated if either a power failure or a condition that causes
any of the error messages in Table 8.1 (page 62) to be displayed occurs.
Wash
– Alarm 3 is configured to control the wash sequence.
Note.
The Wash alarm type can be assigned only to Alarm 3 and is displayed only when
the lower display line shows A3: Type.
A1: Type set to Off or Status.
A1: Type set to Alarm – continued below.
A3: Type set to Wash – see Section 5.1.5.1.
Alarm 1 Assign
Select the alarm assignment required:
Sen.A
– The analyzer activates an alarm if the pH or Redox (ORP) value of the
Sen.B
Process fluid measured by the selected sensor exceeds or drops below
the value set in the Alarm 1 Set Point parameter, depending on the type
of Alarm 1 Action selected – see next page.
Temp.A
– The analyzer activates an alarm if the temperature of the process fluid
Temp.B
measured by the selected sensor exceeds or drops below the value set in
the Alarm 1 Set Point parameter, depending on the type of Alarm 1 Action
selected – see next page.
A–B
– The analyzer activates an alarm if the difference between the Sensor A
and Sensor B readings exceeds or drops below the value set in the
Alarm 1 Set Point parameter, depending on the type of Alarm 1 Action
selected – see next page.
Note.
The Sen.B, Temp.B and A–B alarm assignment types are applicable only to dual
input analyzers and A–B is displayed only when Probe Type for each sensor is set to pH
–
see Section 5.1.3.
Continued on next page.
Config. Alarm 1
-----
A1: Type
-----
A1: Assign
-----
CONFIG. ALARMS
-----
Wash
Status
Alarm
Off
A-B
Temp.B
Sen.B
Temp.A
Sen.A
A1: Failsafe
Config. Alarm 2
A1: Assign
Config. Alarm 1
Wash Mode
Содержание CONTROL 200
Страница 95: ...C200 SOFTWARE Instruction Manual C200 Part2 A1 doc optek Danulat GmbH D 45356 Essen Germany page 73 ...
Страница 128: ...C200 SOFTWARE Instruction Manual C200 Part2 A1 doc optek Danulat GmbH D 45356 Essen Germany page 106 ...
Страница 130: ...C200 SOFTWARE Instruction Manual C200 Part2 A1 doc optek Danulat GmbH D 45356 Essen Germany page 108 8 3 PID Controller ...
Страница 131: ...C200 SOFTWARE Instruction Manual C200 Part2 A1 doc optek Danulat GmbH D 45356 Essen Germany page 109 ...
Страница 133: ...C200 SOFTWARE Instruction Manual C200 Part2 A1 doc optek Danulat GmbH D 45356 Essen Germany page 111 ...